Home / Technical Articles / The art of fire protection and measures in Air-Insulated Substations (AIS)

Estimated Study Time: 33 minutes

How power utilities do it

These days, the dependability of the infrastructure used to distribute energy to customers is a key metric for evaluating electrical utility companies. A single unscheduled interruption may be disastrous for a utility company’s finances and reputation. Most customers lack the time and comprehension to appreciate the intricacies involved in ensuring constant power.

The art of fire protection and measures in Air-Insulated Substations (AIS)
The art of fire protection and measures in Air-Insulated Substations (AIS)

Fire prevention methods in air-insulated high-voltage substations are determined by the utility’s philosophy and requirements. For many utilities, the major method for mitigating the danger of fire-related collateral damage is to construct enough separation clearance distances between plant equipment and structures.

Due to the fact that each country or power utility has its own philosophy in this sector, it is difficult to summarize a worldwide philosophy.

Yet, there are certain overarching ideas that can be discussed. In general, the goal of a fire protection system is to limit the damage caused by the fire, protect the adjacent equipment, and minimize the amount of time that customers are without service.

Other goals include protecting the environment, minimizing the risk of injury to operators and members of the public, and protecting the environment.

While selecting a fire protection system, a designer must to take into account the low likelihood of an actual fire occurring, the expense of the fire protection system, and the dependability of the fire protection apparatus. These three things need to be taken into mind.

Figure XX – Fire hazard in air-insulated substation (AIS)

Fire hazard in air-insulated substation (AIS)
Figure XX – Fire hazard in air-insulated substation (AIS)

The criticality of the installations or of any other facilities that are near to them determines the level of protection that must be provided.

To safeguard power transformers and the surrounding apparatus, equipment, and buildings at substations from fire, the vast majority of utilities employ fire prevention systems in outdoor and/or interior installations. Air pollution is another concern, as is protecting the environment (trees, buildings, etc.) and keeping employees safe.

Fewer utilities than you might think lack fire prevention systems; this is usually because the risk of fire is deemed to be low and the investment and operations and maintenance expense is not warranted. When it comes to fire safety, the majority of utilities adhere to either regional, national, or international standards (such the United States’ National Fire Protection Association).

In the following paragraphs, we’ll go over some of the testing, maintenance, training, and fire events that have occurred in substations, as well as the many fire protection systems and their unique situations of application for power transformers, cables, control, relay, and cable & signaling rooms.

Table of Contents:

  1. AIS Fire Protection Systems
  2. Protection of Power Transformers
    1. Internal Protection of Power Transformers
  3. Protection of Power and Control & Signaling Cables
  4. Protection of Control, Relay, and Cable Rooms
    1. Inert Gas Suppression Systems
  5. Substation No-Fire-Protection Systems
  6. Problems With Traditional Fire Extinguishing Technologies
  7. Important Conclusions

1. AIS Fire Protection Systems

When it comes to exterior installations, a water-spray protection system is almost always recommended (see Figure 1). Indoor substations typically feature gas installations of some kind. These systems ought to make use of clean gaseous agents that are both electrically nonconducting and gaseous, and which, upon evaporation, do not leave behind any residue.

Nitrogen and carbon dioxide systems are available.

As a result of their contribution to greenhouse gas emissions, halon systems are no longer in use. Recent articles have reported the advent of hypoxic fire protection systems, in which the level of oxygen in a substation building is controlled to a lower level such that it will not sustain fire. This ensures that the building will not catch on fire.

Figure 1 – High-velocity water spray system installed around transformer

High-velocity water spray system installed around transformer
Figure 1 – High-velocity water spray system installed around transformer

There are also installations that utilize high-expansion foam and powder.

When selecting a method of fire protection for a specific substation, factors such as the substation’s criticality, the likelihood of a fire breaking out, the effectiveness of the extinguishing agent, the potential for damage to neighboring equipment, and the protection of personnel are taken into consideration.

Transformers are the sole substation piece of equipment that make use of water-spray systems, which are predominately based on a fine water spray and, to a lesser degree, on droplets of water. Its effect is consistently described as chilling, and at times it is described as both chilling and smothering. Moreover, gas systems are becoming more prevalent for use in transformers.

Figure 2 illustrates one such using nitrogen.

Typically, a procedure will take between 5 and 10 minutes to complete. One will rely on either a pressurized gas tank, a locally-stored water supply, or a pump-equipped storage tank. Depending on the substation’s location, several utilities also draw water from nearby rivers and canals.

Figure 2 – Substation Transformer Nitrogen Injection Fire Prevention System

Substation Transformer Nitrogen Injection Fire Prevention System
Figure 2 – Substation Transformer Nitrogen Injection Fire Prevention System (photo credit: Xuming Power)

Keeping a water supply on hand for use in extinguishing fires is not standard practice. The amount of water utilized typically ranges from 10 to 25 liters per minute per square meter of transformer surface area (10 to 6000 liters per minute). Usually, the water supply operates between 7 and 10 bar. Nozzles used in outdoor settings are typically not made to withstand the highest possible wind speeds.

The most common specifications for CO2 installations in buildings are 0.5-3 kg CO2 per m3, 0.5-3 minutes of operation, and 50-60 bar of normal operating pressure.

The usage of high-expansion foam in construction is unusual. The majority of fire safeguards are permanently installed. Almost half of all investigations employ either portable systems or a hybrid of fixed and mobile components. The majority of the fire safety features that are fixed and can’t be moved are activated by a timer or sensor.

Indoor smoke detectors, as well as bimetal and quartzoid bulb detectors, are common fire detection elements. Several types of detectors, such as optical, pneumatic rate-of-rise, plastic tube, and heat-detecting cable, are found in some circumstances. One detecting device is typically installed per 10-25 m2 of substation.

Figure 3 – Smoke Detection installed in an indoor substation

Smoke Detection installed in an indoor substation
Figure 3 – Smoke Detection installed in an indoor substation (credit: Zhejiang Dahua Technology Co.)

The most desired characteristics are detection dependability, detection speed, resilience to interference, and false alarm prevention.

In the past, the presence of a fire detector was required in order to activate the fire suppression system. Several utilities use safeguarding relays in addition to, or instead of, conventional detection mechanisms (gas, differential, pressure, frame leakage relays, etc.).

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know!Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Edvard Csanyi - Author at EEP-Electrical Engineering Portal

Edvard Csanyi

Hi, I'm an electrical engineer, programmer and founder of EEP - Electrical Engineering Portal. I worked twelve years at Schneider Electric in the position of technical support for low- and medium-voltage projects and the design of busbar trunking systems.

I'm highly specialized in the design of LV/MV switchgear and low-voltage, high-power busbar trunking (<6300A) in substations, commercial buildings and industry facilities. I'm also a professional in AutoCAD programming.

Profile: Edvard Csanyi

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.