Search

Premium Membership

Save 15% on Pro Premium Plan with discount code: SX79 (expires on May 31st). Study specialized LV/MV/HV technical articles and papers.

Home / Download Center / Electrical Engineering Books and Technical Guides / Electricity generation, t&d guides / Online partial discharge measurements as a proven way to diagnose power cables

Power cables

MV cables in power networks

Transmission and distribution of large quantities of power, as in power networks, can be established in two ways: with overhead lines (or overhead cables) and with underground power cables. In the early days of electrification, cable technology was just in its beginnings so mainly overhead lines were used. Nowadays, power cables are available for a wide range of voltage and power levels.

Online detection and location of partial discharges in MV cables
Online detection and location of partial discharges in MV cables (photo credit: si-powerline.com)

Still, from an investment-costs point of view, overhead lines usually are preferred. However, regarding aesthetical and environmental considerations, safety issues, regulations but also technical matters, power cables can have the advantage.

Furthermore, if the operation costs, including maintenance, are taken into account, power cables can also be competitive, which especially applies for medium-voltage (MV) networks.

The installed power-cable length is also increasing, because of the ever increasing demand for power. This is especially the case for distribution-class cables, operating in the range of 1 kV – 36 kV. In many countries, a large part of the medium and low voltage grid is constructed with power cables.

In the Netherlands e.g., this is virtually 100 %. The total length of the MV cables in the Netherlands alone is already approximately 100,000 km, which corresponds to an investment of about 5×109 euros.

Medium-voltage power cables are usually applied for distribution of power from a substation to what are often called ‘ring main units’ (RMUs), where the voltage is usually further decreased to a low voltage (LV: < 1 kV) for the customers. The term ‘ring main unit’ is used, as the distribution grid is often, depending on the country, designed as a ring structure (or some variant), where the RMUs, together with the MV cables, form the ring.

In Figure 1.1 an example of a part of a ring-structured MV grid is drawn. As is indicated with dashed lines, several connections to other ring structures and substations are also possible and one substation usually feeds several rings.

Medium-voltage networks, especially in highly populated areas, are often designed with some version of this ring structure, so power delivery can be routed via several paths, to increase reliability and provide maintenance possibilities. Due to limited maximum lengths of MV cables, or partial replacements, joints are used to interconnect cable sections.

Considering the total costs of the complete power grid, the distribution grid takes the major part, in the Netherlands approximately 75 %. Optimal design and maintenance of the distribution grid is therefore crucial from an economical point of view.

Example of relevant components in part of a medium-voltage grid which is designed as a ring structure
Figure 1.1 – Example of relevant components in part of a medium-voltage grid which is designed as a ring structure. One ring main unit is enlarged to show its relevant components.

A large part of the investment costs of the distribution network is taken by the medium voltage cables. Furthermore, the distribution grid is responsible for the majority of the time duration of power delivery failure to the customer. In the Netherlands this figure is about 80 %.

A vast majority of the distribution grid outage times is due to failures of MV cables and especially their joints. As many medium-voltage cable connections were already installed more than 30 years age, a preventive maintenance strategy, as was often applied in the past, would require replacement.

However, deregulation of the energy market and therefore the intensifying competition, bring utilities to pursue reduction of costs, postponing of investments, while maintaining or upgrading the reliability of power delivery. This, together with the ever increasing demand for energy, leads utilities to employ other maintenance and replacement strategies. Condition based maintenance (CBM) aims to postpone replacement and maintenance cost, based upon the current condition of the equipment.

Provided that good knowledge of the condition of the system parts can be obtained, high cost reduction and reliability improvement can be established. As a consequence, good condition diagnostics for especially medium-voltage cables and their accessories (joints, splices, and terminations) have become very important.


Distribution-class power cable types

For medium voltage cables, two main categories can be defined: paper-insulated and extruded cables. Several variations of the specific materials and dimensions exist, but the general lay-out principles are briefly described by the two categories below.


Paper-insulated lead-covered cables

The paper-insulated lead-covered (PILO) cable is one of the oldest power-cable types and exists for almost a hundred years. For a long time, there have been no alternatives that could compete with the proven reliability of this type of cable and in many countries the majority of installed MV cables is still PILC.

Figure 1.2 shows an example of a commonly used PILC-type cable: a belted cable, which relates to the common belt (3) around the three phase cores (1+2). The phase conductors (1) can be stranded copper or aluminium or solid aluminium. The insulation consists of windings of paper tape, which is impregnated in a compound of oil, wax, and resin (2+3). The core-and belt-insulation thicknesses obviously depend on the operating voltage, which is for belted cables usually below 15 kV.

