Search

Premium Membership

Limited Time Offer: Save 15% on Pro Plan with discount code: NTX78. Study specialized LV/MV/HV technical articles and guides.

Home / Download Center / Electrical Engineering Books and Technical Guides / Power substation guides / Substation equipment maintenance, tests and checkings

Measurement of insulation resistance of transformer/reactor

The measurement of insulation resistance is carried out to check the healthiness of the transformer insulation. This test is the simplest and is being widely used by the electrical utilities.

Substation equipment maintenance and checkings
Substation equipment maintenance and checkings (photo credit: saberpowertraining.com)

This test indicates the condition of the insulation i.e. degree of dryness of paper insulation, presence of any foreign containments in oil and also any serious defects in the transformer.

The measurement of insulation resistance is done by means of Megger device of 2.5 kV for transformer windings with voltage rating of 11 kV and above and 5 kV for EHV transformers.

All safety instructions have to be followed as per the utility practice before carrying out this test. It has also to ensured that high voltage and low voltage windings are isolated along with the concerned isolaters. In case transformer is having a tertiary windings, ensure the isolation are the same prior to commencement of the test.

Also the jumpers and lighting arrestors connected to the transformer have to be disconnected prior to start of testing after issue of PTW/SFT.

Following precautions may be taken while conducting the above test.

  1. Bushing porcelain may be cleaned by wiping with a piece of the dry cloth.
  2. When using a Megger, observe the usual accident preventive rules.
  3. As the windings possess a substantial capacitance, the current carrying cords should only be touched after the electric charge have been removed from them.
  4. Connecting wires from the bushing line lead and tank to megger shall be as short as possible without joints and shall not touch tank or each other.

Maintenance/testing procedure:

IR measurements shall be taken between the windings collectively (i.e. with all the windings being connected together) and the earthed tank (earth) and between each winding and the tank, the rest of the windings being earthed.

For auto-transformerFor shunt reactorFor 3-winding transformer
HV/LV+EHV/EHV/LV+TV+E
IV/HV+ELV/HV+TV+E
LV/HV+LV+ETV/HV+LV+E
HV/IVHV+TV/LV+E
IV/LVLV+TV/HV+E
HV/LVHV+LV/TV+E

Where:

  • HV – High voltage,
  • IV – Intermediate voltage,
  • LV-Low voltage,
  • TV – Tertiary voltage windings,
  • E – Earth

Record date and time of measurement, sl.no., make of megger, oil temperature and IR values at intervals of 15 seconds, 1 minute and 10 minutes. The live terminal of the equipment shall be connected to the winding under test.


Evaluation of Test Results

Check the IR values with the values given in the test certificate by the manufacturer. These values may be used as bench marks for future monitoring of the IR values.

The IR values vary with the type of insulation, temperature, duration of application of voltage and to some extent on apply voltage. The IR values in air will be nearly 15 to 20 times more than in the transformer oil at the same temperature.

Title:Substation equipment maintenance and checkings
Format:PDF
Size:1.10 MB
Pages:129
Download:Right here | Video Courses | Membership | Download Updates
Substation equipment maintenance, tests and checkings
Substation equipment maintenance, tests and checkings

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
More Information

9 Comments


  1. EMMANUEL P. SANO
    May 20, 2020

    Your writetings is giving me a lot of new discoveries on substation testing and maintenance.
    Hope to learn more.Thanks.


  2. Anil kumar
    May 01, 2019

    Hi I have a query for complete design of capacitor bank for 900kva load for lt panel.


  3. AbduRahman Yusuf
    Dec 03, 2018

    Great and noble job


  4. Samir Ismail
    Dec 02, 2018

    You are doing a great job Edvard,thank you.


  5. Akram Kadhim Mohammed
    Dec 01, 2018

    many thanks for all information


  6. Hermann Nganwa
    Nov 29, 2018

    Thank you so much for enlightening my path! This portal is by far the best resource for any electrical power engineer. I have no doubt “Electrical Engineering Portal” will help me build up my knowledge and I will become an expert in the near future.
    Thanks again!


    • Edvard
      Nov 30, 2018

      Thank you Hermann, that’s very kind of you.


  7. Emmanuel
    Nov 29, 2018

    thank you for your daily updat.
    be blessed


  8. EVANGIVALDO LIMA
    Nov 28, 2018

    i am interested

Leave a Reply to Akram Kadhim Mohammed

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

  ⁄  one  =  three

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).