Home / Technical Articles / MCC Circuit Featuring Auto Re-Closure Relay Functionality

Estimated Study Time: 10 minutes

MCC Circuit for Critical Motors

An MCC circuit of a motor could be based on the Direct Online Starter (DOL) or Star Delta Starter which has something to do with the requirement of the power system in an industry. But it could have additional logics depending upon the requirement of the process. In that regard, a very important feature of MCC circuits is auto/manual start-up selection for motors.

MCC Circuit Featuring Auto Re-Closure Relay Functionality
MCC Circuit Featuring Auto Re-Closure Relay Functionality

In case of a power interruption of a few minutes followed by power restoration or energization of back-up source in the meantime, it could take long before the control room operator sitting on his desk switches on all the critical motors such as those responsible for the lubrication and barring of turbines, compressors and pumps.

This is where an additional circuit is built into the MCC cubicles of critical motors where they are given a manual selection option (besides auto-mode or the one handled by the operator) and started locally on the field.

In this manual start-up selection, a re-closing relay setup is incorporated into the circuit, which is nothing but a combination of off-delay and on-delay timers so that when the power recovers in a quick time, the lubrication pump or barring motor starts automatically without the involvement of the operator.

Ok, let’s get into the discussion.

Circuit Diagram

Attached below is the simple DOL starter control circuit diagram of a motor. Let’s dissect the circuit diagram in detail,

Figure 1 – Simple DOL starter control circuit diagram of a motor (click to zoom)

Simple DOL starter control circuit diagram of a motor
Figure 1 – Simple DOL starter control circuit diagram of a motor

Where:

  • Auto / Man – Auto/Manual Selector Switch
  • E – Stop Control Switch
  • F – Start Control Switch
  • OLR – Overload Relay Contact
  • f and g – Field Stop Interlocks
  • LCN – Main Power Contactor
  • LCNX – Auxiliary Contactor
  • TMR1 – Off-delay timer
  • TMR2 – On-delay timer
  • d – Test pushbutton

MCC Circuit on Auto-Mode

When the breaker is racked in as highlighted in green, the signal is passed through auto contact L to the main power contactor LCN of the motor. This closes the LCN contact thus energizing the auxiliary contactor LCNX and the motor starts.

The off-delay timer TMR1 is also energized at the same time, however, it doesn’t play any role in auto-mode.

Figure 2 – MCC Circuit on Auto-Mode (click to zoom)

MCC Circuit on Auto-Mode
Figure 2 – MCC Circuit on Auto-Mode

Circuit on Manual-Mode

Now let’s understand the working on manual mode and re-closure relay functionality through the below circuit diagram. When the selection is on manual mode, the only thing stopping the motor from starting is “F” as marked in green, which is the start control station installed locally on the field.

Once the start control station “F” is pressed, the signal is passed and the main power contactor LCN latches, thereby, starting the motor.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know!Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Umer Nasir - Author at EEP-Electrical Engineering Portal

Umer Nasir

I am an electrical engineer specializing in electrical power, with experience in the operation and maintenance of Low- and Medium-voltage electric machinery and switchgear, life assessment testing, troubleshooting, and root cause analysis of various failures associated with electrical machinery.
Profile: Umer Nasir

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.