Home / Technical Articles / The mystery of nuisance tripping incidents in transformer protection that worry engineers

Estimated Study Time: 29 minutes

Transformer Failure Incidents

This technical article deals with transformer failure incidents due to nuisance tripping caused by various design flaws, operational conditions, or improper protection relay settings. The focus is on differential protection and ground protection, as they account for a considerable number of false tripping.

The mystery of nuisance tripping incidents in transformer protection that worry engineers
The mystery of nuisance tripping incidents in transformer protection that worry engineers

I will try to explain two different case studies of primary substation 132/66 kV ∆/∆ and investigate the incident of feeders breakers tripped open although most of the loads were disconnected, and what went wrong and caused the transformers to go out of service.

Table of Contents:

  1. Introduction to Power Transformers
  2. Transformer Types
    1. Applications that Impact Transformer Protection
    2. Transformer Failure Statistics
  3. Transformer Protection
    1. Differential Protection
    2. Ground Fault Protection
  4. Case Studies

1. Introduction to Power Transformers

Transformers are electrical devices that transfer power between two circuits at different voltage and current values using the principle of induction discovered by Faraday in 1831. Devices that are based on the Faraday law like inductors used to be in laboratories till the AC was launched near the end of the 19th century.

The development of the AC power system and transformers almost occurred at the same time because they belong to they are interrelated.

The first practical transformer was invented by the Hungarian engineers Karoly Zipernowsky, Otto Blathy, and Miksa Deri in 1885 who worked for the Hungarian Ganz factory. The transformer core was made of toroidal iron wires, and its primary voltage was a few kilovolts while its secondary voltage rating was 100 volts. It was utilized to supply electric lighting applications.

Transformers vary in types, rating, and design to suit the different connected load types, but they follow the same principle of operations and they do have the same construction (more or less).

A 1928 air-cooled three-phase transformer (4,000 A/13.2 kV) manufactured by CFTH in Saint-Ouen, France
Figure 1 – A 1928 air-cooled three-phase transformer (4,000 A/13.2 kV) manufactured by CFTH in Saint-Ouen, France (photo credit: think-grid.org)

In the following, a list that contains most transformer components could be identified:

  • Magnetic circuit: It consists of a core and yoke that provides a path for magnetic flux.
  • Electric circuit: It is the primary and secondary winding that form the transformation voltage ratio. Transformers are categorized as shell type or core type according to the primary/secondary winding arrangement.
  • Dielectric circuit: It is composed of insulation used in different places within transformers.
  • Tank and accessories: Accessories differ from transformer to transformer based on the specifications and applications. They include conservator, breather, explosion vent, radiator, bushings, and many others.

Transformers are prone to nuisance tripping as a result of design flaws, operational conditions, improper relay settings, or otherwise. Transformers are a major component of substations and many times it is not affordable to have accidental outages, especially for bulk substations that serve large areas.

The nuisance tripping incidents are unwanted events and it is helpful to plan with the help of past case studies in a similar field. In this article, the focus is on differential protection and ground protection, as they account for a considerable number of false tripping. Particularly, the ground protection mentioned in this article is for an ungrounded system that has its application in a special transformer configuration as will be elaborated later.

The main principles are explained briefly and two case studies are discussed to highlight what went wrong and caused the transformers to go out of service.

Go back to Contents Table ↑


2. Transformer Types

Many classifications exist for transformers that are based on different criteria. The transformers are classified according to functionality (step-up/down), insulation (oil or air), indoor/outdoor, and some other categories. That being said, it is common in the industry to have two transformer types: distribution transformers and power transformers (see Figures 2a and 2b).

Figure 2a – Power transformer

Power Transformer
Figure 1a – Power Transformer

Figure 2b – Distribution transformer

Distribution transformer
Figure 2b – Distribution transformer

The main features of each type are listed in Table 1 below.

Oil is a surrounding medium that acts as an insulating and heat transfer medium to protect the core and coil structure. A liquid preservation system is used to protect the contained oil and to prevent its contamination from the surrounding atmosphere. The purity of the insulating medium (oil) becomes increasingly important at higher voltages due to the electrical stress exerted on the oil.

Different liquid preservation systems exist that apply for different ratings and applications. The following are common liquid preservation systems used in industry:

  • Sealed tank
  • Positive-pressure inert gas
  • Gas-oil seal
  • Conservator tank

Table 1 – Transformer Types in Power Grids

BasisPower TransformerDistribution Transformer
SizeLarger in size with complex installationSmaller in size and flexible installation
OperationStep-up/down (generation & transmission)Step down (distribution)
LoadAlways operates at full low 90-100 %Varying load
Rating33 kV, 66 kV, 110 kV, 200 kV, & 400 kV (generally over 200 MVA)230 V, 400 V, 3.3 kV, 6.6 kV, & 11 kV (generally less than 200 MVA)
Efficiency100 % at full load100 % at 50-70 % load

Go back to Contents Table ↑


2.1. Applications that Impact Transformer Protection

A flashover in an off-load tap changer is of a failure type that could be repaired in the field, but if it develops into a winding failure, it surely needs a repair in a specialized facility. Consequently, a special protection function that senses the tap changer fault is important.

Moreover, substantial external faults fed by transformers exert so much mechanical stress and thermal stress against the transformer winding that along through fault can put the transformer internal components at great risk. This mandates a fast clearing for a close-in external fault is desirable. Transformers that are readily replaceable do no need advanced protection schemes.

Occasionally, transformers protection functions cover external buses and cables, and faults in these zones expose personnel to arc flash hazards, so slow clearing protection is not acceptable.

Recommended Reading – How do faults develop in HV transformer?

How do faults develop in a HV transformer and why condition monitoring is important

Fires in indoor transformers could put the facility’s safety as well as personnel safety at risk. Also, transformers in hazardous areas and transformers used in generation plants are all vital and require fast clearing protection to avoid any ramifications after faults. Some transformers are custom designs and their lead time is so long that its replacement is not an option, which again mandates fast clearing protection.

Generally, a proportional relationship exists between the transformer lead time and the protection function scheme. The longer the lead time is, the more advanced the protection scheme is.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know!Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Salem Alshahrani - Author at EEP-Electrical Engineering Portal

Salem Alshahrani

Electrical engineer (BEE & Meng). Specialized in substation design, especially in LV/MV switchgears and transformers. Passionate in power system planning, analysis, and stability studies.

Profile: Salem Alshahrani

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.