Search

Premium Membership ♕

Save 50% on all EEP Academy courses with Enterprise Membership Plan and study specialized LV/MV/HV technical articles & guides.

Home / Technical Articles / An example of calculating transformer size and voltage drop due to starting of large motor

Calculate voltage drop

Let’s calculate voltage drop in transformer 1000KVA, 11/0.480 kV, impedance 5.75% due to starting of  300 kW, 460V, 0.8 power factor, motor code D (kva/hp). Motor starts 2 times per hour and the allowable voltage drop at transformer secondary terminal is 10%.

Medium-voltage motor starting transformer
Medium-voltage motor starting transformer (man. J. Schneider Elektrotechnik; photo credit: DirectIndustry)

Calculation can be checked by using this MS Excel Spreadsheet dedicated especially to this kind of problem.

Ok, let’s get into the calculations…


Motor current / Torque

Motor full load current = (Kw x 1000) / (1.732 x Volt (L-L) x P.F

  • Motor full load current = 300 × 1000 / 1.732 x 460 x 0.8 = 471 Amp.
  • Motor locked rotor current = Multiplier x Motor full load current

Locked rotor current (Kva/Hp)

Motor CodeMinMax
A3.15
B3.163.55
C3.564
D4.14.5
E4.65
F5.15.6
G5.76.3
H6.47.1
J7.28
K8.19
L9.110
M10.111.2
N11.312.5
P12.614
R14.116
S16.118
T18.120
U20.122.4
V22.5
  • Min. motor locked rotor current (L1) = 4.10 × 471 = 1930 Amp
  • Max. motor locked rotor current (L2) = 4.50 × 471 = 2118 Amp
  • Motor inrush Kva at Starting (Irsm) = Volt x locked rotor current x Full load current x 1.732 / 1000
  • Motor inrush Kva at Starting (Irsm) = 460 x 2118 x 471 x 1.732 / 1000 = 1688 kVA

Transformer

  • Transformer full load current = kVA / (1.732 x Volt)
  • Transformer full load current = 1000 / (1.73 2× 480) = 1203 Amp.
  • Short circuit current at TC secondary (Isc) = Transformer full load current / Impedance
  • Short circuit current at TC secondary = 1203 / 5.75 = 20919 Amp
  • Maximum kVA of TC at rated Short circuit current (Q1) = (Volt x Isc x 1.732) / 1000
  • Maximum kVA of TC at rated Short circuit current (Q1) = 480 x 20919 x 1.732 / 1000 = 17391 kVA
  • Voltage drop at transformer secondary due to Motor Inrush (Vd) = (Irsm) / Q1
  • Voltage drop at transformer secondary due to Motor inrush (Vd) = 1688 / 17391 = 10%
  • Voltage drop at Transformer secondary is 10% which is within permissible limit.
  • Motor full load current ≤ 65% of Transformer full load current
  • 471 Amp ≤ 65% x 1203 Amp = 471 Amp ≤ 781 Amp
Here voltage drop is within limit and Motor full load current ≤ TC full load current.

Size of Transformer is Adequate.

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
author-pic

Jignesh Parmar

Jignesh Parmar has completed M.Tech (Power System Control), B.E (Electrical). He is member of Institution of Engineers (MIE), India. He has more than 20 years experience in transmission & distribution-energy theft detection and maintenance electrical projects.

42 Comments


  1. Minu
    Apr 20, 2015

    There is a error in the attached excel calculator. It calculated kVA by multiplying kW and power factor. Actual equation is kVA=kW/power factor.


  2. bhavin mistry
    Jan 28, 2015

    Dear sir, i want know about maximum secondry connectable load as per transfor mer rating


  3. Djarot Prasetyo
    Nov 15, 2014

    Hi! I’d like to know, what standard did you use for the locked rotor current?
    Thanks!


  4. Benn Richey
    Sep 02, 2014

    There’s an error in the calculations above: “Motor inrush Kva at Starting (Irsm) = 460 x 2118 x 471 x 1.732 / 1000 = 1688 kVA”
    It should be: Motor inrush Kva at Starting (Irsm) = 460 x 4.5 x 471 x 1.732 / 1000 = 1688 kVA


  5. Mujeeb Raza
    Aug 28, 2014

    Hi All,
    I want to get this into detail, if the output of this transformer is connected to load of small industries (assume same data), What factors are to look into while selecting cable for the secondary of transformer up to the LV panel.


