Home / Technical Articles / Often wrongly interpreted: Terminals, isolating links and bars in wiring diagrams and schematics

Estimated Study Time: 29 minutes

Terminals, isolating links & bars

Terminals and other connecting elements, such as CT/VT shorting and isolating links, test blocks, and earthlings, often need to be better understood in analysing wiring diagrams and schematics. This can badly impact the testing and maintenance process, and sometimes, it can cause fatal injuries to personnel.

Often wrongly interpreted: Terminals, isolating links and bars in wiring diagrams and schematics
Often wrongly interpreted: Terminals, isolating links and bars in wiring diagrams and schematics

This technical article aims to take you on a journey through the fundamental terminals and other connecting elements of wiring diagrams and electrical schematics and to delve into the minute intricacies of the components that form them.

From the familiar male and female terminals that form the bedrock of electrical connections to the current and transformer shorting and isolating systems that safeguard the integrity of our circuits, we explore the key concepts, symbols, and functionalities that define the landscape of electrical engineering.

As we unravel the mysteries of male and female terminals, decipher the symbols for plugs and terminals, and explore the intricacies of transformers, protection systems, and beyond, our goal remains clear:

To empower you with the tools and understanding necessary to harness the power of electrical schematics and components in your own engineering endeavors.

Table of Contents:

  1. Male Terminal in Schematics
  2. Female Terminal in Schematics
  3. Symbol for Plug and Terminal
  4. Male Terminal Control Circuit
  5. Female Terminal in Control Circuit
  6. Connection Bar” or “Jumper”:
    1. Bypassing Components
    2. Setting Configuration Options
    3. Creating Redundancy
    4. Testing and Debugging
  7. Open Connection Bar (No Jumper Installed):
    1. Isolating Components
    2. Disabling Functionality
    3. Configuration Control
  8. Multi-terminal and Multiplug Connector:
    1. Key Features of Multi-terminal Connectors Include
  9. Current Transformer Shorting and Isolating Links:
    1. Key Functions of Current Transformer Shorting Links Include
    2. Key Functions of Current Transformer Isolating Links
  10. Voltage Transformer Isolation Links:
    1. Key Functions of Voltage Transformer Isolation Links
  11. Test Block in Protection and Control Panels
  12. Connection to Chasis
  13. PE Connection Point
  14. Earth/Ground Connection
  15. Main Conductor Symbol
  16. Secondary Conductor
  17. BONUS (PDF) 🔗 Download Operating and Maintaining Power Plant Equipment Guide

1. Male Terminal in Schematics

In schematic diagrams, a “male terminal” refers to a connector or contact point typically characterized by a protruding pin or prong that inserts into a corresponding “female terminal”. Male terminals are often found on components such as switches, relays, connectors, or integrated circuit packages.

They are designed to establish electrical connections with other components, devices, or circuitry, facilitating the transmission of signals, power, or data within an electrical system. The term “male” is used to describe these terminals because of their projecting nature, which allows them to be inserted into receptacles or sockets with corresponding female terminals.

Figure 1 – Symbol for the male terminal in schematics

Symbol for the male terminal in schematics
Figure 1 – Symbol for the male terminal in schematics

Go back to Content Table ↑


2. Female Terminal in Schematics

In schematic diagrams, a “female terminal” refers to a connector or contact point that typically features a receptacle or socket into which a corresponding “male terminal” can be inserted. Female terminals are commonly found in components such as connectors, jacks, plugs, or sockets.

They are designed to accept the insertion of male terminals, establishing electrical connections between components, devices, or circuitry. The term “female” is used to describe these terminals because of their receptacle nature, which allows them to receive and make contact with the projecting pins or prongs of male terminals.

Figure 2 – Symbol for female terminal in schematics

Symbol for female terminal in schematics
Figure 2 – Symbol for female terminal in schematics

Go back to Content Table ↑


3. Symbol for Plug and Terminal

In schematic diagrams, “plug” and “terminal” are two components commonly used to establish electrical connections within circuits:


Plug

A plug is a connector designed to be inserted into a corresponding receptacle, typically featuring male terminals. Plugs are often used to connect portable devices or components to a power source or to other devices within a circuit. They can vary in design depending on their intended application, such as audio jacks, power connectors, or data connectors.


Terminal

A terminal refers to a point in a circuit where electrical connections are made or terminated. Terminals can be male or female and are often represented in schematic diagrams as small nodes or connection points. They serve as the interface for connecting wires, components, or other conductors within a circuit.

Terminals can be found on various components such as switches, relays, connectors, or integrated circuit packages.

Figure 3 – Symbol for plug and terminal in schematics

Symbol for plug and terminal in schematics
Figure 3 – Symbol for plug and terminal in schematics

Go back to Content Table ↑


4. Male Terminal Control Circuit

In the context of a control circuit, a “male terminal” typically refers to a connector or contact point within the control circuit that features a protruding pin or prong designed to be inserted into a corresponding “female terminal.” These male terminals are often found on components such as switches, relays, connectors, or integrated circuit packages within the control circuit.

In control circuits, male terminals are used to establish electrical connections between various components, enabling the transmission of signals or control commands to activate or deactivate devices or systems.

They play a crucial role in facilitating the flow of control signals within the circuit, allowing for the operation and coordination of different elements within the control system.

Go back to Content Table ↑


5. Female Terminal in Control Circuit

In the context of a control circuit, a “female terminal” refers to a connector or contact point characterized by a receptacle or socket designed to receive and make contact with a corresponding “male terminal”.

Female terminals within a control circuit serve as points of connection for receiving male terminals from other components or devices. They enable the establishment of electrical connections necessary for the transmission of signals or control commands within the circuit.

Female terminals play a crucial role in facilitating the interaction and coordination between different components or subsystems within the control system, allowing for the effective control and operation of various devices or processes.

Figure 4 – Female and male terminals of control circuit

Female and male terminals of control circuit
Figure 4 – Female and male terminals of control circuit

Go back to Content Table ↑


6. Connection Bar” or “Jumper”

In electrical circuits, a “closed connection bar” or “jumper” refers to a conductive element that bridges or connects two or more points within a circuit, creating an uninterrupted electrical pathway.

Essentially, it serves to close a circuit, allowing current to flow between the connected points.

A closed connection bar can take various forms depending on the specific application and requirements of the circuit. It may be a physical component such as a small piece of wire, a metal strip, or a conductive clip that directly connects two terminal points on a circuit board or within a wiring setup.

Closed connection bars are commonly used in circuit design for several purposes:

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

TIme Limited!Save 15% on PRO membership plan with code RMS15.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Muhammad Kashif - Author at EEP-Electrical Engineering Portal

Muhammad Kashif

Muhammad Kashif Shamshad is an Electrical Engineer and has more than 17 years of experience in operation & maintenance, erection, testing project management, consultancy, supervision, and commissioning of Power Plant, GIS, and AIS high voltage substations ranging up to 500 kV HVAC & ±660kV HVDC more than ten years experience is with Siemens Saudi Arabia.
Profile: Muhammad Kashif

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.