Centrifugal Pumps & Variable Frequency Drives

The Pump Essentials

The affinity laws are applicable to pumps in the same manner as they are to fans. To comprehend Variable Frequency Drive (VFD) applications in pumps, it is advisable to examine the fundamental principles of pump utilization. Figure 1 illustrates a pump curve in relation to a hydronic system curve. The pump curve delineates the relationship between “head” (or pressure) and flow characteristics of a certain pump.

Practical guide to Variable Frequency Drives (VFDs) in retrofit and new applications
Practical guide to Variable Frequency Drives (VFDs) in retrofit and new applications

The curve indicates that the pump will yield restricted flow at point “B” when utilized in a system necessitating a substantial differential pressure to elevate the water/glycol and surmount flow resistance. Increased flow rates are attained with this pump when the pressure differential is diminished, as observed at point “A”.

Identifying the operational point of the pump on the pump curve necessitates data from the system curve. The system curve illustrates the attributes of the piping system. It illustrates the increase in “friction head” corresponding to flow rate.

Friction head quantifies the resistance to flow imposed by pipes, valves, elbows, and other system components.

Figure 1 – Pump curve relative to a hydronic system curve

Pump curve relative to a hydronic system curve
Figure 1 – Pump curve relative to a hydronic system curve

Static Head

The head needed with zero flow is referred to as static head or lift. Figure 2 illustrates the combined friction and static head curve for the system. The static head refers to the height in feet that the pump must raise the water, independent of flow rate. Another perspective is to consider it as the effort required to counteract gravity.

The convergence of the pump and system curves indicates the fundamental or designated operating point for the system. The pump pressure currently equals the system losses.

The intersection would typically be selected to guarantee that the pump operates at or near its optimal efficiency.

Figure 2 – Combined friction and static head curve for the system

Combined friction and static head curve for the system
Figure 2 – Combined friction and static head curve for the system

Flow Control

Two-Way Control Valves

Most hydronic systems do not consistently operate under design circumstances. Systems equipped with 2-way control valves regulate flow by adjusting the valve to different positions. Closing the valve diminishes flow and elevates friction inside the system.

Figure 3 illustrates a standard operating point attained when a specific flow is obtained by the control valve. Observe that the flow is attained, albeit at an elevated system pressure.

Three-way control valve systems regulate consistent pressure by diverting flow from the pump discharge back to the pump suction. Although optimal flow is preserved, both pump flow and energy consumption remain constant, resulting in no energy savings.

See Figure 3.

Figure 3 – Typical operating point when a particular flow is achieved by the control valve

Typical operating point when a particular flow is achieved by the control valve
Figure 3 – Typical operating point when a particular flow is achieved by the control valve

Pump Energy Savings With VFDs

Utilizing a VFD on a pump to decrease speed and consequently flow results in a downward shift of the pump curve, as illustrated in Figure 4. The operating point remains at the newly adjusted pump curve and system curve, resulting in the same reduced flow of 700 GPM, down from 1200 GPM, as observed with a valve.

This flow is attained, albeit at a diminished pressure. Operating under diminished pressures can lead to an extended lifespan of pump seals, less impeller degradation, and minimized system vibration and noise.

The affinity rules indicate that power decreases substantially at lower flow rates, resulting in considerable savings!

See Figure 5.

Figure 4 – Applying a VFD to a pump to reduce speed and flow causes the pump curve to shift down

Applying a VFD to a pump to reduce speed and flow causes the pump curve to shift down
Figure 4 – Applying a VFD to a pump to reduce speed and flow causes the pump curve to shift down

Figure 5 – Due to the affinity laws, power is greatly reduced at reduced flows

Due to the affinity laws, power is greatly reduced at reduced flows
Figure 5 – Due to the affinity laws, power is greatly reduced at reduced flows

Applying VFDs To Pumps To Realize Savings

Similar to most HVAC systems, original pump designs may be predicated on worst-case maximum flow scenarios for potential future expansion, or the designer may have applied the standard 15 to 20% over-sizing criterion. When assessing VFD retrofit prospects for energy conservation, one should examine the system and pump curves and analyze the current flow modulation mechanism.

See Figure 1.

  • BYPASS: If bypass control is employed (for instance, a 3-way valve at the coils), the system maintains a consistent pressure at all times. Refer to ‘CP’ in Figure 6. The potential for savings can be substantial in the absence of modulation when retrofitting VFDs.
  • 2-Way VALVE CONTROL: The system operates throughout the pump curve from the Operating Point to P3 when 2-way valves are utilized. These systems consume less energy than constant pressure systems.

If a VFD is utilized, the system will run along the system curve from the Operating Point to V3.

Figure 6 – Applying VFDs To Pumps To Realize Savings

Applying VFDs To Pumps To Realize Savings
Figure 6 – Applying VFDs To Pumps To Realize Savings

Static Head

Static head can influence potential energy savings. If the static head is elevated, the system curve may approximate a constant pressure. Figure 7 illustrates a pump curve accompanied by three system curves: one representing zero static head and two others with varying static heads. The disparity between points A and B indicates potential energy savings for a specified flow rate.

The lower the static head, the larger the potential energy savings with variable frequency drives (VFDs).

Figure 7 – Three system curves: one with no static head, and two others different static heads

Three system curves: one with no static head, and two others different static heads
Figure 7 – Three system curves: one with no static head, and two others different static heads

Determining Pump & System Curves

Pump curves are easily obtainable from manufacturers, whereas system curves are more challenging to ascertain. A rapid technique to estimate the curve:

  1. Determine the un-throttled (open) system flow rate at the location under consideration. (you may need to measure this at different locations or have a balancer establish this for you)
  2. Measure the static head
  3. Plot these two points on a copy of the pump curve.
  4. Connect these points using a square function : Head = Flow2
Title:Practical guide to Variable Frequency Drives (VFDs) in retrofit and new applications by Yorkland Controls Ltd
Format:PDF
Size:20.8 MB
Pages:36
Download:Right here | Video Courses | Membership | Download Updates

Suggested (PDF) – A practical handbook for electrical engineers (beginners)

A practical handbook for electrical engineers (beginners)

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.