Purpose and maintenance of transformer bushings

Transformer porcelain bushings spare parts

Transformer porcelain bushings spare parts (Pure porcelain structure, copper conductor, with low temperature rise and good heat dissipation.)


The two most common types of bushings used on transformers as main lead entrances are solid porcelain bushings on smaller transformers and oil-filled condenser bushings on larger transformers.

Transformer with 420kV RIP bushings

Transformer with 420kV RIP bushings

Solid porcelain bushings consist of high-grade porcelain cylinders that conductors pass through. Outside surfaces have a series of skirts to increase the leakage path distance to the grounded metal case. High-voltage bushings are generally oil-filled condenser type. Condenser types have a central conductor wound with alternating layers of paper insulation and tin foil and filled with insulating oil. This results in a path from the conductor to the grounded tank, consisting of a series of condensers. The layers are designed to provide approximately equal voltage drops between each condenser layer.

Acceptance and routine maintenance tests most often used for checking the condition of bushings are Doble power factor tests. The power factor of a bushing in good condition will remain relatively stable throughout the service life.

A good indication of insulation deterioration is a slowly rising power factor. The most common cause of failure is moisture entrance through the top bushing seal.

This condition will be revealed before failure by routine Doble testing. If Doble testing is not performed regularly, explosive failure is the eventual result of a leaking bushing.

This, many times, results in a catastrophic and expensive failure of the transformer as well.

SOURCE: Transformers:  Basics, Maintenance and Diagnostics – U.S. Department of the Interior  Bureau of Reclamation

author-pic

Edvard - Electrical engineer and programmer working in Schneider Electric, CsanyiGroup and EEP with power substations and energy distribution in residential buildings and industry facilities. Professional in AutoCAD programming and web-design. Also developer of awsome piece of electrical design software - ePlusMenuCAD. If you ain't bored yet, read more HERE.

Write for EEP, become contributor | Introduce yourself to huge number of our readers and followers


Leave a reply!

You must be logged in to post a comment.

Tell us what you're thinking... we care about your opinion!
and oh, not to forget - if you want a picture to show with your comment, go get a free Gravatar!

Subscribe to free EEP’s updates

Subscribe to Monthly Download Updates:

(free electrical software, engineering guides and books)

Subscribe also to EE Technical Articles

Engineering Trainings

Top EEP’s Technical Writers

Technical Categories

Recommended to read and FREE download:
Electrical Engineering Formulas

Electromagnetism The theoretical foundation for EE is electromagnetism. The theory of classical electromagnetism is based on Maxwell’s equations (see below),...

Submit site

Improve Your Bussiness Are you tired of submitting your site to Web directories that offer no real value? Make a...

Litestar

Calculation program Litestar is a lighting engineering calculation program for interiors, large areas, sports areas, roads and tunnels for irregular...

Close