The lead shield (4), around the belt, serves as the earth conductor and ensures watertightness.

Typical PILC-cable layout: the belted construction type
Figure 1.2 – Typical PILC-cable layout: the belted construction type. The numbers correspond with the various layers, explained in the text.

Further coverings are bitumenized paper (5), jute (6), steel armor tape or wires (7), bitumenized jute (8), and chalk (9). The bitumen is applied for preservation. The chalk is used to avoid sticking of the cable to the reel. A polymer sheath from PVC (polyvinyl chloride) or PE (polyethylene) sometimes replaces the jute and gives better protection against e.g. pitting or corrosion (due to e.g. stray currents).

Some characteristics of PILC cables are: rugged, compact, continuous earth screen, high chemical resistance due to the lead sheath and proven long service life. Especially due to this last characteristic, some utilities still favor this type of cable. This belted PILC cable is used extensively for distribution-class cables.

In the Netherlands, the vast majority of the medium voltage cables are belted PILC cables, mainly 10 kV. Therefore, the main focus of this thesis will be pointed at this cable type, although most principles are cable-type independent.

For higher voltage classes (> 15 kV) field strengths between the conductors become too high due to their non-uniform distribution, as depicted in Figure 1.3a, and cables with a separate shield around each round phase conductor are applied. This results in a radial field around each core, as shown in Figure 1.3b. This power cable type is called a radial field or llochstridter’ cable.

Other variations include e.g. the use of a separate lead sheath around each phase core and/or application of semi-conductor layers at the insulation-metal interfaces or as HochstUdter layers, to optimize field control.

The maximum voltage class for this type of cable is 69 kV, although 10-35 kV PILC cables are most commonly used.

Electric field lines in typical PILC-cable layouts
Figure 1.3 – Electric field lines in typical PILC-cable layouts: (a) belted construction type, (b) Hochstddter layers around the cores

Extruded solid-dielectric power cables

Although polymeric cables are already available since the early 1950s, it was only until several tens of years later that the reliability increased enough to compete with PILC cables. Even nowadays, PILC cables sometimes get the advantage, depending on the utility and application.

Although there are many different polymeric cable designs, an example of a single-phase XLPE (cross-linked polyethylene) cable is depicted in Figure 1.4 to present the general structure. Details may differ for various designs. For standardized names of the various layer, see [IECc].

The conductor (1) can be stranded copper or alu-minium or solid aluminium. A semi-conducting layer (often called conductor screen) (2) around the conductor serves for field control of the metal-insulation interface. The insulation material (3) can be PE, which is no longer used for new installations, EPR (ethylene-propylene-rubber) or XLPE. XLPE is by far the most popular choice, due to lower dielectric losses and price.

Around the insulation, a semi-conducting shield (4) ensures smooth interfacing. This shield is also often denoted as insulation screen. Semi-conducting swelling tape (5) is applied for longitudinal watertightness. Copper or aluminium wires (6) and counter wounded tape (7) serve as the earth con-ductor and should accommodate capacitive and short-circuit currents.

Example of an XLPE MV three-core cable design
Figure 1.5 – Example of an XLPE MV three-core cable design

Around this screen, semi-conducting filling rubber (8) can ensure longitudinal watertightness at this location. An aluminium complex strip (9) and a PE or PVC sheath (10) serve as protection against water ingress and mechanical forces. Properties of extruded cables are:

  • Low losses and relative permittivity,
  • Long expected lifetime,
  • Simple handling,
  • Long lengths and,
  • Especially if XLPE is used, high maximum operating temperature.

Extruded cables are not restricted to distribution class voltages. Maximum voltage rates are up to 500 kV. Just as the three-core PILC cables with one common (lead) shield, MV polymeric cables can also embed three cores in one cable.

Figure 1.5 shows an example. The several layers and materials in this structure are similar to those of the single-core design. Now each of the phase conductors and their insulation layers have their own semi-conducting screen around them, resulting in radial electric field distributions in the core insulation, as in the Hochstadter PILL cable.

Title:Online detection and location of partial discharges in MV cables – Petrus Carolina Johannes Maria van der Wielen, to obtain degree of doctor at Eindhoven University of Technology
Format:PDF
Size:5.5 MB
Pages:207
Download:Right here | Video Courses | Membership | Download Updates
Online detection and location of partial discharges in MV cables
Online detection and location of partial discharges in MV cables

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
More Information

One Comment


  1. Umar Yusuf
    Aug 15, 2021

    I have degre in Electrical and computer engineering (power stream) so i will want to study master please contact me if i will get this chance my mail [email protected] or +251919247307. Thanks

Leave a Reply to Umar Yusuf

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

sixty  ⁄  six  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).