Home / Technical Articles / Earthing system for a complex project: Analysis, calculation and installation (XLSX, DWG)

Estimated Study Time: 37 minutes

Earthing Calculation & CAD Drawing

Creating safety measures against various faults that can be fatal for a human is a critical task that electrical designers and site engineers must consider in any project. Furthermore, instability of the electrical system and equipment damage can result from these faults.

Earthing system for a complex project: Analysis, calculation and installation (XLSX, DWG)
Earthing system for a complex project: Analysis, calculation and installation (XLSX, DWG)

Therefore, a safe Earthing or Grounding system MUST be designed and installed properly to safely guide these potentially dangerous faults to the ground by attaching the ground to the non-conductive part of the equipment or the neutral of the power system.

This article covers the major principle of the earthing system implemented in complex and simple project.

There are different types of earthing systems, and designers and engineers must select the suitable one that is applicable for the project. Once you are familiar with the each type, you will understand how to size earthing conductors. In this article, you will learn how to create a very low impedance path for ground fault current by applying the related formulas to reach a low resistance level of less than 1 ohm.

In addition, you will be provided with an Excel spreadsheet you can use to easily calculate the resistance of earthing system. This sheet will also be explained by watching the relevant videos in this article. Testing the earthing system is just as important as the design.

For that reason, you will learn about the most common method used to test the soil and electrode resistivity practically on-site.

This article is also enhanced with an AutoCAD drawing that shows how an earthing system is designed for different systems.

Table of Contents:

  1. Earthing System Concept
  2. Types of Earthing Systems You MUST Know:
    1. TT System Directly Connected To the Earth
    2. TN-S System With Separate Ground & Neutral Conductor
    3. TN-C System With Combined Ground & Neutral Conductor
    4. TN-C-S Multiple Protective Earthing System
    5. IT Earthing System For Critical Applications
  3. How to Calculate Earthing Cable Size?
  4. How to Calculate Earthing System?
    1. BONUS! 🔗 MS Excel Spreadsheet for Earthing Calculation (XLSX)
  5. Components of Earthing System
  6. How to Test Earthing System?
    1. Soil Resistance Testing
    2. Electrode Resistance Testing
      1. Fall of Potential Method (Main Concept)
      2. Earth Electrode Resistance FOP Test (Practical Test)
  7. BONUS! 🔗 Earthing System AutoCAD Drawing (DWG)

1. Earthing System Concept

We can say that electrical earthing is the process of transferring the immediate discharge of the electrical flow directly to the earth. Simple as that! This transfer is achieved with the help of the low-resistance conductor implemented for this purpose. It is an arrangement by which an electrical installation is connected to a means of earthing.

All equipment and appliances must have an earthing terminal to discharge currents to earth during faults. If there is no earthing system, a person in direct contact with any appliance or device will get shocked by the current in case of fault because it does not have a way to be discharged to earth.

Let us assume that someone wants to use the washing machine; the machine is experiencing an internal fault which causes a breakdown in the insulation of the internal wires allowing a current to flow through the body of the washing machine, which in turn, if touched, the current will flow through that person’s body causing severe consequences and may lead to death.

This scenario will likely happen if the machine’s body is not earthed; in other words, it is not connected to a lower resistive pathway (earth wire) than the body of the person touching the washing machine’s outer body.

Figure 1 – Earthing System Concept

Earthing System Concept
Figure 1 – Earthing System Concept

Such single-phase appliances’ plugs should have three pins: live, neutral and earth. You will find that the bigger pin – meant to be bigger to decrease the resistivity – of the wire plug is located at the upper center to allow the fault current to be discharged to the earth.

This can also be called grounding.

Figure 2 – Fault current passing through human body (non-earthed equipment)

Fault current passing through human body (non-earthed equipment)
Figure 2 – Fault current passing through human body (non-earthed equipment)

Moreover, earthing can also be installed independently for some of the equipment and metallic pipes and is called Equipotential Bonding. Bonding involves joining all exposed metalwork and conductive items to the earthing system so that they all have the same potential energy (voltage).

