Home / Download Center / Electrical Engineering Books and Technical Guides / Relay control and protection guides / Earth fault protection functions for long cable feeders in compensated networks

Network fault situations

There are two types of faults in the network. First, we have symmetrical faults. These faults are easy to calculate because network can be translated to a simple single-phase equivalent circuit. Symmetrical fault is a three-phase short circuit. Secondly, we have asymmetrical faults. These faults are more common than symmetrical faults.

Earth fault protection functions for long cable feeders in compensated networks
Earth fault protection functions for long cable feeders in compensated networks (photo credit: Anord Mardix)

The most common fault causing asymmetry is an earth fault. When faults are asymmetrical, network can no longer be transformed to a single-phase equivalent circuit and the whole network has to be treated as a three-phase circuit in its original form.


Symmetrical faults

Symmetrical fault is a very rare situation. As mentioned before, a three-phase short circuit is a symmetrical fault. Although this type of fault is very rare, it has to be taken care of, because it’s the most severe accident the power delivery system will face.

One of the common three-phase short circuits is generator fault. The fatality is caused by very big fault current. Big current is produced, because limiting inductances are very small. The fault starts from the subtransient current, which leads to the steady-state fault current values. Fault detection and clearing has to be very fast in order to limit disturbances to the power system.

Further reading:

Symmetrical components theoretical and real-world examples for relay engineers


Asymmetrical faults

More often occurring fault is asymmetrical fault. When fault is asymmetrical, fault currents and voltages are not equal at different phases. There are two main types of asymmetrical faults: shunt type and series type faults. Shunt type fault is a connection between two network elements. Series type means broken connection at the conductor.

The most common asymmetrical fault is an earth fault. Asymmetrical fault indicates itself easily and from the phase values it is easy to acquire what type of asymmetrical fault it is.

The studies of the network’s asymmetrical faults are important because of the network protection. Studies are usually carried out by the method of the symmetrical components.


Basic theory and data of earth fault

Earth fault is a situation where non-earthed, live part of the network is connected to the earth trough relatively low impedance. It can be a permanent fault, which requires the personnel to rectify the fault situation, or it can be a transient fault, which can be managed via automatically controlled protection system.

Critical issue at earth fault is the magnitude of fault resistance. If magnitude is relatively high, electricity supply can be continued even if the fault is permanent.

Four basic types can classify earth fault types. These types are shown in the figure 1.

The simplest type is single-phase to earth fault as shown in point 1. This is most commonly caused by wire drop. Second alternative is a 2-phase earth short circuit as shown in point 2. In this fault type, two different phases are short circuited together with the earth. Third alternative is a double earth fault, where two different phases are simultaneously connected to the earth at the different locations.

This alternative is shown in point 3. Fourth fault type is cut wire, where load side is connected to the earth as shown in point 4.

Illustration of different types of earth faults
Figure 1 – Illustration of different types of earth faults

Most common reasons to earth faults are, for example, arcs during lighting, trees, which have fallen to conductors; and animals, which are moving near live wires. It is usual that during the earth fault there are also some other faults.

Harmful effects of the earth fault can be measured by two alternative ways. First of all, you have to measure whether the fault is fatal to human beings. Second, you have to measure how harmful the fault is to the property. It is estimated that 80 – 90 % of the faults in the MV network are earth faults.

In some cases, earth faults may lead up to more complex situations like 2-phase earth faults. Although the number of earth faults is large, they are usually temporary. Today’s relay technology has also improved the situation.

When modern protection relays have artificial intelligence, they normally are able to reclose network after the arc is cleared.


Basic measurements at fault situation

Basic measurements during the faults are carried out with voltage or current transformers. Also combination is possible. Transformers are used, because the values are too high to be measured directly. Both magnitude and and values are normally compared to known healthy state values. If any changes occur, needed operations are carried out.

An earth fault situation at the compensated network is always challenging for feeder protection. When determining values for protection, many variables have to be known. Length of cable and type of cable are some issues to be mentioned.

In the earth fault calculations the network is simplified to a partial network, which contains only crucial components. This makes calculations and logical deduction much easier.

Title:Earth fault protection functions for long cable feeders in compensated networks – Atte Hietalahti at University Of Vaasa, Faculty Of Technology, Electrical And Energy Engineering
Format:PDF
Size:1.9 MB
Pages:94
Download:Right here | Video Courses | Membership | Download Updates
Earth fault protection functions for long cable feeders in compensated networks
Earth fault protection functions for long cable feeders in compensated networks

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.