Inspection and test procedures for Rotating Machinery, Synchronous Motors and Generators
Visual and Mechanical Inspection Electrical Tests Test Values Visual and Mechanical Tests Electrical Tests Pictures: Electrical machine wired for electrical testing The Electrical Machines Laboratory TABLE 100.10 – Maximum Allowable Vibration Amplitude TABLE 100.12 – US Standard Fasteners Compare equipment… Read more
Feb 19, 2014 | By Edvard Csanyi
Power Transformer Capacitance and Dissipation Factor Test
The capacitance and dissipation factor test is an AC low voltage maintenance test and is very similar to the power factor test. While the transformer preparation is identical to the power factor test procedure, there is no requiremnts to make… Read more
Jan 22, 2014 | By Edvard Csanyi
How to perform a power transformer turns ratio test
Power transformer turns ratio test is an AC low voltage test which determines the ratio of the high voltage winding to all other windings at no-load. The turns ratio test is performed on all taps of every winding. The Transformer… Read more
Jan 17, 2014 | By Edvard Csanyi
Field Inspection and Testing of Medium-Voltage Motor Control Centres (MCCs)
Check MCC equipment for: alignment, levelness, and tightness of all bolting. Check all equipment for: removal of blocking, supports, temporary ties, and temporary wire jumpers. Check that all protective barriers are properly installed. Check door alignment of individual starter units… Read more
Oct 28, 2013 | By Edvard Csanyi
Eight important checks to do before powering up the dry-type transformer
The transformer should be powered up only after checking the following items: name plate ratings, parallel operation, connections: cables, busbars, tap change connections, grounding connection, thermal protective device, impurities removal and insulation resistance test. Make sure the name plate ratings… Read more
Oct 23, 2013 | By Edvard Csanyi
Testing and commissioning procedure for electric motors
It should be noted that the scope of motor testing depends upon the motor type and size, this being indicated on the inspection forms. Motor vibration shall be measured in a tri-axial direction, i.e.: Point x axis – side of… Read more
Sep 20, 2013 | By Edvard Csanyi
Identifying The Primary And Secondary Phasor Polarities Of Transformer – Polarity Test
This is needed for identifying the primary and secondary phasor polarities. It is a must for poly phase connections. Both a.c. and d.c methods can be used for detecting the polarities of the induced emfs. The transformer is connected to… Read more
Aug 26, 2013 | By Edvard Csanyi
Commissioning of HV Panel – Operational and Functional Checkup
The main objective of the test is to check the proper operation function of the circuit breaker; in this test we do the following: This test is conducted by manual, Local and Remote. For the manual Operation test, we will… Read more
Jul 17, 2013 | By Edvard Csanyi
High voltage testing – Direct current (DC)
DC tests are used mainly to do “pressure tests” on high voltage cables. Although the cables operate with AC, AC testing is not practical. The high capacitance of the cables necessitates AC test sets with a high kVA rating to… Read more
Jun 01, 2013 | By Edvard Csanyi
Condition Monitoring of Transformers
It is possible to provide transformers with measuring devices to detect early signs of degradation in various components and provide warning to the operator in order to avoid a lengthy and expensive outage due to failure. The technique, which can… Read more
May 24, 2013 | By Edvard Csanyi
Transformer Routine Dielectric (Insulation) Test
The following insulation tests are performed in order to meet the transformer insulation strength expectations. Unless otherwise requested by the customer, the following test are performed in the following order (IEC 60076-3) : To confirm the insulation of the transformer terminals… Read more
May 23, 2013 | By Edvard Csanyi
Erection Procedure for Power Transformer
This technical article deals with transformers and their installation so we restrict ourselves here to the procedures associated with their commissioning. Transformers should be inspected for internal or external damage, particularly if they have been dropped or tipped over. This should include such… Read more
May 20, 2013 | By Edvard Csanyi
When a transformer has stomach pain and wants to…
During normal operation, transformer internal structures and windings are subjected to mechanical forces due to the magnetic forces. These forces are illustrated in Figure 1. By designing the internal structure very strong to withstand these forces over a long period of… Read more
May 08, 2013 | By Edvard Csanyi
Erection procedure for HV switchgear (Part 2)
Continued from first part: Erection procedure for HV switchgear (Part 1) Positioning of the cubicles should start near to the centre of the switchboard, installing as early as possible the enclosures associated with any special chambers or trunking. The first… Read more
May 01, 2013 | By Edvard Csanyi
Erection procedure for HV switchgear (Part 1)
Before commencing erection of HV switchgear check that all connections are tight on busbars and on main circuits as well as auxiliary circuits. Examine the insulation very carefully, because there have been reported cases of burned out connections due to… Read more
Apr 29, 2013 | By Edvard Csanyi