Formulas

If a node in a power system operating at frequency f has a inductive source reactance XL per phase and has power factor correction with a capacitive reactance XC per phase, the source inductance L and the correction capacitance C are:

L = XL / w

C = 1 / wXC

where w = 2pf

The series resonance angular frequency wr of an inductance L with a capacitance C is:

wr = (1 / LC)½ = w(XC / XL)½

The three phase fault level Ssc at the node for no-load phase voltage E and source impedance Z per-phase star is:

Ssc = 3E2 / |Z| = 3E2 / |R + jXL|

If the ratio XL / R of the source impedance Z is sufficiently large, |Z| » XL so that:

Ssc » 3E2 / XL

The reactive power rating QC of the power factor correction capacitors for a capacitive reactance XC per phase at phase voltage E is:

QC = 3E2 / XC

The harmonic number fr / f of the series resonance of XL with XC is:

fr / f = wr / w = (XC / XL)½ » (Ssc / QC)½

Note that the ratio XL / XC which results in a harmonic number fr / f is:

XL / XC = 1 / ( fr / f )2

so for fr / f to be equal to the geometric mean of the third and fifth harmonics:

fr / f = Ö15 = 3.873

XL / XC = 1 / 15 = 0.067

NOTATION
The symbol font is used for some notation and formulae. If the Greek symbols for alpha beta delta do not appear here [ a b d ] the symbol font needs to be installed for correct display of notation and formulae.
B
C
E
f
G
h
I
j
L
P
Q
susceptance
capacitance
voltage source
frequency
conductance
h-operator
current
j-operator
inductance
active power
reactive power
[siemens, S]
[farads, F]
[volts, V]
[hertz, Hz]
[siemens, S]
[1Ð120°]
[amps, A]
[1Ð90°]
[henrys, H]
[watts, W]
[VAreactive, VArs]
Q
R
S
t
V
W
X
Y
Z
f
w
quality factor
resistance
apparent power
time
voltage drop
energy
reactance
admittance
impedance
phase angle
angular frequency
[number]
[ohms, W]
[volt-amps, VA]
[seconds, s]
[volts, V]
[joules, J]
[ohms, W]
[siemens, S]
[ohms, W]
[degrees, °]
[rad/sec]

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.