Formulas

If an inductive load with an active power demand P has an uncorrected power factor of cosf1 lagging, and is required to have a corrected power factor of cosf2 lagging, the uncorrected and corrected reactive power demands, Q1 and Q2, are:

Q1 = P tanf1

Q2 = P tanf2

where tanfn = (1 / cos2fn – 1)½

The leading (capacitive) reactive power demand QC which must be connected across the load is:

QC = Q1 – Q2 = P (tanf1 – tanf2)

The uncorrected and corrected apparent power demands, S1 and S2, are related by:

S1cosf1 = P = S2cosf2

Comparing corrected and uncorrected load currents and apparent power demands:

I2 / I1 = S2 / S1 = cosf1 / cosf2

If the load is required to have a corrected power factor of unity, Q2 is zero and:

QC = Q1 = P tanf1

I2 / I1 = S2 / S1 = cosf1 = P / S1

Shunt Capacitors

For star-connected shunt capacitors each of capacitance Cstar on a three phase system of line voltage Vline and frequency f, the leading reactive power demand QCstar and the leading reactive line current Iline are:

QCstar = Vline2 / XCstar = 2pfCstarVline2

Iline = QCstar / Ö3Vline = Vline / Ö3XCstar

Cstar = QCstar / 2pfVline2

For delta-connected shunt capacitors each of capacitance Cdelta on a three phase system of line voltage Vline and frequency f, the leading reactive power demand QCdelta and the leading reactive line current Iline are:

QCdelta = 3Vline2 / XCdelta = 6pfCdeltaVline2

Iline = QCdelta / Ö3Vline = Ö3Vline / XCdelta

Cdelta = QCdelta / 6pfVline2

Note that for the same leading reactive power QC:

XCdelta = 3XCstar

Cdelta = Cstar / 3

Series Capacitors

For series line capacitors each of capacitance Cseries carrying line current Iline on a three phase system of frequency f, the voltage drop Vdrop across each line capacitor and the total leading reactive power demand QCseries of the set of three line capacitors are:

Vdrop = IlineXCseries = Iline / 2pfCseries

QCseries = 3Vdrop2 / XCseries = 3VdropIline = 3Iline2XCseries = 3Iline2 / 2pfCseries

Cseries = 3Iline2 / 2pfQCseries

Note that the apparent power rating Srating of the set of three series line capacitors is based on the line voltage Vline and not the voltage drop Vdrop:

Srating = Ö3VlineIline

NOTATION
The symbol font is used for some notation and formulae. If the Greek symbols for alpha beta delta do not appear here [ a b d ] the symbol font needs to be installed for correct display of notation and formulae.
B
C
E
f
G
h
I
j
L
P
Q
susceptance
capacitance
voltage source
frequency
conductance
h-operator
current
j-operator
inductance
active power
reactive power
[siemens, S]
[farads, F]
[volts, V]
[hertz, Hz]
[siemens, S]
[1Ð120°]
[amps, A]
[1Ð90°]
[henrys, H]
[watts, W]
[VAreactive, VArs]
Q
R
S
t
V
W
X
Y
Z
f
w
quality factor
resistance
apparent power
time
voltage drop
energy
reactance
admittance
impedance
phase angle
angular frequency
[number]
[ohms, W]
[volt-amps, VA]
[seconds, s]
[volts, V]
[joules, J]
[ohms, W]
[siemens, S]
[ohms, W]
[degrees, °]
[rad/sec]

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

One Comment


  1. ahmad
    Jan 31, 2011

    we have a 420 kva transformer and the load is about 380kva help me to find the best capasitor bank
    for this specification
    thank

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.