Home / Technical Articles / Switching devices you are likely to spot in every medium voltage switchgear

MV switchgear up to and including 52 kV

Up to and including 52 kV voltage range is generally referred to as “medium voltage”. This technical article shed some light on a few devices you are likely to spot in most of the medium voltage switchgear. But, before diving into technical details, it’s a good idea to remind ourselves of important terms and definitions relating to MV switchgear.

Switching devices you are likely to spot in every medium voltage switchgear
Switching devices you are likely to spot in every medium voltage switchgear (on photo: Unigear ZS1 type 550 17,5 kV 1250A)

Let’s start this article with a few basic terms used later. After, the seven most common MV switching devices will be explained in detail, referring to ABB’s equipment as an example.


Basic terms (reminder)

Term â„– 1 – Disconnectors

Disconnectors are mechanical switching devices which provide an isolating distance in the open position. They are capable to open or close a circuit if either a negligible current is switched or if there is no significant change in voltage between the terminals of the poles.

Term â„– 2 – Isolating distances

Isolating distances are gaps of specified dielectric strength in gases or liquids in the open current paths of switching devices. They must comply with special conditions for the protection of personnel and installations and their existence must be clearly perceptible when the switching device is open.

Term â„– 3 – Switches

Switches are mechanical switching devices, which not only make, carry and interrupt currents under normal conditions in the network but also must carry for a specific time and possibly make currents under specified abnormal conditions in the network (e.g. short circuit).

Term â„– 4 – Switch disconnectors

Switch disconnectors are switches which satisfy the requirements for an isolating distance specified for a disconnector in their open position.

Term â„– 5 – Circuit breakers

Circuit-breakers are mechanical switching devices able to make, carry and interrupt currents occurring in the circuit under normal conditions, and can make, carry for a specified time and break currents occurring in the circuit (e.g. short circuit) under specified abnormal conditions.

Term â„– 6 – Earthing switches

Earthing switches are mechanical switching devices for earthing and short-circuiting circuits. They we capable of carrying currents for a specified time under abnormal conditions (e.g. short circuit).

Earthing switches are not required to carry normal operating currents.

Term â„– 7 – Fuses

Good old fuses are switching devices that open the circuits in which they we installed by the melting of one or more parts specified and designed for the purpose of breaking the current when it exceeds a given value for a sufficiently long period.

ABB's Unigear medium voltage switchgeara
ABB’s Unigear medium voltage switchgear

Table of contents:

  1. Disconnectors
  2. Switch-disconnectors
  3. Earthing switches
    1. Recognizable switch position
  4. HRC fuse links
    1. Characteristic current values for HRC fuse links
    2. Selecting fuse links for specific conditions
  5. Short-circuit current limiter
  6. Circuit-breaker
    1. Vacuum circuit breakers
    2. SF6 circuit breakers
  7. Vacuum contactors

1. Disconnectors

The classic design of the disconnects is the knife-contact disconnector (see Figure 1). It has become less common with the increasing use of withdrawable circuit-breakers and switch-disconnectors. This functional principle is more frequent in gas-insulated switchboard (GIS) technology.

The blades of knife-contact disconnectors installed in en upright or hanging position must be prevented from moving by their own weight.

Disconnectors can be actuated manually and, in remotely operated installations, by motor or compressed-air drives.

Medium voltage knife-contact disconnector
Figure 1 – Medium voltage knife-contact disconnector

Go back to Contents Table ↑


2. Switch-disconnectors

Switch-disconnectors are increasingly being used in distribution networks for switching cables and overhead lines. Switch-disconnectors in connection with HRC fuses are used for protection of smaller transformers. Switch-disconnectors are switches that in their open position meet the conditions specified for isolating distances.

General purpose switches can make and break all types of operating currents in fault-free operation and in the event of earth faults. They can also make and conduct short-circuit currents.

NALF switch-disconnector
Figure 2 – NALF switch-disconnector

Knife-contact switch-disconnectors as per Figure 2 and rod-type switch-disconnectors as shown in Figure 3 are actuated in two ways, depending on their type:

  1. “Snap-action mechanism”, also referred to as toggle-spring mechanism. With this type of operating mechanism, a spring is tensioned and released shortly before the operating angle is completed and its release force actuates the main contact systems. This is used for both closing and opening.
  2. “Stored-energy mechanism”. This mechanism has one spring for closing and a second spring for opening. During the closing operation, the opening spring is simultaneously tensioned and latched. The stored energy for the opening operation is released by magnetic type or the striker pin of the HRC fuse.
The rod-type switch-disconnector is particularly suitable for the design of compact switchgear because the knife-contact switch-disconnector requires a greater depth for the switching zone because of the projecting contact blade in its open state.

The rod-type switch-disconnectors also enable very small phase spacings without phase barriers.

Rod-type switch-disconnector with fuse assembly
Figure 3 – Rod-type switch-disconnector with fuse assembly

Go back to Contents Table ↑


3. Earthing switches

Earthing switches are installed in switchgear primarily near cable sealing ends, i.e. before the main switching device. However, earthing switches are often specified also for busbar earthing, for example in metering panels. It the main switching device is a switch-disconnector, the earthing switch and the switch-disconnector will often be on a common base frame (Figure 4).

Every earthing switch must be capable of conducting its rated short-time current without damage.

Arrangement of earthing switches on a switch-disconnector base frame
Figure 4 – Arrangement of earthing switches on a switch-disconnector base frame

“Make-proof” earthing switches are also capable of making the associated peak current at rated voltage. For safety reasons, make-proof earthing switches are recommended with air-insulated switchgear because of possible faulty actuations.

In gas-insulated switchgear (GIS), the earthing of a feeder is often prepared by the earthing switch and completed by closing the circuit-breaker. In this case, a separate make-proof earthing switch is not required.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Black Friday Deal đź’Ą – Save 20% on Pro Plan with code BLACKFRIDAY

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Edvard Csanyi - Author at EEP-Electrical Engineering Portal

Edvard Csanyi

Hi, I'm an electrical engineer, programmer and founder of EEP - Electrical Engineering Portal. I worked twelve years at Schneider Electric in the position of technical support for low- and medium-voltage projects and the design of busbar trunking systems.

I'm highly specialized in the design of LV/MV switchgear and low-voltage, high-power busbar trunking (<6300A) in substations, commercial buildings and industry facilities. I'm also a professional in AutoCAD programming.

Profile: Edvard Csanyi

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

8  +  1  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Save 20% with coupon BLACKFRIDAY.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.