Measuring Motor Displacement PF

Start measuring motor displacement power factor by selecting which of the two methods to use based on the transformer configuration supplying the 3-phase induction motor. Either method will give the same results. Method #1 is for the grounded-Y source.

How to successfully recognize and fix power quality problems
How to successfully recognize and fix power quality problems

It is simple and can be applied in most situations, since virtually all of the low voltage motors in commercial and light industrial facilities are fed from a grounded-Y source.

Method #2 is for floating sources sometimes found in heavy industrial facilities.


Method #1: Grounded-Y source

To check if the source is grounded-Y, measure voltage of each phase to ground. If the readings are equal, you can use this measurement method.


Set-up:

Clamp the current probe on any phase (with arrow on clamp pointing towards the motor). Then, attach the red voltage probe to the same phase and the black probe to ground (not to another phase).

  • Active Power: Read kW and multiply by 3: kWMOTOR = 3 × kW
  • Displacement PF: Read DPF. (Not necessary to measure kVA)
Method #1: Grounded-Y source
Method #1: Grounded-Y source

Method #2: Three-wire Source

With floating-Y, floating-delta or grounded-delta, the voltage will be different for at least one of the phase-to-ground readings. (For the floating source, the phase-to-ground voltage is unpredictable, since it depends on phase to ground capacitance).

Method #2 is known as the Two-Wattmeter method.


Set-up:

First connect the black voltage probe to any phase. Then connect the red voltage probe and the clamp (arrow towards the load) together on a second phase. Record kW1.

Then move red probe and clamp to the third phase (do not move the black probe). Record kW2. Record kVA (kVA of either phase will be more or less equal if the current unbalance is within limits).

Power Factor Using the Two-Wattmeter Method
Figure 2 – Power Factor Using the Two-Wattmeter Method

  • Active Power: KwMOTOR = kW1 + kW2 (If either kW reading is negative, as might happen on a very lightly loaded motor, it would be subtracted instead of added)
  • Apparent Power: kVAMOTOR = kVA × 1.73.
  • DPF = kWMOTOR / kVAMOTOR

Example (Two-Wattmeter):

Measurements:

  • kW1 = + 1.52
  • kW2 = + 1.74
  • kVA = 2.41

Calculations:

  • KwMOTOR = kW1 + kW2 = (+ 1.52) + (+1.74) = 3.26 kW
  • kVAMOTOR = kVA × 1.73. = (2.41) (1.73) = 4.17 kVA
  • DPF = KwMOTOR / kVAMOTOR = 3.26 / 4.17 = 0.78
Title:How to successfully recognize and start fixing power quality problems by Fluke
Format:PDF
Size:2.10 MB
Pages:32
Download:Right here | Video Courses | Membership | Download Updates
How to successfully recognize and fix power quality problems
How to successfully recognize and fix power quality problems

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.