Power systems exposed to ashfalls

Electricity is the ‘life blood’ of modern society. Increasing demand for electricity has been driven by population growth and increasing use of electrically powered technologies. Electricity supply is arguably the most essential contemporary infrastructure, especially considering the dependencies of other infrastructure groups on electric power to maintain functionality.

Vulnerability of electric power systems to volcanic ashfall hazards
Vulnerability of electric power systems to volcanic ashfall hazards (on photo: Volcanic Ash Cleaning at Butong Substation; credit: Batangas 1 Electric Cooperative, Inc.)

Given that 9% of the world’s population is estimated to live within 100 km of a historically active volcano, and many of these areas are experiencing significant population and economic growth, their exposure and vulnerability to the impacts of volcanic hazards is increasing.

Effective disaster risk reduction and infrastructure management thus makes it imperative that system operators understand the potential impacts from natural disasters and take the necessary precautions to avoid unintended interruptions.

Although pyroclastic flows and surges, sector collapses, lahars, and ballistic blocks are the most destructive and dangerous of explosive eruption products, ashfall is the most widespread volcanic phenomenon.

Volcanic ash is the product of explosive volcanic eruptions and is composed of pulverised fragments of rock, minerals, and glass (SiO2) with a particle diameter smaller than 2 mm. Fine-grained ash (defined here as <1 mm particle diameter), can be dispersed large distances by winds. Even in small eruptions, thousands of square kilometres may be impacted by ashfalls.

Extensive, above-ground, corridor systems of electrical apparatus used in power generation, transformation, transmission, and distribution often stretch hundreds to thousands of kilometres, making them highly exposed to such ashfalls.

This high level of exposure emphasises the need to understand the vulnerabilities of power systems in both proximal and distal locations.

Schematic diagram illustrating some of the interdependencies between critical infrastructure systems
Figure 1 – Schematic diagram illustrating some of the interdependencies between critical
infrastructure systems

Volcanic ash can cause disruption to electricity generation and supply in the following five ways explained below:


Way #1

High voltage (HV) insulators (porcelain, glass or composite) are electrical hardware designed to mechanically support and electrically isolate energised lines or apparatus from earthed (bonded with the ground) structures such as steel towers or wooden poles.

During humid conditions such as light rain, fog, or mist, wet deposits of volcanic ash on insulators can initiate a leakage current (small amount of current flow across the insulator surface) that, if sufficient current is achieved, can cause ‘flashover’ (the unintended electrical discharge around or over the surface of an insulator).

If the resulting short-circuit current is high enough to trip the circuit breaker then disruption of service will occur. The presence of leakage current is due to the electrical conductivity of the wet ash, which is influenced by:

  1. Moisture content,
  2. Soluble salt content,
  3. Compaction and, to a lesser extent,
  4. Grain size

Ash-induced flashover on or across external insulation (bushings) for power transformers can burn, etch or crack the bushings irreparably and potentially damage the internal components (e.g. windings) of the transformer.


Way #2

Controlled outages of vulnerable nodes (e.g. generation facilities and/or substations) or circuits until ashfall has subsided or for offline (de-energised) cleaning of equipment.


Way #3

The hardness and angularity of volcanic ash make it highly abrasive. Volcanic ash can accelerate normal wear by eroding and scouring metallic apparatus, particularly moving parts such as water and wind turbines at generation sites and cooling fans on power transformers.

Cleanup of tephra from roof in progress (left), and abrasion damage to surface coating on roof (right)
Cleanup of tephra from roof in progress (left), and abrasion damage to surface
coating on roof (right)

Way #4

The high bulk density of some volcanic ash deposits can cause line breakage due to ash loading. This is most hazardous when the ash and/or the lines are wet and usually following at least 10 mm of ashfall. Fine-grained ash adheres to lines and structures (e.g. wooden poles and steel towers) most readily.

Volcanic ash may also load overhanging vegetation, causing it to fall onto lines which can bridge (make contact between) phases (lines) or cause line breakage and/or damage to structures.

Snow and ice accumulation on lines and overhanging vegetation further exacerbates the risk.

Recommended reading:

Power Plant Horror Stories – The Loss Of a Generator


Way #5

Ash ingress can block air intakes causing a reduction of air intake quality and quantity for turbines and cooling and heating, ventilation, and air-conditioning (HVA) systems at generation sites and substations. This may lead to a reduction in efficiency, precautionary shut-down (to avoid damage), damage, or even failure.

Volcanic ash could potentially abrade, clog, and corrode thermal turbines and control systems following ingestion, although these impacts have not been recorded.

This thesis provides an overview of the recorded impacts to power systems from volcanic eruptions since 1980. We have compiled data from existing literature, personal communications with system operators during meetings and semi-structured interviews, and field observations from around the world to summarise electricity system performance following ashfalls and successful mitigation strategies.

Given the lack of existing data, a fragility function was developed to provide an estimate for the likelihood of insulator flashover at different thicknesses of wet or dry ash.

This study ultimately aims to inform the volcanological, hazard mitigation and electrical engineering communities of the potential adverse impacts arising from ash contamination and provide best-practice and impact-specific mitigation advice.


Research context

Over the past 15 years our international research group led by the University of Canterbury and GNS Science, New Zealand has aimed to undertake a sustained and systematic approach to volcanic impact assessment in critical electrical power infrastructure.

Meetings and interviews were carried out with infrastructure managers, and operations and maintenance staff at affected facilities. The interviews followed an extensive group of prompt questions that were used to steer the conversation, and touched upon the main topics of interest for research, including:

The general impacts of ashfall on the sector; actions taken in response to ashfall; ash clean-up operations; emergency management plans; and interdependency issues.

Title:Vulnerability of electric power systems to volcanic ashfall hazards – John Blackburn Wardman; A thesis submitted in partial fulfilment of the requirements for the degree of Doctor of Philosophy in Hazard and Disaster Management at the Natural Hazards Research Centre, University of Canterbury
Format:PDF
Size:27.7 MB
Pages:441
Download:Right here | Video Courses | Membership | Download Updates
Vulnerability of power systems to volcanic ashfall hazards
Vulnerability of power systems to volcanic ashfall hazards

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.