Search

Premium Membership ♕

Save 50% on all EEP Academy courses with Enterprise Membership Plan and study specialized LV/MV/HV technical articles & guides.

Home / Technical Articles / 6 Adjustable Tripping Settings of a Circuit Breaker You MUST Understand

Basic tripping settings of CB

There are (at least) six basic adjustable tripping settings (functions) you really should understand in order to fully understand how circuit breaker actually works. All these adjustable functions actually shape the time-current curve of a circuit breaker and allows proper tripping according to the network parameters and also the proper coordination between upstream and downstream devices.

6 Adjustable Tripping Settings of a Circuit Breaker You MUST Know
6 Adjustable Tripping Settings of a Circuit Breaker You MUST Know

Note that modern circuit breakers (MCCB, ACB) mostly have an electronic tripping unit which is much more advanced comparing to these explained here, but the basics are the same, very same.

So, let’s start with explanation!

  1. Continuous Amps (Ir)
  2. Long-Time Delay
  3. Short-Time Pickup
  4. Short-Time Delay
  5. Instantaneous Pickup
  6. Ground Fault Pickup
Circuit breaker adjustable tripping functions
Circuit breaker adjustable tripping functions

The below time-current curve reflects one possible setup for a 1200 ampere circuit breaker with a nominal (maximum continuous ampere) rating of 1000 amps. This time-current curve will be the basis for discussing adjustable tripping settings of the circuit breakers.

Time-current curve of a circuit breaker
Time-current curve of a circuit breaker


1. Continuous Amps (Ir)

Continuous Amps (Ir) varies the level of current the circuit breaker will carry without tripping. Ir is a percentage of the circuit breaker’s nominal rating (In). Continuous amps can be adjusted from 20 to 100 percent of the circuit breaker’s nominal rating.

For example, a 1000 amp breaker can be changed from 1000 amps to 800 amps by adjusting the breaker continuous amps setting to 80%.

Continuous current [Amps]
Continuous current [Amps]

Go back to CB tripping settings ↑


2. Long-Time Delay

Long-time delay causes the breaker to wait a certain amount of time to allow temporary inrush currents, such as those encountered when starting a motor, to pass without tripping.

The adjustment is from 2.2 to 27 seconds at six times the continuous amps (Ir) setting.

As shown below, the long-time delay effects the position of an I2T slope. This means that lower levels of current will allow the breaker to remain online for longer periods of time.

Long time delay tripping settings
Long time delay tripping settings

Go back to CB tripping settings ↑


3. Short-Time Pickup

Short-time pickup is used for selective tripping. The short-time pickup function determines the amount of current the breaker will carry for a short period of time, allowing downstream protective devices to clear short-circuits without tripping the upstream device.

Short-time pickup is adjustable from 1.5 to 10 times the trip unit ampere setting (Ir).

For example, a 1000 ampere frame can be adjusted to trip anywhere from 1500 to 10,000 amps. The switch also has an “OFF” position to eliminate short-time pickup and short-time delay.

Short-time pickup used for selective tripping
Short-time pickup used for selective tripping

Go back to CB tripping settings ↑


4. Short-Time Delay

Short-time delay, used in conjunction with short-time pickup, controls the time involved in postponing a short-time pickup trip.

There are two modes: fixed time, or I2T ramp. Fixed time is adjustable from .05 to .5 seconds. The I2T ramp mode is adjustable from .18 seconds to .45 seconds, providing a short inverse time ramp.

This allows better coordination with downstream thermal-magnetic circuit breakers and fuses. A fixed instantaneous trip point of 10,000 amps trips the breaker automatically and overrides any pre-programmed instructions.

Short-time delay, used in conjunction with short-time pickup
Short-time delay, used in conjunction with short-time pickup

Go back to CB tripping settings ↑


5. Instantaneous Pickup

Instantaneous pickup is used to trip the circuit breaker with no intentional delay at any current between 2 and 40 times the breaker’s continuous ampere setting (Ir).

In this example instantaneous pickup has been set to 10 times the continuous amp setting, or 10,000 amps (10 x 1000) with a continuous amp setting of 1000 amps. In this case a higher setting would still trip at 10,000 amps due to a fixed instantaneous override of 10,000 amps which automatically trips the breaker regardless of the instantaneous pickup setting.

