Home / Technical Articles / Inside the capacitor bank panel: Power factor correction, calculation and schematics

Estimated Study Time: 32 minutes

It’s all about loads and angles

Various calculations must be performed during the electrical design stages of any project to deliver a safe electrical system for the end user. One of the essential things that must be taken into account after calculating the total and demand load of the project is to consider the power factor.

Inside the capacitor bank: Power factor correction, circuits, calculation and schematics
Inside the capacitor bank: Power factor correction, circuits, calculation and schematics

But before indulging in the power factor correction, you should be aware of different types of loads. Real and wasted power are the main cause of power factor variation in the system.

Therefore, taking full advantage of increasing real power and minimizing wasted power through improving the power factor is crucial in every system to reduce the monthly electricity bill and avoid penalties imposed by the electrical authorities, as you will know how this could happen in the following paragraphs.

The power factor is defined as the cosine angle between voltage and current. This angle may vary and be increased or decreased depending on several factors, affecting the productivity of clean power in the low voltage system. This article will go through the main aspects of a power factor.

You will learn what it means and how to improve power factor value using capacitor banks and analyze capacitors and reactors control and power circuit diagrams.

Table of contents:

  1. Types of Power
  2. Types of Loads
  3. Lagging and Leading Loads
  4. Capacitor Bank Size Calculation
    1. Project Example
  5. Automatic Capacitor Bank Power Circuit
    1. Capacitor Bank Switching
    2. Stages in PF Correction
    3. Harmonics and Connection of Reactors
    4. Capacitor Bank Control Circuit
      1. Analyzing Control Circuit of APFC

1. Types of Power

It is very important to understand the different types of loads represented in what is known as the “power triangle” which clearly shows the relationship between different kinds of power. By understanding different types of loads and their output waveforms, it will be easier to analyze how the power factor plays an important role in increasing or decreasing the efficiency of power in the grid.

As you can see in the power triangle, three types of power are influenced when the power factor angle is either increased or decreased.

Figure 1 – Power triangle (apparent, reactive and real power)

Power triangle (apparent, reactive and real power)
Figure 1 – Power triangle (apparent, reactive and real power)

Electrical power in the low voltage system is divided into three types:

Active Power (P): The power needed for useful work such as turning a lathe, providing light or pumping water, expressed in Watts or Kilowatts (kW).

Reactive Power (Q): A measure of the stored energy reflected in the source which does not do any useful work, expressed in VAR or Kilovar (kVAR).

Apparent Power (S): The vector sum of active and reactive power, expressed in Volt Amperes (VA) or Kilovolt Amperes (kVA).

These three types are related and have a direct relationship represented in the power triangle. Real power is also called pure and active power, and it is what we need to energize all devices, equipment, and appliances in our homes.

On the other hand, reactive power is considered wasted power and needs to be minimized as much as possible. Reactive power is required to provide an electromagnetic field that can start up motor-driven loads; however, a high amount of kVAR value is not recommended and may decrease the system’s efficiency.

At the same time, the apparent power is the addition of real and wasted reactive power. It is clearly shown in the power triangle that the wider the power factor angle, the more reactive power will result and less real power. In contrast, the less the angle it gets, the more real power and less reactive power will result.

So, how does this relate to the electrical design of a low-voltage system? This question is better answered after you know the types of loads in the coming section.

AC Circuits Analysis: Real, Reactive and Complex Power Calculation

Go back to the Contents Table ↑


2. Types of Loads

Most loads in electrical distribution systems fall under one of three categories; resistive, inductive, or capacitive. In most cases, the most common is likely to be inductive.

So, to answer the previous question, “how would this information have its benefit in our electrical low voltage design?” understanding the types of loads would help to answer that question comprehensively. Since we have two major loads in any project – resistive and inductive – the power factor will surely be positively or negatively affected.

Simply put, the more resistive loads present in the system, the more real power in watts will be consumed, keeping the power factor at its high values. In case of more inductive loads, e.g. air conditioners, water pumps, extraction fans etc., are operating in the project, the power factor will decrease.

So let’s define these loads separately:

Type of LoadExamples
Resistive Loads:

Any heating load that consumes active or real power.
(phase angle = 0º)

Incandescent lights, toasters, water heaters, ovens, coffee makers, etc.
Inductive Loads:

Loads that utilize reactive power to create magnetic fields that rotate the motor. All inductive loads require two kinds of power to operate: Active power (KW) – to produce the motive force & reactive power (KVAR) – to energize the magnetic field.
(Has a lagging power factor).

Inductive motors, VFD, Vacuum cleaners, washing machines, air conditioners, etc.
Capacitive Loads:

Loads that don’t exist in a standalone form like resistive lights or inductive motors.
(Has a leading power factor)

Capacitors, Capacitor banks, motor starting capacitors, and generators.

It may reach a poor value that may put more load on the transformer and heat it due to the higher amount of reactive load (kVAR) in the system. For this reason, improving power factor equipment must be designed to correct and increase it to an efficient value.

This power factor improving equipment is called the “Capacitor Bank.” A capacitor bank is a panel containing several capacitors connected to the main board or the LV panel of the project to correct the power factor when it reaches lower values.

In most countries, electrical companies impose on achieving a minimum power factor of 0.9 to avoid penalties.

This means that if the power factor decreases to a lower amount of 0.7, for instance (mainly due to the higher inductive and non-linear loads connected to the system), the main electrical company will penalize the consumers because of the low factor may put the entire system’s equipment (like the transformer) in danger of being damaged or overheated.

Therefore, designing and sizing a capacitor bank in any project is compulsory because it will not only exempt the consumers from the authority’s penalty but it will also increase the amount of real power in the system.

This will allow the addition of more loads to the transformer of the project, reducing voltage drops, reducing electricity bills, and lowering heat generation in cables, switchgear, transformers and alternators of the system.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know!Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Mohammed Ayman - Author at EEP-Electrical Engineering Portal

Mohammed Ayman

I earned my degree from Eastern Mediterranean University (Turkey, North Cyprus) in B.S Electrical & Electronic Engineering; shortly after, I began my career as an electrical site engineer in a mega-scale project in Qatar which allowed me to monitor and supervise electrical site installations. I indulged in the design field of the electrical low voltage distribution systems and have accomplished more than 10 projects with the compliance of the national codes & international standards.
Profile: Mohammed Ayman

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.