Search

Premium Membership ♕

Learn from experienced engineers and study specialized technical articles, studies & courses. Save 50% on courses with the Enterprise Plan.

Home / Download Center / Electrical Engineering Books and Technical Guides / Electricity generation, t&d guides / Insulation coordination study for an ultra-high voltage (UHV) AC transmission system

Insulation coordination study

Over time there has been a significant rise in demand and transferring such a huge amount of power from generating stations to distribution substations via 765kV transmission lines have comparatively more losses (I2R losses) than if the voltage is higher. This gives rise to Ultra High Voltage (UHV) systems. UHV systems deal with voltages up to 1200kV.

Insulation coordination study for an ultra-high voltage (UHV) AC transmission system
Insulation coordination study for an ultra-high voltage (UHV) AC transmission system

China has been constructing a 1000kV UHV system and has been facing many technical issues and it has been increasing prominently. For any electrical system, insulation coordination and overvoltage protection are the most critical issues to be addressed.

Insulation Coordination is a designing criterion for any electrical equipment which enables the design of insulation for the equipment in such a way that it minimizes interruptions during steady-state conditions and also minimizes damages in case of transient overvoltages and this is done economically.

To achieve this goal we must have information regarding stress, strength and protection of the system. Stress is the rise in the voltage due to lightning, switching surges, etc. Strength can be defined as the dielectric withstand capability of various insulation systems.

Protection devices eliminate surges or reduce their effect.

Before constructing an actual transmission system for any system, data regarding the topological area is taken, these data are useful to predict faults in the foreseeable future and to design the system accordingly.

Transmission tower under consideration
Transmission tower under consideration

EHV/UHV systems and insulation coordination

Ultra-high voltage (UHV) systems are created to satisfy large power transmission requirements and hence becomes important to reduce transients over the system which could lead to system failure. Similar to Extra high voltage (EHV) a number of factors affect the insulation strength.

However, in UHV the time to crest in switching overvoltage can be higher than 250 μs.

The methodology while implementing insulation coordination is to determine the stresses and assess the strength of the system on the basis of quantitative analysis or a perceived degree of reliability. So for this process, all sources of stress that can be applied to the system is considered and the minimum insulation strength should be greater than the applied stress under all circumstances.

The possible choices for Basic lightning impulse insulation level (BIL) for a 1200 kV system range from 2100 to 2700 kV peak and Basic switching impulse insulation level (BSL) ranges from 1675 to 1950 kV. Any system is checked before installation, a severe voltage surge is injected in the equipment for various operating conditions to check for maximum overvoltage, this result is compared to the specified basic lightning impulse insulation level (BIL) of the equipment.

To be able to perform a productive insulation coordination study, the outcome of the study will be a selection of specifications of electrical strengths of all equipment, the phase to ground, phase to phase clearances and the leakage or creepage distance of external porcelain.

According to need surge arrester must also be selected.

The transmission and distribution circuits which connect a substation, load centres, act as a telephone line picking up surges and delivering them to the opposite end. This is especially true when it comes to lightning overvoltages. If these surges have higher voltages than what the equipment can withstand then these surges should be prevented from reaching the equipment or at least must be mitigated to acceptable values of faults that the system can withstand.

Of the various overvoltages that occur in any system as mentioned below, insulation coordination should withstand all of them and if there are cases where the system fails to withstand the overvoltage then protective devices must be implemented in those cases to bring the overvoltage range within the required limits.


Overvoltages in Ultra High Voltage Systems

Types of overvoltages in the UHV system according to their duration.

Representation of magnitude of over voltages v/s duration
Representation of magnitude of over voltages v/s duration

1. Temporary Overvoltage

Mainly arises due to single-phase earth faults on the lines except on which the fault occurs. Temporary overvoltages increase the stress on internal insulation and are present for a duration of around 1 second. Further temporary voltages can also occur due to resonance and ferroresonance while energizing and de­energizing transformers.

Load rejection overvoltages caused in Ultra High Voltage (UHV) usually are severe compared to extra-high voltage (EHV) due to lengthier transmission lines higher capacity. Shunt reactors, temporary overvoltage protection relays are used to mitigate the effects of temporary overvoltages.


2. Slow Front Overvoltage Analysis

Mainly due to earth faults on the faulty line. The consequence could be loss of 3 lines due to failure in one phase. The magnitude of such overvoltage can reach up to 1.5 p.u.


3. Fast Front Overvoltages

Mainly due to lightning on overhead lines and disconnector switching in substations. Disconnector switching in substations can have overvoltage as high as 7 p.u. Protective devices are needed in such cases to reduce the voltage as the nominal voltage itself is as high as 1200 kV.

This is the main focus of this paper as fast front overvoltages provide maximum stress on the system.


4. Very Fast Front Overvoltage

Mainly due to disconnector switching operation and line to enclosure breaks down in SF6 gas-insulated substations. Overvoltages up to 2 p.u. can occur due to these faults.

Various protection devices such as Surge Arresters, Pre-Insertion Resistors/Inductors, Synchronous Close/Open Control, Surge Capacitors are among the few equipment that can be used to mitigate overvoltages in UHV.

Title:Insulation coordination study for an ultra-high voltage (UHV) AC transmission system – Dr. Bruce Mork, Harshil Patel, and Ravi Raj Gupta at Michigan Technological University
Format:PDF
Size:2.1 MB
Pages:38
Download:Right here | Video Courses | Membership | Download Updates
Insulation coordination study for an ultra-high voltage (UHV) AC transmission system
Insulation coordination study for an ultra-high voltage (UHV) AC transmission system

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount 💥 - Save 50% on all 90+ video courses with Enterprise Membership plan.

More Information

4 Comments


  1. Parantap K Raha
    Dec 10, 2021

    Excellent Topic


  2. SURINDER KUMAR
    Aug 04, 2020

    THIS IS VERY GOOD INFORMATION FOR ME BEING A ELECTICAL ENGINEER IN j&k STATE WE ARE DEALING UPTO 220KV LINES AND SUBSTATIONS.

    THANKS AND REGARDS


  3. Ideh Jude
    Aug 04, 2020

    How can this be applied in Nigeria


  4. Muhammad Usama Hameed
    Aug 04, 2020

    Insulation of material that repels the electric and magnetic field of flowing current

Leave a Reply to Parantap K Raha

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

  +  3  =  six

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
EEP Academy Courses - A hand crafted cutting-edge electrical engineering knowledge