Home / Download Center / Electrical Engineering Books and Technical Guides / Power substation guides / How reliable are modern substation automation systems?

Protection, control and monitoring

Typical power substations are supposed to receive, transform the electricity either by stepping up or down the voltage and then send it forward. Substations designed in the past made use of protection and control schemes implemented with a single-function, electromechanical or static devices and hard-wired relay logic.

How reliable are modern substation automation systems?
How reliable are modern substation automation systems? (photo credit: Arteche)

With the advent of microprocessor based multi-function Intelligent Electronic Devices (IEDs), we get the opportunity to move more functionality into fewer devices; as well as resulting in simpler designs with reduced wiring.

Beginning in early 1990s, industry developed a communications architecture that would facilitate the design of systems for protection, control, monitoring and diagnostics in the substation, which was the Substation Automation Systems (SAS).


IEC 61850 Based SAS

The IEC 61850 protocols provide the utilities and manufacturing entities with a new standard and design for the modern electric substation.

Modern communication network technology and the use of merging units accelerate the development of substation automation system and push the traditional substation to the cyber-physical systems stage.

Since the approval of IEC 61850 by UCA (Utility Communication Architecture) International Users Group in 2004, many European and Chinese utilities have implemented IEC 61850 standards on the newly installed smart high voltage substations, i.e. 110/10kV air insulated substation.

Figure 1 depicts the IEC 61850 based substation architecture; the different components are described below.

IEC 61850 Based Substation Architecture
Figure 1 – IEC 61850 Based Substation Architecture

Regarding to the substation protection, IEC 61850 protocols standardized the data exchange rules over the Process and Station bus in high-speed peer-to-peer communications. Generic Object Oriented Substation Event (GOOSE) message is introduced through the entire system to make sure the high priority of the signals from Circuit Breaker IEDs.

Some critical devices and structures are described in the following parts.


IEC 61850 Critical Devices

1) Merging Unit (MU)

A merging unit combined with the instrument transformer (CT/VT) monitors the working status of lines and devices. Unlike the conventional analog signal, MU can digitize the original current and voltage signals and send them over the Ethernet network in the form of sampled values.

The Merging Units (MU) multicast sets of measured sampled values to multiple other IEDs in the substation over the substation local area network, which shows as the process bus level. Status and all the information for circuit breakers and circuit switches are available through the input/output unit.

Merging unit and these input/output units are usually combined into single devices and recognized as Merging Unit.


2) Intelligent Electronic Devices (IEDs)

Intelligent Electronic Devices (IEDs) are devices that perform electric protection or control functions in power systems, with advanced local control intelligence and have the ability to monitor processes.

IEDs receive data from sensors and power equipment, and can issue control commands, such as tripping circuit breakers if they sense voltage, current, or frequency anomalies, or raise/lower voltage levels in order to maintain the desired level.

Common types of IEDs include protective relaying devices, load tap changer controllers, circuit breaker controllers, capacitor bank switches, reclose controllers, voltage regulators, etc.

Title:Reliability evaluation of modern substation automation systems – YAN ZHANG at Texas A&M University
Format:PDF
Size:2.1 MB
Pages:63
Download:Right here | Video Courses | Membership | Download Updates
How reliable are modern substation automation systems?
How reliable are modern substation automation systems?

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
More Information

One Comment


  1. Hari kusnomo
    Jul 12, 2019

    Good morning sir , dou you have any formula for cakculation termal setting for tesys.

    Koez.harry

Leave a Reply to Hari kusnomo

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

63  ⁄    =  nine

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).