Power supply in buildings

When designing electricity supply to a residential building, design power for both separate groups of the switchgear and the feeding lead in general must be determined, considering the existing or planned using equipment. Three-phase, two-phase, and single-phase using equipment can be connected to three-phase switchgear.

Electrical installation design of residential buildings (practical guidelines)
Electrical installation design of residential buildings (practical guidelines)

Calculation of 3-phase SC current

To be able to select and test electrical apparatuses and conductors, for example in the switchgear cable of a residential building, three-phase short-circuit currents both before 10 kV or 20 kV transformer and after the transformer on the 0.4 kV side must be taken into account in calculations.

For the calculation of short-circuit current according to the design circuit diagram (Figure 1a), a substitution circuit diagram (Figure 1b) must be drawn up.

Resistances of electrical apparatuses on the high-voltage side are not taken into account in calculation of short-circuit currents, as they are very small.

Example of a fragment of electric supply circuit for a residential house
Figure 1 – Example of a fragment of electric supply circuit for a residential house: a) design circuit; b) substitution circuit, where K1โ€“K4 is short-circuit point

Three-phase short-circuit current is calculated as follows:

Three-phase short-circuit current formulae

where:

  • ES โ€“ system electromagnetic force, V;
  • ZS โ€“ total impedance, โ„ฆ.

Calculation of single-phase short-circuit current

Single-phase short-circuit current is calculated to test the sensitivity of electrical apparatuses. It is very important as single-phase short-circuit current may be the decisive one in selecting protective devices in some cases. In practice, when protective devices are selected, one-phase short-circuit currents are often disregarded.

In low-voltage networks with earthed neutral, the symmetrical component method is used in the calculations of single-phase short-circuit current. Figure 2 shows shorted loop with resistance values used in the design.

Design circuit of one-phase short-circuit loop
Figure 2 – Design circuit of one-phase short-circuit loop

Positive sequence component of single-phase short-circuit current

where:

  • Uf โ€” phase voltage
  • ZT โ€” transformer impedance
  • Rf โ€” resistance of phase wire
  • Xfโ€ โ€” internal inductive reactance of phase wire
  • RN โ€” resistance of neutral conductor
  • XNโ€ โ€” internal inductive reactance of neutral conductor
  • Xcโ€™ โ€” external inductive reactance of short-circuit loop
Title:Electrical installation design of residential buildings (practical guidelines) – Riga Technical University; Institute of Power Engineering; Department of Electric Power Supply
Format:PDF
Size:3.1 MB
Pages:42
Download:Right here | Video Courses | Membership | Download Updates
Electrical installation design of residential buildings (practical guidelines)
Practical guidelines to electrical installation design of residential buildings

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
More Information

3 Comments


  1. Marc A RICHARDSON
    Apr 27, 2022

    Ive been in this industry for more than 40 years and would love to be a ingeneer very much interrested in solar as well


  2. Jack
    Mar 09, 2022

    Hi, There is nice work, I have checked all the necessary and was really amazed that I found all related to them very quickly. I have also found this amazing website that teaches for free


  3. Gajjela kushali
    Dec 19, 2019

    Instrument transformers in 132KVSS

Leave a Reply to Marc A RICHARDSON

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

three  ×    =  15

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).