Home / Technical Articles / Field secrets and warnings in power transformer mechanical check and visual inspection

Experience in transformer maintenance

Let’s discuss the visual and mechanical inspection procedures for oil-filled power transformers. It’s important, very important to examine a variety of key checkpoints, both external and internal to transformers, all based on the IEC 60076 standard. Each item on the checklist contributes to a complete picture of a transformer’s condition, from the quality of its paint to the functionality of its auxiliary devices.

Field secrets and warnings in power transformer mechanical check and visual inspection
Field secrets and warnings in power transformer mechanical check and visual inspection

But first, let’s remind ourselves and our younger engineers why transformers are so important in a power system.

Power transformers play a pivotal role in the efficient and reliable distribution of electrical energy across various systems. These complex machines are responsible for stepping up or stepping down voltage levels, facilitating the transfer of electricity from generation points to consumption centers.

Ensuring the optimal performance and longevity of power transformers is not just a matter of necessity; it’s a requirement for maintaining a seamless power supply network.

One of the cornerstones of transformer maintenance is a comprehensive regimen of visual inspections and mechanical checks. These routines, guided by standards such as the IEC 60076, enable engineers and maintenance personnel to meticulously assess the condition of oil-filled power transformers. Through careful scrutiny and adherence to specific checklists, potential issues can be identified, preventive measures can be taken, and the overall reliability of transformers can be upheld.

In this article, we delve into the intricacies of visual inspection and mechanical checklists for oil-filled power transformers. Drawing from the IEC 60076 standard, we explore a range of critical checkpoints that cover both the exterior and interior aspects of transformers.

From assessing paint quality to evaluating the operation of auxiliary devices, each step in the checklist contributes to the holistic understanding of a transformer’s health.

The proactive approach advocated by these inspections not only enhances operational safety but also extends the transformer’s service life, thereby reducing downtime and minimizing operational disruptions.

Join us as we navigate through the systematic process of evaluating power transformers, step by step, ensuring that every element is meticulously examined. By the end of this article, you’ll have a clear grasp of the indispensable role played by visual inspections and mechanical checklists in the world of power transformers.

Table of Contents:

  1. Impact Analysis and Transit Checks in Oil-Filled Transformers
  2. Impact Recorder Empowerment: Strengthening Transformer Transport Reliability
  3. Nitrogen or Dry Air Pressure Check
  4. Transport Weight Reduction and Storage Considerations
  5. Advantages of Nitrogen and Dry Air Filling
  6. Critical Pressure Monitoring for Transformer Integrity
  7. Mitigating Moisture Intrusion: A Case Study
  8. Verification of Transformer Components During On-Site Assembly
  9. Check for quality of paint, lifting lugs, weld areas, rust spots and wheel stoppers
  10. Inspect the transformer nameplate information and accurate placement
  11. Comprehensive Bolt Tightness Inspection Using Torque Wrench Method
  12. Thoroughly Inspection of All Grounding Points for the Secure Connection
  13. Check Direction and Slope of the Buchholz Relay
  14. Maintaining Cooling Efficiency (Open Valves Between the Main Tank and…)
  15. A Case Study of Diagnosing and Rectifying Abnormal Transformer Behavior
  16. Check the HV, LV and TV (if applicable) bushings for damage and completeness
  17. Check for Correct Color and Quantity of Desiccant in Breathers
  18. Verify the Proper Configuration of Heaters and Humidity Meters in Local Control Cabinet
  19. Ensuring Harmonious Phase Marking
  20. Ensuring Safe and Effective Clearances for Live Components in Power Transformers
  21. Checking Proper Operation of Auxiliary Devices in Power Transformers
  22. Ensuring Accurate Labeling of Auxiliary Devices According to Approved Drawings
  23. BONUS! Power Transformer Maintenance and Application Guides (PDF)

1. Impact Analysis and Transit Checks

Understanding the Role of Impact Recorders in Oil-Filled Transformers

During the transportation and delivery of heavy machinery like oil-filled transformers, the risk of encountering external forces and mechanical shocks is significant. These forces can potentially cause structural damage and compromise the transformer’s integrity, leading to performance issues or even catastrophic failures.

To address this concern, impact analysis and transit checks play a crucial role in ensuring that the transformer arrives at its destination unharmed and ready for operation.

An impact recorder, also known as a shock recorder or impact indicator, is a specialized device designed to measure and record mechanical shocks and impacts experienced by a transformer or any other equipment during transportation. The recorder is installed on the transformer’s packaging or frame before it begins its journey.

The recorder consists of a sensor capable of detecting various types of mechanical forces, including vibrations, shocks, and impacts.

Figure 1 – Shock Watch Digital Fault Recorder

Shock Watch Digital Fault Recorder
Figure 1 – Shock Watch Digital Fault Recorder

1.1 Function of Impact Recorders

The primary function of impact recorders is to monitor and record any significant external forces experienced by the transformer during transit. The recorder captures data related to the magnitude, duration, and direction of the shocks or impacts.

