Magnetic and electric fields influence

The electromagnetic fields occurring in substations due to the high currents and high voltages produce different effects on people and objects nearby. High levels of permanent magnetic or electric fields have impacts on the health of people exposed to them. These effects depend on the field strength and duration of exposure. There are specific legislations specifying the maximum values that should not be exceeded.

Solving health and EMC problems due to magnetic and electric fields in substations and neighborhood
Solving health and EMC problems due to magnetic and electric fields in substations and neighborhood

Permanent magnetic fields can also cause effects of magnetic induction and overheating in metal parts near to their source. In addition, transient magnetic fields produced by high currents at rated frequency (short circuit) or higher frequencies like in the switching of capacitive circuits, can induce high voltages in the control circuits and other closed circuits in substations.

The focus of this report is the calculation of the values, which may occur, depending on the geometry of the object under study and the values of currents and voltages involved. The object may be a complete substation or an enclosed metallic equipment.

The more frequent objectives of such studies are:


Objective #1

To verify if the values of electromagnetic fields in a substation are lower than the reference levels established in references like ICNIRP “Guidelines for Limiting Exposure to Time-varying Electric and Magnetic Fields (1 Hz to 100 kHz)”. There you may find limits for human exposure to electric and magnetic fields in generation, transmission and distribution of electricity.

ICNIRP means International Commission on Non‐Ionizing Radiation Protection.

Figure 1 – Magnetic field inside a low voltage switchgear (Three phase currents 3200 A and with aluminum enclosure + non-magnetic supports)

Magnetic field inside a low voltage switchgear (Three phase currents 3200 A and with aluminum enclosure + non-magnetic supports)
Figure 1 – Magnetic field inside a low voltage switchgear (Three phase currents 3200 A and with aluminum enclosure + non-magnetic supports)

Objective #2

To see if local gradients of voltage / electric field are higher than the values which could produce a dielectric discharge or corona in an energized circuit


Objective #3

To see if the magnetic field acting in a metal plate or part is sufficient to produce overheating by magnetic induction.

This report intends to help the users of the software SwitchgearDesign to do validations of their simulations.

The software permit to simulate:

  1. Temperature rise tests
  2. Short time current and crest tests (electro dynamical forces)
  3. Internal arc tests.
  4. Mapping of electric and magnetic fields. This ability enable the user to estimate the results of dielectric tests (impulse and applied AC voltage) as well as to solve EMC (Electromagnetic Compatibility) problems.

Table 1 – Tolerances between test results and simulation results

Type of testParameter to compareTypical values of acceptable tolerance
Temperature rise testTemperature rise in solid and fluid parts1% to 5%
Internal arc testOverpressure in the enclosure above the atmospheric pressure (crest and duration)5% to 10%
Short-time withstand current and peak withstand current testsElectrodynamic forces and mechanical stresses5% to 15%
Magnetic and electrical field mappingModule and XYZ components of the field at any point5%

Such validations are to prove, transparently, that the simulation results are within an acceptable tolerance from the values of the actual results obtained in the laboratory tests. Table 1 present values of acceptable tolerances considered here. These values as well as a “technical standard” for the use of simulatio are in Annex F.

An IEC technical standard is missing on this theme and so, this is the best reference in the moment.

Title:Solving health and EMC problems due to magnetic and electric fields in substations and neighborhood – Cognitor
Format:PDF
Size:2.0 MB
Pages:37
Download:Here 🔗 (Get Premium Membership) | Video Courses | Download Updates

Further Study – A Guide to Substation Earthing Design and Understanding Dangerous Voltages

A Guide to Substation Earthing Design and Understanding Dangerous Voltages

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount - Save 50% on all 110+ video courses with Enterprise Membership plan.

More Information

One Comment


  1. Samir Sadek Ismail
    Jul 13, 2025

    I am well satisfied of all what you present as educative topics which had help us more than we have expected, Indeed thanks a lot.

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.