Capacitor bank switching

The energy associated with re-striking due to capacitor bank switching must be assessed with the greatest care. Although rare, restriking can be a challenging task, especially for surge arresters installed near the capacitor banks.

Medium Voltage Capacitor Switching Guide
Medium Voltage Capacitor Switching Guide

In actual fact, surge arresters installed even further away, including low voltage ones, can be affected in the case of multiple restriking events. The energy that affects the surge arrester depends on the capacitance of the capacitor bank owing to the charge stored in the bank itself.

The effect of this is to increase overvoltage oscillation amplitude the instant restriking occurs. Annex G.2, standard IEEE Std C62.22-2009 “IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating-Current Systems”, provides a method for calculating the energy dissipated by the surge arrester in this situation.

Suppos that the transient overvoltage due to circuit breaker restriking during the opening operation of a capacitor bank reaches 3 p.u. and that the discharge voltage of a typical surge arrester installed on the bank or in its immediate vicinity is about 2 p.u..

The suggestion provided by the Standard is to estimate the energy discharged by a surge arrester (energy in surge arrester in kJ) as depending on the size of the capacitor bank, as described below:

Esa (kJ) = 13.3 × MVAr per phase at 60 Hz = 16.0 × MVAr per phase at 50 Hz

For example, considering the previously described 60 Hz system at Us = 13.8 kV with 6 MVAr three-phase capacitor bank, the result is:

Energy in surge arrester (kJ) = 13.3 · 6/3 = 26.6 kJ

thus, if the maximum continuous operating voltage Uc (according to IEC, MCOV or IEEE) that can be applied to the terminals of the surge arrester without impairing its characteristics in any way is:

Maximum continuous operating voltage

The result is:

Maximum continuous operating voltage

This means that there will be no problems from an energy aspect if an ABB MWD surge arrester is installed, since its energy has been tested in accordance with Standard IEC 60099-4 and is 5.5 kJ/kV.

Table 1 – Limiting inductor positions and relative benefits / disadvantages

Limiting inductor positions and relative benefits/disadvantages
Table 1 – Limiting inductor positions and relative benefits/disadvantages

Surge arresters can be installed in different positions depending on the switching device and limiting inductor. These positions are listed below:

  1. On the supply side of the switching device
  2. On the supply side of the limiting inductor
  3. Between the limiting inductor and capacitor
  4. At the ends of the limiting inductor

The benefits and disadvantages of each installation, which must be preceded by research for the purpose of coordinating the insulation of the system, are outlined in above table.

Title:Medium Voltage Capacitor Switching Guide – ABB
Format:PDF
Size:2.2 MB
Pages:52
Download:Right here | Video Courses | Membership | Download Updates
Guide To Medium Voltage Capacitor Bank Switching And Impact Of Overvoltage On The System
Guide To Medium Voltage Capacitor Bank Switching And Impact Of Overvoltage On The System

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.