This information is crucial in assessing whether the transformer’s packaging and protective measures are adequate to withstand the stresses encountered during transportation.


1.2 Importance of Impact Analysis

Impact analysis is an essential step in evaluating the transformer’s condition upon arrival at its destination. By analyzing the data collected by the impact recorder, engineers and operators can assess whether the transformer has experienced any potentially damaging impacts during transit.


1.3 Benefits of Impact Recorders

Damage Detection: Impact recorders provide a clear indication of whether the transformer has encountered damaging mechanical forces during transportation, enabling timely action to address any potential issues.


1.4 Risk Mitigation

By knowing the impact severity, manufacturers and operators can take corrective measures, such as reinforcing packaging or implementing additional protective measures to minimize the risk of damage.

Figure 2 – Twin impact recorder Units Safely Affixed to Transformer for Comprehensive Impact Analysis, the laptop is used to download the data

Twin impact recorder Units Safely Affixed to Transformer for Comprehensive Impact Analysis, the laptop is used to download the data
Figure 2 – Twin impact recorder Units Safely Affixed to Transformer for Comprehensive Impact Analysis, the laptop is used to download the data

1.5 Insurance Claims

It’s important to know that in the event of damage during transit, impact recorder data can serve as valuable evidence for insurance claims, expediting the claims process and ensuring appropriate compensation.


1.6 Quality Assurance

The use of impact recorders demonstrates a commitment to quality assurance, ensuring that transformers are delivered to customers in optimal condition.


1.7 Interpreting Impact Recorder Data

Analyzing the impact recorder data requires expertise to understand the magnitude and consequences of the recorded impacts properly. Depending on the recorder’s capabilities, the data may provide insights into the forces encountered at different stages of transportation, such as loading, unloading, and transit.

Go back to Content Table ↑


2. Impact Recorder Empowerment

Strengthening Transformer Transport Reliability and Customer Confidence

In a specific instance, a transformer was in transit to a client and experienced an impact exceeding the defined 2g threshold. The integrated impact recorder promptly alerted Siemens, leading to a detailed analysis of the impact’s waveform. Upon scrutinizing the data, Siemens discerned that the duration of this impact held the potential to cause harm to the transformer.

In response, Siemens opted for a more comprehensive inspection of the product, aiming to ensure its integrity. Communication was established with the client, apprising them of the potential transit-induced damage and guaranteeing that a thorough assessment would address any concerns.

Despite an initial lack of observable damage, the diligent inspector persisted in the examination. This persistence yielded valuable results as it was eventually uncovered that the transformer had, indeed, incurred damage. Siemens conveyed this revelation to the client, enabling swift repair measures prior to the equipment’s deployment. The outcome not only translated into cost savings for Siemens, avoiding a full replacement but also protected the company’s client relationship from potential harm.

The absence of the Impact recorder alert could have led to undetected damage or, at the very least, a more protracted and challenging identification process.

Figure 3 – Impact recorder software screen showing that transformer had shock in transport (click to zoom)

Impact recorder software screen showing that transformer had shock in transport
Figure 3 – Impact recorder software screen showing that transformer had shock in transport

Go back to Content Table ↑


3. Nitrogen or Dry Air Pressure Check

Nitrogen and Dry Air Filling for Transport and Storage of Large Transformers

Large power transformers serve as critical components in electrical systems, facilitating the efficient transmission and distribution of electricity. The transportation of these substantial units from the manufacturing facility to their designated installation sites is a complex process that requires careful consideration of various factors.

Among these factors, the choice of internal filling medium, such as nitrogen or dry air, plays a pivotal role in ensuring the transformer’s integrity during transit and storage.

Suggested Video – Checking Power Transformer Nitrogen System

Go back to Content Table ↑


4. Transport Weight Reduction and Storage Considerations

To streamline the logistics of transporting large transformers, manufacturers often opt for the use of nitrogen or dry air as the filling medium within the transformer’s sealed compartments. This choice serves the dual purpose of reducing the overall transport weight and ensuring the preservation of the transformer’s critical components.

The inert nature of nitrogen or dry air minimizes the risk of oxidation and chemical reactions within the transformer during transit, safeguarding its structural and functional integrity.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Black Friday Deal 💥 – Save 20% on Pro Plan with code BLACKFRIDAY

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Muhammad Kashif - Author at EEP-Electrical Engineering Portal

Muhammad Kashif

Muhammad Kashif Shamshad is an Electrical Engineer and has more than 17 years of experience in operation & maintenance, erection, testing project management, consultancy, supervision, and commissioning of Power Plant, GIS, and AIS high voltage substations ranging up to 500 kV HVAC & ±660kV HVDC more than ten years experience is with Siemens Saudi Arabia.
Profile: Muhammad Kashif

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

  ×  3  =  27

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Save 20% with coupon BLACKFRIDAY.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.