Home / Technical Articles / Guidelines for selecting the proper Variable Frequency Drive (VFD) for motor applications

Estimated Study Time: 45 minutes

VFD control, applications, schematics

This article addresses the Variable Frequency Drive (VFD) concept in several aspects that matter the most in selecting the proper VFD for applications. One of the important factors is the control type required for a given application since it is not uncommon to misselect the control type that does not provide the desired performance.

Guidelines for selecting the proper Variable Frequency Drive (VFD) for motor applications
Guidelines for selecting the proper Variable Frequency Drive (VFD) for motor applications (photo credit: gibbonsgroup.co.uk)

Also, the impacts on motor applications that are expected upon utilizing VFDs are discussed along with the grounding requirements.

Often, VFDs are associated with LV applications; the MV applications are overlooked most of the time, so the main differences are highlighted. Lastly, the VFD schematics are presented to shed some light on common drawings that might be encountered.

Table of Contents:

  1. Introduction to VFDs
  2. VFD control types:
    1. V/f control (speed control at constant torque)
    2. Phasor (vector) control
    3. Direct torque control
  3. Influence of the inverter on the insulation system
    1. Rise time
    2. Cable length
    3. Switching frequency
    4. High frequency bearing currents
  4. VFD grounding
  5. LV and MV applications
  6. VFDs schematics

1. Introduction to VFDs

The simplest method to control the motor speed is to operate it at full speed, but many applications require variable speed. Many technologies had been used prior to the advent of the variable frequency drive (VFD) for speed controlling as follows: control valves, dampers, and vanes; eddy current clutches; fossil fuel engines; variable pitch sheaves; hydraulic coupling and DC solid-state control.

Initially, DC motors were used as VFDs because they could easily achieve the required speed and torque without the need for sophisticated electronics.

However, the evolution of AC variable speed drive technology has been driven partly by the desire to emulate the excellent performance of the DC motor, such as fast torque response and speed accuracy, while using rugged, inexpensive, and maintenance-free AC motors.

Figure 1 shows the block diagram of a typical three-phase VFD controller.

Figure 1 – Block diagram of a typical Variable Frequency Drive (VFD)

Block diagram of a typical VFD
Figure 1 – Block diagram of a typical VFD

The function of each VFD block is as follows:

Converter

A full-wave rectifier that converts the applied AC to DC.

DC bus

Also referred to as a DC link connects the rectifier output to the input of the inverter. The DC bus functions as a filter to smooth the uneven, rippled output to ensure that the rectified output resembles as closely as possible pure DC.

Inverter

The inverter takes the filtered DC from the DC bus and converts it into a pulsating DC waveform. By controlling the output of the inverter, the pulsating DC waveform can simulate an AC waveform at different frequencies.

Figure 2 – B6 converter

B6 converter
Figure 2 – B6 converter

Control logic

The control logic system generates the necessary pulses used to control the firing of the power semiconductor devices such as SCRs and transistors. Fairly involved control circuitry coordinates the switching of power devices, typically through a control board that dictates the firing of power components in the proper sequence.

An embedded microprocessor is used for all internal logic and decision requirements.

The number of pulses of a converter defines the number of commutations, which are used within one fundamental period, to convert AC to DC. The basic converter for a three-phase system is a B6 topology (see Figure 2). The B6 converter uses 6 commutations within one fundamental period. This results in a commutation every 60 degrees.

Table 1 – Converter pulses implementation

Converter number of pulsesImplementation
6-pulsebase on 1 B6 circuits
12-pulsebase on 2 B6 circuits
18-pulsebase on 3 B6 circuits
24-pulsebase on 4 B6 circuits
36-pulsebase on 6 B6 circuits

Table 1 lists common converter pulse numbers. Additionally, the number of secondary terminals of the isolation transformer (if any) is proportional to the drive number of pulses as per the following formula:

xmfr#secondary × 6 = Converter#pulses

For instance, a drive with one secondary would have a 6-pulse converter whilst a drive with 4 secondaries would yield a 24-pulse converter. Figure 3 depicts a 12-pulse converter with two B6 converters and two transformer secondaries.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

TIme Limited!Save 15% on PRO membership plan with code RMS15.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Salem Alshahrani - Author at EEP-Electrical Engineering Portal

Salem Alshahrani

Electrical engineer (BEE & Meng). Specialized in substation design, especially in LV/MV switchgears and transformers. Passionate in power system planning, analysis, and stability studies.

Profile: Salem Alshahrani

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.