Home / Technical Articles / The art of the switchyard design: Handpicked details you must consider without fail

Estimated Study Time: 45 minutes

Switchyard design

This article deals with switchyard design and it’s divided into two parts in which switchyard design considerations are discussed in the first part and the other part presents a case study of a 33/220 kV transmission switchyard. This article discusses different switchyard design considerations ranging from location to voltage, general layout.

The art of the switchyard design: Handpicked details you should consider without fail
The art of the switchyard design: Handpicked details you should consider without fail (on photo: 220 kV switchyard "Chesnokovskaya")

Also, switchyard component sizing is presented along with the control and protection schemes implemented.

Table of Contents:

  1. Introduction
  2. Switchyard Design Considerations:
    1. Switchyard Location
    2. Basic Information
    3. Applicable Standards
    4. Safety of Life
    5. Power Supply Reliability
    6. Switchyard Internal System Reliability
    7. Voltage Considerations
    8. Cost
    9. Relay Building Location
    10. Layouts and Conductor Spacing
    11. Busbar Design
    12. Grounding Design
    13. Lightning Protection Design:
      1. Overhead Shield Wires
      2. Masts
      3. Clamps and Connections
  3. Switchyard Components:
    1. Switchyard Component Sizing
    2. Instrument Transformers
    3. Busbars
    4. Disconnectors
    5. Circuit Breakers
    6. Auxiliary System
  4. Switchyard Control and Protection

1. Introduction

An electrical substation is a part of an electricity generation, transmission, and distribution system where voltage is transformed from high to low or in reverse using transformers. It also serves as a point of connection between various power system elements such as transmission lines, transformers, generators, and loads.

To allow for flexibility in connecting the elements, circuit breakers are used as high power switches.

Electric power may flow through several substations between generating plant and consumer and may be changed in voltage in several steps. There are different kinds of substations such as transmission substations, distribution substations, collector substations, switching substations, and some other types of substations.

An air-insulated substation (AIS), shown in Figure 1, is one where the main circuit potential is insulated from the ground by air using porcelain or composite insulators and/or bushings.

AIS is fully composed of air-insulated technology components such as circuit breakers, disconnecting switches (disconnectors), surge arrestors, instrument transformers, power transformers, capacitors, bus bars, and so on, and the components are connected by stranded flexible conductors, tubes, or buried power cables.

AIS is the most common type of substation, accounting for more than 70% of substations all over the world.

Figure 1 – Switchyard, air-insulated substation (AIS)

Switchyard
Figure 1 – Switchyard, air-insulated substation (AIS)

Switchgear consists of electrical disconnect switches such as fuses or circuit breakers, which are used to control protect and isolate the electrical equipment in case of fault conditions. Switchgears are devices that are used for the switching, protection, and controlling of an electrical circuit.

But switchyard is entirely different from it, maybe switchgear can be a piece of equipment in a switchyard, the transmission of the power which is generated in a power plant is done with the help of a switchyard it acts as a junction where the power transmission takes place. Switchyard can secure the power plant and can help in the transmission of power.

The switchyard operations depend on a safe and reliable power system. Each switchyard system design, whether new or an expansion to an existing system, must be analyzed to ensure that it is safe, reliable, meets the present objective and permits expansion for future needs.

Go back to the Contents Table ↑


2. Switchyard Design Considerations

The switchyard planning and design must include several considerations at the initial and planning or design stage.


2.1. Switchyard Location

Special consideration needs to be given to the location to achieve the optimal compromise between the line entry to the site and the switchyard.
The main factors that must be considered in the selection of the site for the construction of a switchyard are:

  1. Availability of access for the incoming transmission or sub-transmission lines and the distribution and communication systems circuits within the switchyard.
  2. Facilities for the transport of heavy equipment to the site.
  3. Environmental impacts of the site related to its appearance, noise, or electrical interference or its impact on other facilities.
  4. Conditions of the ground, its facility of drainage, soil resistivity, and its load-bearing capability.
  5. Cost of excavations and earthwork.
  6. Governmental or municipal restrictions at the site.
  7. General topographical considerations, including seismic levels and the risk of flooding and the proximity to marshy.
  8. Total cost, including the provision of distribution circuits to the plant and the required control and communication facilities.

Go back to the Contents Table ↑


2.2. Basic Information

Before beginning the design of a switchyard, it is necessary to obtain information on which the design will be based. One set of information required will concern the system to which the switchyard will be connected, such as the levels of active and reactive power available, the voltage regulation, the system short-circuit levels, the lightning risk, etc.

Other information includes the climatic data of the site, the seismic risk levels, the altitude, and the environmental requirements that must be taken into account in the design of the facilities.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know!Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Salem Alshahrani - Author at EEP-Electrical Engineering Portal

Salem Alshahrani

Electrical engineer (BEE & Meng). Specialized in substation design, especially in LV/MV switchgears and transformers. Passionate in power system planning, analysis, and stability studies.

Profile: Salem Alshahrani

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.