Internal losses that reduce efficiency of a DC generator

DC Generator

DC Generator


There are four internal losses that contribute to lower efficiency of a DC generator.

Copper Losses

Copper loss is the power lost as heat in the windings; it is caused by the flow of current through the coils of the DC armature or DC field. This loss varies directly with the square of the current in the armature or field and the resistance of the armature or field coils.

Armature:Ia2 Ra
Field:If2 Rf

Eddy-Current Losses

As the armature rotates within the field, it cuts the lines of flux at the same time that the copper coils of wire that are wound on the armature cut the lines of flux. Since the armature is made of iron, an EMF is induced in the iron, which causes a current to flow. These circulating currents within the iron core are called eddy-currents .

To reduce eddy-currents, the armature and field cores are constructed from laminated (layered) steel sheets. The laminated sheets are insulated from one another so that current cannot flow from one sheet to the other.

Hysteresis Losses

Hysteresis losses occur when the armature rotates in a magnetic field. The magnetic domains of the armature are held in alignment with the field in varying numbers, dependent upon field strength. The magnetic domains rotate, with respect to the particles not held in alignment, by one complete turn during each rotation of the armature. This rotation of magnetic domains in the iron causes friction and heat.

The heat produced by this friction is called magnetic hysteresis loss.

Hysteresis

Hysteresis


To reduce hysteresis losses, most DC armatures are constructed of heat-treated silicon steel, which has an inherently low hysteresis loss. After the heat-treated silicon steel is formed to the desired shape, the laminations are heated to a dull red and then allowed to cool.

This process, known as annealing, reduces hysteresis losses to a very low value.

Mechanical Losses

Rotational or mechanical losses can be caused by bearing friction, brush friction on the commutator, or air friction (called windage), which is caused by the air turbulence due to armature rotation. Careful maintenance can be instrumental in keeping bearing friction to a minimum. Clean bearings and proper lubrication are essential to the reduction of bearing friction.

Brush friction is reduced by assuring proper brush seating, using proper brushes, and maintaining proper brush tension. A smooth and clean commutator also aids in the reduction of brush friction.

SOURCE: Handbook of electrical science Vol.2

author-pic

Edvard - Electrical engineer and programmer working in Schneider Electric, CsanyiGroup and EEP with power substations and energy distribution in residential buildings and industry facilities. Professional in AutoCAD programming and web-design. Also developer of awsome piece of electrical design software - ePlusMenuCAD. If you ain't bored yet, read more HERE.

Write for EEP, become contributor | Introduce yourself to huge number of our readers and followers


One Comment


  1. anbarasan
    Feb 07, 2012

    very good post really useful

Leave a reply!

You must be logged in to post a comment.

Tell us what you're thinking... we care about your opinion!
and oh, not to forget - if you want a picture to show with your comment, go get a free Gravatar!

Subscribe to free EEP’s updates

Subscribe to Monthly Download Updates:

(free electrical software, engineering guides and books)

Subscribe also to EE Technical Articles

Engineering Trainings

Top EEP’s Technical Writers

Technical Categories

Recommended to read and FREE download:
Theorems and laws

There are few theorems that can be applied to find the solution of electrical networks by simplifying the network itself...

What Do You Need To Know When Connecting Solar Electric System to the Utility Grid

In the past, most homes with solar electric systems were not connected to the local utility grid. It made sense...

How To Apply Capacitors To Low Voltage Power Systems

Understanding Power Factor In most modern electrical distribution systems, the predominant loads are resistive and inductive. Resistive loads are incandescent...

Close