Home / Technical Articles / Learn how to interpret and design single-line diagrams (SLD) for complex projects

Estimated Study Time: 25 minutes

It’s all about loads and ratings

A complex project comprises loads ranging from small loads such as sockets and lights to higher loads like Air Handling Units (AHUs), Fan Coil Units (FCUs), motor pumps, and other high motor-driven loads. Loads connected to the project are gathered and represented with symbols in what is known as a “single-line diagram.”

Learn how to interpret and design single-line diagrams (SLD) for complex projects
Learn how to interpret and design single-line diagrams (SLD) for complex projects

Single-line diagram is considered vital for maintenance activities, tracking the location of faults, and useful for operators to identify the electrical placement of different devices and components. In an LV distribution system, the diagram should clearly show the main, sub-main, and distribution panel boards and the motor-driven loads of the project represented with symbols.

These loads are connected by cables or busbars which must be clearly shown in the single-line diagram. Also, a single-line diagram represents comprehensive data for each component or device connected to it.

In other words, the exact cable sizes, circuit breakers ratings, voltage drop values, and short circuit current calculated values must be reflected in the low voltage distribution single line diagram. The diagram must show the source of supply power to the project, either the generator or the step-down transformer at the start, down to the final distribution board or final connected load.

Generally, creating a single-line diagram enables electrical personnel to fully understand the layout and design of the facility’s electrical distribution system. It is mainly considered the road map for maintenance activities because a single-line diagram represents how the main electrical system components of the project are connected. In this article, you will understand how a single-line diagram is interpreted by exploring different diagrams for different types of panels.

Every component included in the SLD will be explained, and clarify why it is mentioned in the diagram and why it is functional. Moreover, the design of an SLD will be explained using the well-known AutoCAD drafting software.

Table of Contents:

  1. HV to LV Generation, Transmission & Distribution of Power
  2. Interpreting a LV Panel Single-Line Diagram
  3. Interpreting a SLD with a Backup Generator
  4. Sub-main Panel SMDB Single Line Diagram
  5. MCC Panel Single Line Diagram
  6. Design a Single Line Diagram in AutoCAD

1. HV/LV Generation, Power Transmission & Distribution of Power

To understand the low voltage side of power distribution in a single-line diagram, let’s remind ourselves how electric power is delivered to our homes and other facilities. Electricity passes through three stages: generation, transmission, and distribution.

Electricity is generated in power plants or power stations with a voltage of 11KV, then stepped up using step-up transformers to increase the voltage to between 100 KV to 700KV depending on the distance it will be transferred to; the longer the distance, the higher the voltage. After that, electricity is transmitted via overhead electrical lines, which we can notice when driving between cities.

The transmission of these lines is aimed at reaching several receiving substations. When electrical power reaches a receiving station, the voltage decreases to between 33kV and 66kV. It is then sent to transmission lines emerging from this receiving station to electrical substations close to cities, villages, and urban areas.

When electrical power reaches a substation, it is stepped down once more by a step-down transformer to voltages closer to what was generated at usually around 11kV. From here, the transmission phase graduates to the distribution phase, and electrical power is used to meet demand from primary and secondary consumers.

Figure 1 – Low Voltage Panel Single Line Diagram

Low Voltage Panel Single Line Diagram
Figure 1 – Low Voltage Panel Single Line Diagram

This is done by installing a low-voltage transformer that steps this voltage down to 500V or less for distribution. So, to understand a LV single-line diagram, it is advised to know how power is generated, transmitted before studying the distribution part which is what will be covered in this article.

In this article, our main aim is to understand the distribution part of the single-line diagram, which does not include the upstream side of the transformer. In other words, the SLD shall not represent what is before the low-voltage transformer and will only show the connections from the LV transformer to distribution boards and other end branch loads.

Figure 2 – Generation, Transmission and Distribution SLD of Power System

Generation, Transmission and Distribution SLD of Power System
Figure 2 – Generation, Transmission and Distribution SLD of Power System

Go back to the Contents Table ↑


2. Interpreting a LV Panel Single-Line Diagram

A single-line diagram (SLD) or a one-line diagram (OLD) is a simplified schematic representing a three-phase system’s electrical elements with a single line representing the connected conductors. We can say that the single-line diagram is finished once all loads are distributed throughout the project in the last stages.

The design of a single diagram is relatively easy. However, the electrical designer must understand how to interpret a single-line diagram to perform a well-designed SLD adequately.

As mentioned, a single-line diagram gathers all electrical elements, like circuit breakers, transformers, capacitors, busbars, conductors, etc. In a low-voltage power system, the single-line diagram should start by showing the step-down transformer represented by an internationally recognized symbol.

Of course, the symbol must also include written text showing the transformer specifications, like its rating and type. Right after the transformer, the main distribution board, or what is known as the LV panel, should be reflected in the diagram. The LV panel is considered the main panel that feeds the entire project.

Suggested Course – Learn AC Distribution Panel Drawings: SLDs, Wirings & Interlocking Schematics

Learn AC Distribution Panel Drawings: Single-Line Diagrams, Wirings, and Interlocking Schematics


Low voltage panel comprises the main circuit breaker, indicating lamps, ammeters, fuses, outgoing circuit breakers, and other related components that should be represented in the diagram with symbols, including their specifications and types.

The main LV panel must feed several sub-main panels connected by conductors, cables, or busbars. The conductors connected between the LV and sub-main panels must be represented by one line regardless of the number of conductors connected. This explains why it is called a single-line diagram.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know!Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Mohammed Ayman - Author at EEP-Electrical Engineering Portal

Mohammed Ayman

I earned my degree from Eastern Mediterranean University (Turkey, North Cyprus) in B.S Electrical & Electronic Engineering; shortly after, I began my career as an electrical site engineer in a mega-scale project in Qatar which allowed me to monitor and supervise electrical site installations. I indulged in the design field of the electrical low voltage distribution systems and have accomplished more than 10 projects with the compliance of the national codes & international standards.
Profile: Mohammed Ayman

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.