When two objects hold different potential energy, it can be hazardous if anyone touches both objects simultaneously. This is because when a circuit is created between two points of varying potential energy/voltage, the energy will flow from the higher potential point to the lower potential point as fast as possible.

Figure 3 – Electrical equipment connected to earth

Electrical equipment connected to earth
Figure 3 – Electrical equipment connected to earth

This flow will result in a current that will travel through the person in direct contact, which can be fatal if it is large enough. Examples of equipotential bonding include connecting water and gas metal pipes to earth.

Also, it could be done in bathrooms and wet areas by connecting exposed metals to the earth to ensure they are always at the same potential. Considering the washing machine example mentioned earlier, if the person touches the casing of the faulty earthed washing machine, the current will not pass through the body and will be considered a safe situation.

However, when the same person touches a metal pipe at the same time touching the faulty machine, a difference in the potential energy may happen to lead to an electric shock.

In a nutshell, bonding is a technique used to minimize the danger of equipment damage and personal injury by connecting all metals and conductive parts to an earthing system so that all of them have the same potential energy (voltage).

Whereas earthing connects a particular equipment to the earth. Therefore, earthing must be included in any project’s design to protect people and devices from potential faults.

Figure 4 – Equipotential bonding for metallic pipes

Equipotential bonding for metallic pipes
Figure 4 – Equipotential bonding for metallic pipes

Go back to the Contents Table ↑


2. Types of Earthing Systems (You MUST Know)

According to the British Standard and IEC 60364 standard, there are five main types of earthing connections represented by two letters: T or N. The first letter indicates whether the supply source equipment (Transformer or Generator) is connected to a separate earthing.

The second letter indicates whether the load is directly earthed or not. There could be a third and fourth letter to describe the neutral, whether separated or connected, using the letters S, C, or both.

Figure 5 – House earthing system

House earthing system
Figure 5 – House earthing system

Go back to the Contents Table ↑


2.1 TT System Directly Connected To the Earth

In this type of Earthing System, connection to the supply source is directly connected to the earth, denoted by the first T. The consumer has solidly earthed independently of the source earthing method, donated by the second T.

The neutral and earthing conductors must be separated through the installation because the power supply authority only provides the neutral or protective conductor for the connection to the consumer. This method is the standard arrangement for most installations fed from an overhead supply.

Figure 6 – TT Earthing System

TT Earthing System
Figure 6 – TT Earthing System

Go back to the Contents Table ↑


2.2 TN-S System With Separate Ground & Neutral

In this system, the Ground Conductor & Neutral Conductor are separate throughout the distribution system. The protective conductor is the metallic covering of the cable supplying the installation.

All the exposed conductive parts of the installation are connected to this protective conductor or via the main earthing terminal of the installation. S indicates that the working neutral line and the protection line are strictly separated, so the PE line is called a dedicated protection line.

The customer may have an earth terminal connected to the sheath of the service cable or a separate earth conductor. Most installations with an underground supply will likely be of this type of earthing.

Figure 7 – TN-S earthing system

TN-S earthing system
Figure 7 – TN-S earthing system

Go back to the Contents Table ↑


2.3 TN-C System With Combined Ground & Neutral

The Neutral and the protective earth are combined into a single conductor throughout the system. All the exposed and conductive parts of the installation are connected to the PEN conductor.

The third letter in this type of earthing, C, indicates that the working neutral and protection lines are one. Therefore, in TN-C (Terra Neutral – Combined) method, the earth and neutral share the same conductor (two-wire single-phase).

The neutral conductor is also a protective conductor referred to as a PEN (Protective Earth and Neutral) conductor.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know!Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Mohammed Ayman - Author at EEP-Electrical Engineering Portal

Mohammed Ayman

I earned my degree from Eastern Mediterranean University (Turkey, North Cyprus) in B.S Electrical & Electronic Engineering; shortly after, I began my career as an electrical site engineer in a mega-scale project in Qatar which allowed me to monitor and supervise electrical site installations. I indulged in the design field of the electrical low voltage distribution systems and have accomplished more than 10 projects with the compliance of the national codes & international standards.
Profile: Mohammed Ayman

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.