Distribution Automation Handbook – Power System Protection Practice // Impedance Based Fault Location – by ABB
Distribution Automation Handbook – Power System Protection Practice // Impedance Based Fault Location – by ABB

Introduction

As utilities today concentrate on continuity and reliability of their distribution networks, fault location has become an important supplementary function in modern IEDs. These fault location algorithms typically rely on the calculation of impedance from the fundamental frequency phasors measured in the substation.

Therefore, it can be said that impedance-based methods have become an industry standard in this respect.

The reason for their popularity is their easy implementation as they utilize the same signals as the other protection and measurement functions in the IEDs.

Their performance has been proven quite satisfactory in locating short circuits, but improving further the performance in locating earth faults, especially in high-impedance earthed networks, is an on-going objective in the algorithm development. Distribution networks have certain specific features which complicate and challenge fault location algorithms.

These include, for example, non-homogeneity of lines, presence of laterals and load taps and the combined effect of load current and fault resistance.

Typical fault location algorithms are based on the assumption that the total load is tapped to the end point of the feeder, that is, the fault is always located in front of the load point. In real distribution feeders, this assumption is rarely correct. In fact, due to voltage drop considerations, loads are typically located either in the beginning of the feeder or distributed more or less randomly over the entire feeder length. In such cases, fault location accuracy becomes easily deteriorated unless somehow taken into account in the algorithm design.

The effect of the above factors on the accuracy becomes more substantial the lower the fault current magnitude in relation to the load current becomes.

In the following, basic principles of impedance-based methods are introduced, and the performance of different algorithm implementations is demonstrated using computer simulations.

Title:Distribution Automation Handbook – Power System Protection Practice // Impedance Based Fault Location – ABB
Format:PDF
Size:971 KB
Pages:24
Download:Right here | Video Courses | Membership | Download Updates
Distribution Automation Handbook – Power System Protection Practice // Impedance Based Fault Location – by ABB
Distribution Automation Handbook – Power System Protection Practice // Impedance Based Fault Location – by ABB

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

One Comment


  1. Wayan Aries d
    Nov 24, 2017

    Are there any reference for travelling wave fault locator ?

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.