In any three phase system, the line currents Ia, Ib and Ic may be expressed as the phasor sum of:

– a set of balanced positive phase sequence currents Ia1, Ib1 and Ic1 (phase sequence a-b-c),

– a set of balanced negative phase sequence currents Ia2, Ib2 and Ic2 (phase sequence a-c-b),

– a set of identical zero phase sequence currents Ia0, Ib0 and Ic0 (cophasal, no phase sequence).

The positive, negative and zero sequence currents are calculated from the line currents using:

Ia1 = (Ia + hIb + h2Ic) / 3

Ia2 = (Ia + h2Ib + hIc) / 3

Ia0 = (Ia + Ib + Ic) / 3

The positive, negative and zero sequence currents are combined to give the line currents using:

Ia = Ia1 + Ia2 + Ia0

Ib = Ib1 + Ib2 + Ib0 = h2Ia1 + hIa2 + Ia0

Ic = Ic1 + Ic2 + Ic0 = hIa1 + h2Ia2 + Ia0

The residual current Ir is equal to the total zero sequence current:

Ir = Ia0 + Ib0 + Ic0 = 3Ia0 = Ia + Ib + Ic = Ie

which is measured using three current transformers with parallel connected secondaries.

Ie is the earth fault current of the system.

Similarly, for phase-to-earth voltages Vae, Vbe and Vce, the residual voltage Vr is equal to the total zero sequence voltage:

Vr = Va0 + Vb0 + Vc0 = 3Va0 = Vae + Vbe + Vce = 3Vne

which is measured using an earthed-star / open-delta connected voltage transformer.

Vne is the neutral displacement voltage of the system.

The h-operator

The h-operator (1Ð120°) is the complex cube root of unity:

h = – 1 / 2 + jÖ3 / 2 = 1Ð120° = 1Ð-240°

h2 = – 1 / 2 – jÖ3 / 2 = 1Ð240° = 1Ð-120°

Some useful properties of h are:

1 + h + h2 = 0

h + h2 = – 1 = 1Ð180°

h – h2 = jÖ3 = Ö3Ð90°

h2 – h = – jÖ3 = Ö3Ð-90°

NOTATION
The symbol font is used for some notation and formulae. If the Greek symbols for alpha beta delta do not appear here [ a b d ] the symbol font needs to be installed for correct display of notation and formulae.
B
C
E
f
G
h
I
j
L
P
Q
susceptance
capacitance
voltage source
frequency
conductance
h-operator
current
j-operator
inductance
active power
reactive power
[siemens, S]
[farads, F]
[volts, V]
[hertz, Hz]
[siemens, S]
[1Ð120°]
[amps, A]
[1Ð90°]
[henrys, H]
[watts, W]
[VAreactive, VArs]
Q
R
S
t
V
W
X
Y
Z
f
w
quality factor
resistance
apparent power
time
voltage drop
energy
reactance
admittance
impedance
phase angle
angular frequency
[number]
[ohms, W]
[volt-amps, VA]
[seconds, s]
[volts, V]
[joules, J]
[ohms, W]
[siemens, S]
[ohms, W]
[degrees, °]
[rad/sec]

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.