If the continuous amp setting had been 300 amps, setting the instantaneous pickup at 10 would make the instantaneous setting equal to 3000 amps, well below the fixed instantaneous override.

Instantaneous pickup - Used to trip the circuit breaker with no intentional delay at any current between 2 and 40 times the breaker’s continuous ampere setting (Ir)
Instantaneous pickup – Used to trip the circuit breaker with no intentional delay at any current between 2 and 40 times the breaker’s continuous ampere setting (Ir)

Go back to CB tripping settings ↑


6. Ground Fault Pickup

Ground fault pickup controls the amount of ground fault current that will cause the breaker to interrupt the circuit. The adjustment can be set from 20 to 70% of the maximum breaker rating. In compliance with NEC® 230-95 (A), no trip point setting exceeds 1200 amps.

The ground fault pickup is divided into three sections; .1s, .2s, and .4s. This feature adds a time delay of .1, .2, or .4 seconds to the breaker’s trip when a ground fault occurs.

Ground fault pickup controls the amount of ground fault current that will cause the breaker to interrupt the circuit
Ground fault pickup controls the amount of ground fault current that will cause the breaker to interrupt the circuit

Circuit breaker coordination

The ground fault pickup time delay feature is useful for circuit breaker coordination. In the following scheme, upstream breaker “A” has been set to .2s and downstream breakers “B” and “C” have been set to .1s.

The ground fault pickup time delay feature is useful for circuit breaker coordination
The ground fault pickup time delay feature is useful for circuit breaker coordination

A ground fault occurring in the circuit supplied by “B” will trip the “B” breaker without disturbing “A” or “C”.

Go back to CB tripping settings ↑

Reference // STEP 2000 – Molded Case Circuit Breakers (MCCB) by SIEMENS

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
author-pic

Edvard Csanyi

Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV/MV switchgears and LV high power busbar trunking (<6300A) in power substations, commercial buildings and industry facilities. Professional in AutoCAD programming.

49 Comments


  1. WAREZ ALI
    Jun 23, 2022

    NEED TO LEARN AND DOING BUSINESS


  2. Vincent Byrne
    Feb 27, 2022

    Just starting to get into ACB is there any other advice or information your could give or point me towards


  3. tim
    Feb 09, 2022

    Great article


  4. Kalum Prasanna
    Dec 31, 2021

    Continuos current can be adjusted between 200A to 1000 A isn,t it ? Example says its 800A is that correct ?


  5. Mike
    Oct 05, 2021

    I did’nt understand why there’s setting of 6*IR in short term overload release.


  6. Mohammed Ewais
    Aug 01, 2021

    Great


  7. DILIP KUMAR DAS
    Jul 31, 2021

    Useful information for ACB / MCCB settings.
    Thanks a Lot !


  8. Indika
    Mar 09, 2021

    Great 👍👍👍🙏🙏🙏


  9. Silviu Darie
    Jan 30, 2021

    Great presentation. Congratulations


  10. juan de la cruz ravelo
    Sep 26, 2020

    Esta información es muy completa y me ayuda a tener un conocimiento de cómo ajustar los parámetros correctamente.


  11. Engr. Juliano Osngal
    Jul 21, 2020

    Thanks the topic is 200%excellent


  12. Daniel tecleab
    Feb 16, 2020

    the information provided is very helpful for practical based and theory based lessons and has been presented in precise manner, it is what i was looking for and i will expect more edvard


  13. Saleh Farman
    Dec 17, 2019

    Dear Sir,

    Does the Direct Acting Series Trip is only build on ACB or both ACB & MCCB?

    Thank you


  14. eng. ghassan
    Oct 23, 2019

    thank a lot for all thing you always provide.
    best regards
    Ghassan


  15. Michael
    Oct 03, 2019

    Just a quick question – what exactly does The adjustment is from 2.2 to 27 seconds “at six times the continuous amps (Ir) setting” mean, i.e. what does the @ 6,000A mean exactly?


    • Jamil Ahmed Khan
      May 31, 2020

      Yes. At 6000A or some minor+/- CB will trip at pre set time.

Leave a Reply to WAREZ ALI

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

four  ⁄    =  one

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
EEP Academy Hand-Crafted Courses