  6. Zulfiqar Ali
    Aug 20, 2014

    Dear sir i hope u r doing fine..your website is very helpfull for engineering articles.many thanks for creating a such type of website.
    but in above article there is a slight mistake in calculations.i hope u ll remove and correct it immediately to avoid more confusions between engineers
    Motor inrush Kva at Starting (Irsm) = 460 x 2118 x 471 x 1.732 / 1000 = 1688 kVA
    in above equation 471 is repeating .which should not b repeated
    this equation should be
    Motor inrush Kva at Starting (Irsm) = 460 x 2118 x 1.732 / 1000 = 1688 kVA

    hope u got my point.

    Thanks And Regards,

    Engr Zulfikar Ali


  7. Mayank P Shah
    Aug 13, 2014

    We are going to set up a new project.Biggest motors are of 260 KW x 2 and 245 KW x 4.
    Total running load is expected of 3100 KVA.Please let us know the size of Dist.Transformer of 11 / 0.433 KV when we starts these heavy motors.All motors are proposed by VFD.We are working around 3500 KVA Transformer.Please guide us.


  8. haytham151
    Jun 21, 2014

    It’s v.g refreshable exp , but l have to wander if i missed something here or you make amistake by the formula :
    Motor inrush Kva at Starting (Irsm) = Volt x locked rotor current x Full load current x 1.732 / 1000
    I think you point to :

    Motor inrush Kva at Starting (Irsm) = Volt x locked rotor current x Full load current x 1.732 / 1000


    • haytham151
      Jul 12, 2014

      Motor inrush Kva at Starting (Irsm) = Volt x locked rotor current x 1.732 / 1000


  9. vinod
    Jun 08, 2014

    Please furnish relevant standard for the portion” Motor full load current ≤ 65% of Transformer full load current”.
    Efficiency not considered while calculating full load current of motor.


  10. Mohammed zougti
    May 30, 2014

    Mistake
    •Motor inrush Kva at Starting (Irsm) = 460 x 2118 x 471 x 1.732 / 1000 = 1688 kVA

    Should be •Motor inrush Kva at Starting (Irsm) = 460 x 2118 x 1.732 / 1000 = 1688 kVA


  11. P.Paulpandy.
    May 21, 2014

    I have found formula of motor inrush kva at starting time wrong because when i use your formula the motor kva must be 795353 kva ( motor capacity is 300 kw). but, i see your electrical article 1688 kva.

    Please check and clarify.


  12. Maher M. Al Qadhi
    May 18, 2014

    Dear Sir

    I hope you are doing well.
    And thank you for this useful example
    I have one question which is if I want to calculate the transformer size & volt drop due to building of 11.89 Km square.
    Can I use the important above tips to calculate it ?

    thank you again.


  13. Amr Ahmed
    May 18, 2014

    This calculation for DOL motor starting only or for any starting method , also kindly give me information about the following standard in the point ”Motor full load current ≤ 65% of Transformer full load current ”.

    Thanks & Regards


  14. subrata deb
    May 16, 2014

    Following points to be considered even assuming that prior to starting of this motor

    there is no other load which is fed by the transformer:

    1) 300KW is the output rating of motor.Therefore efficiency of motor should be considered
    to find F.L current 2) +10% tolerance on percentage impedance of transformer should be considered

    As per IS 6600, all the parts of transformer are designed to carry maximum overload

    of +50%. Therfore it should be checked that motor starting kva must be within 1.5 times of
    transformer capacity.

    The logic that motor F.L current shall be less or equal to 65% of transformer rated current is not clear. Please furnish the relevant standard.


  15. Lalit Kumar
    May 13, 2014

    The above calculations does not consider additional loads which might be fed from the same transformer feeding the large motor.

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

seven  ×  one  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
EEP Academy Courses - A hand crafted cutting-edge electrical engineering knowledge