Home / Download Center / Electrical Engineering Books and Technical Guides / Electricity generation, t&d guides / Modeling and analysis of external balanced and unbalanced faults (symmetrical components)

Analysis of AC power systems

The analysis of three-phase AC power systems is greatly simplified if the system is assumed perfectly balanced. The three-phase system can then be modeled and analyzed on a per-phase basis because knowledge of voltages and currents in one phase allows us to calculate those in the other two phases where they differ by ±120° phase displacement from those of the known phase.

Modeling and analysis of external balanced and unbalanced faults (symmetrical components)
Modeling and analysis of external balanced and unbalanced faults (symmetrical components)

However, in practical three-phase power systems, there are a number of sources of unbalance which can be divided into internal and external sources. Internal sources of unbalance are those due to the inherent small differences in the phase impedances and susceptances of the three-phase power plant such as overhead lines and transformers.

Three-phase generators, however, produce, by design, a balanced set of three-phase voltages. External sources of unbalance are those that impose an unbalanced condition on the power system network such as the connection of unbalanced three-phase loads or single-phase loads, to a three-phase power system, the occurrence of unbalanced short-circuit and open-circuit faults.

These external conditions create unbalanced voltages and currents in the three-phase network even if this network is balanced in terms of impedance and susceptance elements.

The modeling and analysis of external balanced and unbalanced faults are the core topic of this guide.

The analysis of unbalanced short-circuit and open-circuit faults in practical power systems makes extensive use of the theory of symmetrical components. Fortescue proposed this general theory in a famous paper in 1918. It applies to a system of N unbalanced phasors, including the case of three unbalanced phasors representing three-phase power systems.

Offshore wind farm and sequence equivalents
Offshore wind farm and sequence equivalents: (a) typical layout of a 128 MW wind farm (64 generators) and (b) sequence equivalents at collector busbar (boundary node(s))

The theory enables the transformation of three unbalanced phasors into a three-set of balanced phasors called:

  1. Positive phase sequence (PPS),
  2. Negative phase sequence (NPS), and
  3. Zero-phase sequence (ZPS) phasors.

This property presents an extremely powerful analysis tool that enables the formation of three separate and uncoupled equivalent networks called the PPS, NPS, and ZPS networks provided that the three-phase power system network in physical phase terms is internally balanced.

The types of external unbalanced conditions imposed on the actual three-phase network determine the methods of connection of these sequence networks.

This guide introduces the theory of symmetrical components, the definitions of sequence networks, the methods of connecting these networks for different fault types, and the analysis of sequence and phase currents and voltages for various conditions of external unbalances that may be imposed on the three-phase power system network.

Short-circuit analysis & calculations

Short-circuit analysis is carried out in electrical power utility systems, industrial power systems, commercial power systems, and power station auxiliary systems. Other special applications are in concentrated power system installations onboard military and commercial ships and aircraft. Short-circuit calculations are generally performed for a number of reasons.

These are briefly described in this guide.


Characterization of faults

Because they are unbalanced, one-phase open-circuit and two-phase open-circuit faults are characterized by the negative and zero phase sequence voltages and currents they generate at the fault location and elsewhere in the power system particularly at substations where electrical machines are connected.

Machines are vulnerable to damage by overheating due to excessive negative phase sequence currents flowing into them.

Short-circuit faults are characterized by the short-circuit current and its components. These are the AC or symmetrical root mean square (rms) short-circuit current, DC short-circuit current or DC time constant or X/R ratio, and the overall asymmetrical short-circuit current.

Title:Modeling and analysis of external balanced and unbalanced faults (symmetrical components) – Nasser D. Tleis BSc, MSc, PhD, CEng, FIEE
Format:PDF
Size:536 KB
Pages:46
Download:Here 🔗 (Get Premium Membership) | Video Courses | Download Updates
Modeling and analysis of external balanced and unbalanced faults (symmetrical components)
Modeling and analysis of external balanced and unbalanced faults (symmetrical components)

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.