Individual PFC for transformers

The utility regulations for the allowable size of capacitors permanently connected to a transformer vary according to region. Before installing a PFC system of this type, it is therefore advisable to consult the utility company concerned.

Power Factor Correction: Theory, Methods, Applications, Specification and Installation
Power Factor Correction: Theory, Methods, Applications, Specification and Installation (on photo: PFC module by FRAKO)

The modern design of transformer features core laminations that only require a small amount of power for reversal of magnetization. If the capacitor power rating is too high, overvoltage conditions may occur during no-load operation.

Capacitors with built-in fuse switch disconnectors are well suited for this duty.

If capacitors with fuse switch disconnectors are connected directly to the transformer terminals, the designer should be aware of the fact that the lines to the capacitor are dimensioned for the full short-circuit power.

Typical transformer with permanent power factor correction
Figure 1 – Typical transformer with permanent power factor correction

The capacitor with fuse switch can be directly connected to the terminals of the transformer. This means that the lines to the capacitor must be dimensioned for the full short-circuit power. The fuse switches are operated under purely capacitive load.

They must therefore never be withdrawn when under load or dangerous arcing may otherwise occur!

Table 1 – Approximate capacitor ratings for individual power factor correction of transformers according to the German Association of Energy and Water Industries (BDEW)

Transformer nominal rating [kVA]Capacitor power rating [kvar]
100 – 1602.5
200 – 2505.0
315 – 4007.5
500 – 63012.5
80015.0
100020.0
125025.0
160035.0
200040.0

If it is possible to disconnect the capacitor even when the transformer is switched on, a power capacitor with an automatic circuit breaker must be used.


Individual PFC for motors

The capacitor power rating should be some 90% of the motor apparent power when running under no-load conditions.
Required capacitor power rating:

Qc [VAR] = 0.9 × √3 × V × I0

where: I0 is no-load motor current.

This produces a power factor of about 0.9 under full load and 0.95 – 0.98 under no-load conditions. The German Association of Energy and Water Industries (BDEW) recommends the approximate capacitor ratings for induction motors running at 1500 min-1.

The values given in the table should be increased by 5% for motors running at 1000 min-1, or by 15% for motors running at 750 min-1.

Title:Power Factor Correction: Theory, Methods, Applications, Specification and Installation – Peter Riese, FRAKO
Format:PDF
Size:4.6 MB
Pages:72
Download:Right here | Video Courses | Membership | Download Updates
Power Factor Correction: Theory, Methods, Applications, Specification and Installation
Power Factor Correction: Theory, Methods, Applications, Specification and Installation

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount 💥 - Save 50% on all 90+ video courses with Enterprise Membership plan.

More Information

One Comment


  1. Hugo Gil Figueroa
    Mar 17, 2020

    Very useful infomation.

Leave a Reply to Hugo Gil Figueroa

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

five  ×  5  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
EEP Academy Hand-Crafted Courses
MV Switchgear Components