Home / Technical Articles / AC and DC facilities in electrical station services of major power plant types

Station services switchgear in power plants

In a power plant, the electrical station services (abbreviated to SS in the following) consist of all the DC facilities from 24 to 220 V and AC facilities up to about 20 kV for controlling and supplying power to the equipment needed to keep the plant running. Hence, these auxiliary services clearly play a vital role in assuring the plant’s reliable operation.

AC and DC facilities in electrical station services of major power plant types
AC and DC facilities in electrical station services of major power plant types

Close attention must therefore be paid to requirements affecting the particular plant and the safety considerations, such as the provision of backup systems.

Table of contents:

  1. Alternating current (AC) station services
  2. Direct current (DC) station services
  3. Station services in power plants
    1. Hydro power plants
    2. Diesel power plants
    3. Gas turbine / combined-cycle power plants
    4. Conventional steam thermal power plant
    5. Combined heat and power stations
  4. Automatic station service power transfer
    1. Switchgear configuration with two circuit breakers

1. Alternating current (AC) station services

The AC services for a generating plant unit consist essentially of the station service power transformer, in most cases a medium voltage distribution network, and low voltage distribution facilities. They may include a power transformer and the necessary distribution gear fed from a separate MV network for supplying general loads, i.e. not directly related to the generating unit, and possibly for starting the units and shutting them down.

Standby power supplies are dealt with in the below technical article.

Generators applicable to high reliability requirements of healthcare and other facilities


The basic SS arrangement in a so-called unit-type system for a power plant composed of separate units is shown in Figure 1, and the corresponding layout for a bus-type system in Figure 2.

The advantages of the unit-type configuration are that the ratings for the SS distribution facilities are lower, making it easier to cope with short-circuit currents and that the units are self-contained, so enhanced availability.

Basic diagram of SS power supply fora unit-type generating plant
Figure 1 – Basic diagram of SS power supply for a unit-type generating plant

Bus-type system configurations are employed in plants with smaller generators and hence reduced SS power requirements, and have the advantage of lower capital cost. The station services of all power plants are based on these two principal arrangements.

Redundancy in the form of double busbars, cross-links between generating units, etc are possible, giving rise to a gnat many alternative layouts.

Special requirements of auxiliary systems for different types of power plants are described in the following paragraphs.

Basic diagram of bus-type station services power supply
Figure 2 – Basic diagram of bus-type station services power supply

Go back to Table of Contents ↑


2. Direct current (DC) station services

Direct current (DC) systems are used for control and monitoring purposes, but also for supplying power to DC drives and, as part of an emergency (UPS) system, via inverters to alternating-current drives. The required energy is stored in batteries, with conversion by means of rectifiers and inverters.

In normal operations, the DC loads are fed via the rectifiers. The batteries some only as a buffer in the event of shortlived high load currents or to brief interruptions in the AC supply, particularly to ensure that the generating units are shut down safely.

The DC systems employed in generating stations for providing power and for control purposes have voltages of 110 or 220 V, while the increasing use of electronics has also led to self-contained rectifier-battery systems of 24 or 48 V.  As with AC station services systems, both unit-type and busbar arrangements are possible, or a mixture of the two (e.g. 220 V as a unit system and 24 V as a busbar system for higher-level control facilities.

Redundancy needs to be provide in order to achieve the required reliability.

Typical doubled battery and charger application
Figure 3 – Typical doubled battery and charger application

Go back to Table of Contents ↑


3. Station services in power plants

3.1 Hydro power plants

In hydro power plants the station services require 1-3% of the generators rated power, depending on type and size. Most of the individual motor ratings are below 50 kW. Often the only exceptions to this are ratings of the power house crane, governor oil pumps and dewatering pumps. For this reason, medium-voltage distribution can be dispensed with.

Only in the case of long distances to outside installations such as water intake stations, or a very extensive powerhouse, is medium voltage switchgear required. The unit-type layout is preferred with unit ranges >50MW.

An uninterruptible SS power supply is not an absolute necessity. A brief interruption of up to a few minutes does not cause the turbines to trip out because the governor oil pumps are either fed from the station battery, or the governor system has an oil accumulator tank.

Nevertheless, standby power facilities (usually a diesel set) or an external supply from a separate medium-voltage network cannot be omitted, since the energy sources mentioned above are available for only a short time and power must be secured for the gates and valves.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Black Friday Deal 💥 – Save 20% on Pro Plan with code BLACKFRIDAY

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Edvard Csanyi - Author at EEP-Electrical Engineering Portal

Edvard Csanyi

Hi, I'm an electrical engineer, programmer and founder of EEP - Electrical Engineering Portal. I worked twelve years at Schneider Electric in the position of technical support for low- and medium-voltage projects and the design of busbar trunking systems.

I'm highly specialized in the design of LV/MV switchgear and low-voltage, high-power busbar trunking (<6300A) in substations, commercial buildings and industry facilities. I'm also a professional in AutoCAD programming.

Profile: Edvard Csanyi

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

  ×  7  =  21

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Save 20% with coupon BLACKFRIDAY.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.