Home / Technical Articles / Learn to successfully analyze single-line, schematic, P&ID, logic, and wiring diagrams

Estimated Study Time: 31 minutes

Reading and interpreting drawings

Engineering tasks require a good skill in reading and interpreting information on drawings. Engineering drawings are the industry cornerstone of conveying detailed and precise information on how to construct, troubleshoot, maintain, and operate a system. Basic requirements are needed to understand the way of reading these drawings: rules, basic symbols, and industry conventions.

Practical advice in successful reading single-line, schematic, P&ID, logic, and wiring diagrams
Practical advice in successful reading single-line, schematic, P&ID, logic, and wiring diagrams

That being said, a pre-requisite of learning how to read the drawings is to know how to read non-drawing areas of a print. Vendors have variant drawing formats and information, so all drawings will have different information from these addressed here, but these drawings are usually similar.

This article provides tips for different drawing types that help to grasp these drawings’ main principles quickly. These drawings cover single-line, schematic, wiring, logic, and P&ID drawings that are found in the industry. Prior to delving into more details of these drawings, non-drawing topics are usually overlooked in explaining the drawing reading basics.

It is essential to master how to move between drawing sheets, how to pinpoint a specific component, how to surf through different drawing corrected versions, and so on. These basic steps are explained briefly to establish a foundation over which these drawings are tackled.

Then, the mentioned drawing types are introduced and some tips are presented to help to interpret these drawings. This article does not explain these drawings, instead one must have some sort of basic understanding of the drawings.

Table of Contents:

  1. Drawing Anatomy
    1. Title Block
    2. Drawing Scale
      1. Grid System
      2. Revision Block
      3. Tracking Changes
      4. Notes and Legends
  2. Types of Drawings
    1. Piping and Instrument Drawing (P&IDs)
      1. Symbols and Notations
      2. Engineering Fluids Diagrams
      3. Fluid Power Diagrams
    2. Single-Line and Schematic Diagrams
      1. Steps in Reading Electrical Diagrams and Schematics
    3. Logic Diagrams

1. Drawing Anatomy

Engineering drawings are classified into the following areas:

  1. Title block
  2. Grid system
  3. Revision block
  4. Notes and legends
  5. Engineering drawing (graphic portion)

The first four items represent the non-drawing parts that are essential in reading the drawing itself. Hence, a brief description of each item is presented in this article.


1.1. Title Block

A title block is normally located at the bottom of a print, lower right-hand corner in particular. It has the all necessary information to identify drawings and verify their validities. Several areas comprise a title block as shown in Figure 1.


1.1.1. Title block first area

This area contains the drawing title, number, location, site, or vendor. The drawing title and the drawing number are used to identify and fill the required drawing. The drawing number is usually unique and consists of a code containing information about the drawing like site, drawing type, and system.

Moreover, the drawing number might contain information, such as revision level and sheet number. The drawing number, also, is often the means of filling drawings rather than their titles, as the titles could be common to some prints.

1.1.2. Title block second area

The second area encompasses the signatures and the dates of approval that provide information about when and who verified the drafted drawing for final approval. This information is invaluable in finding further data on the system design. Also, these referees can be helpful in discrepancy resolution and dispute settlements.

Figure 1 – Title block

Title block
Figure 1 – Title block (click to expand drawing)

1.1.3. Title block third area

This block is the reference block that lists other drawings that are either related or cross-referenced on the underlying drawing. Obviously, the reference block is extremely important in locating additional information of a given system that can be found in other related drawings.

Go back to Contents Table ↑


1.2. Drawing scale

Drawings are generally categorized to either with a scale or not to a scale. The former provides only functional information about the system while the latter render figures accurately. Furthermore, scale drawings allow systems that are too large to be drawn full size and vice versa. In other words, small systems could be enlarged such that their details are noticeable.

Scale drawings often provide the means to fabricate or assemble a system.

Additional information is obtained from scale drawings, such as physical dimension, materials, and tolerance that aid the fabrication process. Since the scale drawings present actual dimensions, actual dimensions are not stated in writings on the drawings. Instead, a drawing scale is used to obtain the correct measurement by dividing or multiplying.

The drawing scale is ratio-based as illustrated in Table 1.

Table 1 – Drawing scale

Drawing scale
1″=1″1 inch on drawing equals 1 inch on actual.
Stated as FULL SIZE in the drawing scale box
Measured dimension on drawing is the same as the actual dimension
3/8″=1’3/8 inches on drawing equals 1 foot on actual
Called “3/8 scale”
1/2″=1’1/2 inches on drawing equals 1 foot on actual
Called “1/2 scale”

Go back to Contents Table ↑


1.2.1. Grid System

Drawings complexity varies according to the system application. Complex drawings make it challenging to locate a specific point or equipment on a drawing. This becomes more difficult when moving between drawings to trace cables or pipe runs that continue to other drawings. This is why drawings utilize a grid system, especially for Piping and Instrument Drawings (PID) and electrical schematic diagrams.

The grid system might consist of letters, numbers, or both that run horizontally as well as vertically around the drawing as depicted in Figure 2.

Figure 2 – A grid system example

A grid system example
Figure 2 – A grid system example (click to expand drawing)

Drawings are divided into smaller blocks, each has its own unique grid identifier that is composed of two letters or numbers. For instance, a cable that continues from a drawing to another, the second drawing references the other drawing and it uses the grid coordinates to locate the continued cable, thereby facilitating the search process significantly.

Go back to Contents Table ↑


1.2.2. Revision Block

Changes made to systems must be redrafted and reissued. A drawing first issue is called revision zero, and the revision block is empty. The revision block is filled with a revision number, a revision date, a title, or a revision summary at every drawing revision release. The revision number could be part of the drawing number that appears at the end of this drawing number or in its own separate block (see Figure 3).

Whenever a system modification is held, the drawing is updated to reflect such modifications, the revision number is incremented by one, the revision number in the revision block is updated to represent the new revision number. Note that the drawing number remains the same. The old revision drawing is filed for historical purposes.

Figure 3 – Revision block

Figure 3 - Drawing revision block
Figure 3 – Drawing revision block (click to expand drawing)

Go back to Contents Table ↑


1.2.3. Tracking Changes

Two approaches are commonly used to indicate changes made on drawings in their corresponding revisions. The cloud method encloses each change within a cloud-shaped box as illustrated in Figure 4. The other approach is to place changes within circles, triangles, or any other shapes with the revision number written next to each modified portion of the drawing as indicated in Figure 4.

The cloud approach indicates the changes from the most recent revision whilst the other approach represents all revisions to the drawing since all previous revision circles/triangles remain on the drawing. Both the revision number and the revision block are useful in tracing the evolution of a system by comparing the various revisions.

Figure 4 – Methods to indicate changes

Methods to indicate changes
Figure 4 – Methods to indicate changes (click to expand drawing)

Go back to Contents Table ↑


1.2.4. Notes and Legends

Symbols and lines to drawings are what genes to chromosomes, which both form the basic building block for larger systems. To a great extent, symbols are self-explanatory, but a few symbols shall be elaborated for each drawing.

The notes and legends section list and illustrate special symbols as shown in Figure 5. Moreover, a designer can add any information that is necessary to interpret correctly the drawing. It is essential to view this section prior to proceeding to the drawing contents so as to fully understand the symbols and conventions used in the drawing package.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know!Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Salem Alshahrani - Author at EEP-Electrical Engineering Portal

Salem Alshahrani

Electrical engineer (BEE & Meng). Specialized in substation design, especially in LV/MV switchgears and transformers. Passionate in power system planning, analysis, and stability studies.

Profile: Salem Alshahrani

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.