Gas engine power plant equipment

This document covers the types of machinery used in the 33MW gas engine power plant, the operating and controlling of these machines, transformer, troubleshooting, switchyards, and its protection systems, what equipment is placed in which zone, how the equipment has been synthesized, etc. The scope will be limited to only this type of power generation and transmission system.

Machinery used in power generation and substation of 33MW gas engine plant
Machinery used in power generation and substation of 33MW gas engine plant (photo credit: summitpowerinternational.com)

Control and Safety Zone

The generating set can be operated in automatic or manual mode. The control mode selection is made with the “generating set control” switch on the manual control unit. In automatic mode, the control system selects the engine and generator control methods according to the “parallel with grid” signal.

In manual mode, the engine and generator control modes are selected with switches on manual control unit. Some control modes are enabled only when the generating set is in parallel with the grid.

Parallel operation

If the generating set is in parallel with the grid, the grid will determine the frequency and voltage. Any fluctuation in grid voltage or frequency is followed by the generating set. An increase or decrease in the output of the generating set does not affect the network frequency or voltage, provided that the power plant is relatively small compared to the total network capacity.

Parallel operation requires that the generating set is synchronized with the grid.


Island operation

In island operation mode, the power plant feeds an isolated network. The control system of the power plant controls the frequency and voltage in the network.

Control Room of MNPP
Control Room of MNPP

Control functions

The main functions of the control system are:

  1. Start and stop of the generating set
  2. Synchronization
  3. Engine speed and load control
  4. Generator output control
  5. Control of auxiliary systems
  6. Monitor and alarm handling
  7. Safety functions, such as start blocking, shutdown and load reduction.

The generating set can be controlled in automatic or manual mode. In automatic mode, which is the normal operating mode, the control system takes care of start and stop, loading and unloading, and generator output control.

In manual mode, the loading and unloading as well as the generator output control must be done manually by the operator. The safety functions, such as checking of the start conditions, work in the same way as in automatic mode.


Engine Starting Condition

Engine start is enabled when the following starting conditions are to be met.

  1. Lube oil pressure >0.6 Bar
  2. HT- water temperature >450C
  3. Engine speed=0
  4. Valve power supply>18vdc
  5. Safety wire ok
  6. Turning gear disengaged
  7. External start block
  8. WECS ready for start
  9. Exhaust gas ventilation
  10. Engine is not running
  11. Stop command inactive
  12. Shutdown alarm inactive
  13. Tripping alarm inactive
  14. Earthing disconnector open
  15. Breaker truck in service
  16. PLC- WECS communication

Automation System

The Engine Control System is an engine-mounted distributed system. The various electronic modules are dedicated to different functions and communicate with each other via a CAN data bus. All parameters handled by the Engine Control System are transferred to the operator interface and the plant control system.

Its features are:

  1. Easy maintenance and high reliability due to rugged engine-dedicated connectors, CIB´s (cabling interface boxes) and high quality cables
  2. Less cabling on and around the engine
  3. Easy interfacing with external system via a data bus
  4. Digitized signals giving immunity from electromagnetic disturbance
  5. Built-in diagnosis for easy troubleshooting
Cabling Interface Boxes (CIB)
Cabling Interface Boxes (CIB)

It is the Work Station of the Power house which incorporates the following major control units:

  • PLC (Programmable Logic Controller)
  • WOIS (Wartsila Operator Interface System)
  • WISE workstation
  • CRP (Control Relay Panel)
  • Energy Metering Panel
  • CFA901 Panel
  • CFC Panel
  • Auto-Synchronizer
  • Differential Relay
  • Distance Relay
  • U/f Relay
  • AVR (Automatic Voltage Regulator)
  • DC Charger Panel
  • Speed droop control

PLC (Programmable Logic Controller)

The programmable logic controller (PLC) system is the core of the control system. The PLC system includes a PLC for each generating set, and a common PLC. Each PLC includes a central processing unit (CPU), which contains the control functions, and a number of I/O cards for collecting and transmitting process signals.

The PLC system controls the operation of the generating sets and some of the auxiliaries. It collects data, executes controls, generates alarms and performs measurement scalings for the WOIS terminal.

PLC Configuration
PLC Configuration

The main control functions of the generating set PLC are engine start and stop, engine speed and load control, generator output control, synchronization and control of auxiliary systems. The engine speed is controlled by the PLC together with the engine control system.

The common PLC collects data and controls operations that are common for the generating sets in the power plant. The WOIS reads values from the PLC memory. Control commands and setting values from the WOIS workstation are automatically transferred to the PLC.

The PLC system consists of one common PLC, one engine vice PLC and one WECS per Gen-set and one operator’s station. For this system Ethernet is used for communication between the PLCs and the operation’s station. The WECS system controls and monitors the engine while the PLC controls and monitors engine auxiliaries and common systems.

The WECS and PLC system collect and scale data from the inputs and sends the data to the operator’s station through the Ethernet.

Title:Machinery used in power generation and substation of 33MW gas engine power plant – Saiful Islam, Department of Electrical and Electronics Engineering, IUBAT- International University of Business Agriculture and Technology
Format:PDF
Size:9.5 MB
Pages:116
Download:Right here | Video Courses | Membership | Download Updates
Machinery used in power generation and substation of 33MW gas engine plant
Machinery used in power generation and substation of 33MW gas engine plant

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount đź’Ą - Save 50% on all 90+ video courses with Enterprise Membership plan.

More Information

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

  ×  3  =  3

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Save 20% with coupon BLACKFRIDAY.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.