Home / Technical Articles / How to use Lockout Relay (master trip relay) in substation protection and control design

Estimated Study Time: 20 minutes

The art of lockout in control circuitry

Lockouts and auto-reclosures are apprentices of power systems protection that have long served to regulate power supply and safeguard important components from probable catastrophes. But are we taking them seriously enough? In implementing the lockout features, apart from their placements in control circuitry, operating principles, construction, and functionalities remain almost the same over decades, while their counterparts have seen massive overhauls.

Lockout relay (master trip relay) in substation protection and control design
Lockout relay (master trip relay) in substation protection and control design

This article will focus on the practical applications of lockout relays on mainstream switchgear and protection. The primary goal is to discuss the transition from the current mode of application to possible upgrades and adaptations in modern digital power substation protection.

The terminologies lockout relay, master trip relay, and 86-relay are used interchangeably in this article.

Table of Contents:

  1. What does lockout relay do exactly?
  2. Operation in protection circuit
  3. What makes lockout relay indispensable in substation protection
  4. An analogy with auto-reclosure
  5. Next-generation implementation of lockout features
    1. The transition from traditional lockout to modern distributed lockout

1. What does lockout relay do exactly?

Protection relays are undoubtedly the soul of substation protection and require multiple auxiliary relays to support them for the overall functionality of protection, control, and monitoring. Master trip relay or lockout relay, also known by ANSI code 86, holds a significant position as an intermediator between the protection relay and control points, even though it is not self-equipped with fault sensing capabilities.

The master trip relay can operate as a hub of multiple protection relays trip commands and drive multiple subsequent contacts. This makes the relay a protagonist to execute simultaneous commands like breaker trips, interlocks, alarms, data display, SCADA extensions, and lockouts.

Figure 1 – Trip function interface: Soft Logic to a hard-wired connection

Trip function interface: Soft Logic to a hard-wired connection
Figure 1 – Trip function interface: Soft Logic to a hard-wired connection (click to zoom)

In absence of a master trip relay, imagine connecting individual trip circuits of each protection relay to circuit breaker trip coils. Along with the obvious extra cost incurred, this would be a mess for operation and troubleshooting. The concept of lockout relay as an intermediator of protection is illustrated in Figure 1.

Initiation of fault signals in modern-day protection IED activates the lockout relay to perform the trip command of associated breakers. Likewise, the command for a closing coil of breaker only receives the close signal upon confirmation from the lockout relay.

The sequence of operation for medium voltage switchgear with numerical protection relay to execute closing command is illustrated in Figure 2.

Figure 2 – Close function interface- Soft Logic to a hard-wired connection (click to zoom)

Close function interface- Soft Logic to a hard-wired connection
Figure 2 – Close function interface- Soft Logic to a hard-wired connection

The picture in Figure 3 is of one of the most popular choices for master trip relay with a hinged flag reset mechanism used in a plethora of applications like medium voltage radial feeder protection, transformer protection, busbar protection, etc. The movable part with a white cover is used for indicating two states of the relay- Faulty or normal.

The legacy master trip relays rely on solenoid operating coils for their operations, and the terminals are latched every time the lockout command activates. This mandatorily requires resetting (Self, via flags or push buttons, or electrically via pickup voltage) of latched terminals to resume the circuit for normal operation.

This holds more importance in relatively less sophisticated substations as it requires the operators to manually acknowledge and take necessary action for fault remedial before closing back the circuit.

Figure 3 – Lockout relay in an MV breaker panel

Lockout relay in an medium-voltage breaker panel
Figure 3 – Lockout relay in a medium-voltage breaker panel

Electromechanical master trip relays provide excellent isolation against any probable trip circuit hazards that might damage the costly set of modern-day microprocessor-based protection relays that are vulnerable to voltage spikes and transients in trip circuits.

The hinged armature construction with adequate electrical and mechanical rating ensures prompt and continuous rated operation within a fraction of seconds without over-heating.

Go back to the Contents Table ↑


2. Operation in protection circuit

The master trip relays usually consist of operating coil rated at 220V or 110V DC and supplied with a continuous negative DC voltage from one end. It operates to latch the contacts once it receives positive voltage from the opposite end, which is triggered by operating of protective relay associated.

The diagram below illustrates a typical connection principle of a master trip relay with the tripping and closing circuits in an 11 kV VCB panel. In the illustrated connection, once the trip signal is initiated by protective relay 51/50, the operating coil of the master trip relay (86) is instantly energized via its own NC contact to revert and latch the position of 16-17, 12-13, and 10-11 secondary contacts as indicated in the diagram.

In trip circuits, this completes the path to extend positive voltage at the trip coil, and the breaker operates to open the contact, along with 52-a secondary contacts.

Figure 4 – Vacuum circuit breaker (VCB) trip and close coil operation (click to zoom)

Vacuum circuit breaker (VCB) trip and close coil operation
Figure 4 – Vacuum circuit breaker (VCB) trip and close coil operation

Meanwhile, the contact multiplications of master trip relay help to cover up ancillary duties of annunciation led indication, and so on. As it stands, the breaker can be closed back neither automatically nor manually via TNC switch unless the latched terminal NC contact 12-13 is reverted by resetting the operating coil of the master trip relay.

The figure below is a contact multiplication for a master trip relay. Between 27-28 terminals lies the operating coil of the relay in a series of its own NC contact, which helps to automatically cut off the supply to the coil once it is triggered.

Figure 5 – Contact multiplication principle of master trip relay

Contact multiplication principle of master trip relay
Figure 5 – Contact multiplication principle of master trip relay

Anti-pumping relay is another essential component in circuit breaking, which helps to avoid any possibility of CB hunting effect due to spring failure in TNC switch. It forms a part of the closing circuit as its auxiliary NC contact links the path of positive voltage extension to the breaker closing coil, and its operating coil forms a parallel path to ensure the closing coil does not receive continuous positive voltage.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know!Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Bishal Lamichhane - Author at EEP-Electrical Engineering Portal

Bishal Lamichhane

Electrical Engineer (B.E Electrical, M. Sc Engineering) with specialization in energy systems planning. Actively involved in design and supervision of LV/MV substations, power supply augmentations and electrification for utilities and bulk consumers like airports and commercial entities. An enthusiast and scholar of power systems analysis.
Profile: Bishal Lamichhane

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.