Home / Technical Articles / My worst experience in the maintenance and supervision of medium voltage substations

Estimated Study Time: 21 minutes

Operational and maintenance hazards

While there are various voltage levels applicable across the globe depending upon the usability, the category of Medium Voltage remains one of the most critical voltage group comprising primary distribution or sub-transmission category of power supply at the range of 2 to 35 kV. This is the range either used to feed in the bulk consumers directly or facilitate the secondary distribution to small retail consumers over a large area after a suitable stepping down of voltage via MV substations.

My worst experience in the maintenance and supervision of medium voltage substations
My worst experience in the maintenance and supervision of medium voltage substations (on photo: Taulihawa 33 kV Substation switchyard)

Since breakdowns in these substations come with an evident impact of power failure over a large consumer group, proper supervision and maintenance are mandatory to keep the breakdown time and the probability of safety hazards to a minimal value.

In this article, I will skip the basic introduction of major components of substation and try to emphasize various practical aspects of operational and maintenance hazards. I’ll try to present my worst experience I have had as a maintenance engineer working in MV substation.

Two fully operational local electricity utility-owned substations 33/11 kV, capacities 11MVA, and 24 MVA in Kapilbastu district of Nepal, established in the year 1987 and 1993, are taken as reference for the explanation. They consist of ten 11 kV outgoing primary distribution lines and are responsible for the electrifying approximate area of 2000 km2 of dense residential as well as some industrial consumers.

Table of contents:

  1. Worst experience in switchyard
  2. Problems with power transformers
  3. Issues with station transformer and battery room
  4. Abnormalities in switchgear and protection units
  5. Issues with drainage and cable trench
  6. Summary

1. Worst experience in the switchyard

Switchyard is a part of a substation that houses the components like disconnecting switches, lightning arrestors, instrumentation transformers, breakers, busbar, etc. for facilitating the incoming and/or outgoing feeders with the power transformer.

Prone to high voltage contacts and potential difference, this area is usually attended with proper safety and precautions by well-trained technicians only. Despite that, accidents happen one way or another.

The accident that will be discussed here is step potential. Although it is well-heard terminology around the electrical fraternity, step potential is still an enigma in terms of on-field usability.

33/11 kV 24 MVA newly upgraded Power transformer and poorly maintained switchyard at Jeetpur Substation, Nepal
Figure 1 – 33/11 kV 24 MVA newly upgraded Power transformer and poorly maintained switchyard at Jeetpur Substation, Nepal

The use of rocks and gravel in and around the switchyard is common to reduce step and touch potential and keep them tolerable when operators are in the switchyard. However, the presence of weeds, grasses, algae, etc. tends to compromise that to a great extent. As they trap more moisture than usual, suddenly, the probability of getting electrocuted is far higher than in standard stone or graveled surface.

In this substation, there have been multiple cases in which a poorly maintained and wet switchyard area has caused the operator to feel the electric shock. There were seriously injured operators in cases during damp weather and the electrical shock accidents nearby trench water.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know!Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Bishal Lamichhane - Author at EEP-Electrical Engineering Portal

Bishal Lamichhane

Electrical Engineer (B.E Electrical, M. Sc Engineering) with specialization in energy systems planning. Actively involved in design and supervision of LV/MV substations, power supply augmentations and electrification for utilities and bulk consumers like airports and commercial entities. An enthusiast and scholar of power systems analysis.
Profile: Bishal Lamichhane

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.