Power Transformer Diagnostics

This application note is focusing on using winding resistance measurements on power transformers for diagnostic purposes. The intention is to guide the operator in the appropriate measurement method and assist in the interpretation of test results obtained.

Measurements Of Transformer Winding Resistance For Diagnostic Purposes
Measurements Of Transformer Winding Resistance For Diagnostic Purposes

It is not a complete step-by-step procedure for performing tests and is not replacing the user manual for the actual instrument. Before performing any test with an instrument, read the user manual and observe all safety precautions indicated.


Winding resistance measurements (WRM)

Winding resistance measurements in transformers are of fundamental importance for the following purposes:

  1. Calculations of the I2R component of conductor losses.
  2. Calculation of winding temperature at the end of a temperature test cycle.
  3. As a diagnostic tool for assessing possible damage in the field.

Transformers are subject to vibration.

Problems or faults occur due to poor design, assembly, handling, poor environments, overloading or poor maintenance. Measuring the resistance of the windings assures that the connections are correct and the resistance measurements indicate that there are no severe mismatches or opens.

Many transformers have taps built into them. These taps allow the ratio to be increased or decreased by fractions of a percent.

If any of the ratio changes involve a mechanical movement of a contact from one position to another, these tap changes should also be checked during a winding resistance test.

Regardless of the configuration, either star or delta, the measurements are normally made phase to phase and comparisons are made to determine if the readings are comparable. If all readings are within one percent of each other, then they are acceptable.

Keep in mind that the purpose of the test is not to duplicate the readings of the manufactured device, which was tested in the factory under controlled conditions and perhaps at other temperatures.


When To Measure Winding Resistance?

At Installation

Risk of damage is significant whenever a transformer is moved. This is inherent to the typical transformer design and modes of transportation employed. Damage can also occur during unloading and assembly. The damage will often involve a current carrying component such as the LTC, RA switch or a connector.

Damage to such components may result in a change to the DC resistance measured through them. Hence, it is recommended that the DC resistance be measured on all on-load and off-load taps prior to energizing.

If the transformer is new, the resistance test also serves as a verification of the manufacturers work. Installation measurements should be filed for future reference.

Transformer windings measurement principle
Transformer windings measurement principle – A DC test current is injected across the measured winding (-s), the voltage drop as well as the test current is measured and the resistance is calculated.

At Routine (scheduled) Transformer Maintenance

Routine maintenance is performed to verify operating integrity and to assure reliability. Tests are performed to detect incipient problems. What kind of problems will the resistance test detect?

SAFETY! Specific aspects of safety are addressed in this guide. However comprehensive procedures are not detailed. It is assumed the operator has sufficient knowledge of electrical theory and safe working practices to use the test instrument in a safe and responsible manner.

Title:Measurements Of Transformer Winding Resistance For Diagnostic Purposes – MEGGER
Format:PDF
Size:572 KB
Pages:20
Download:Right here | Video Courses | Membership | Download Updates
Measurements Of Transformer Winding Resistance For Diagnostic Purposes
Measurements Of Transformer Winding Resistance For Diagnostic Purposes

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
More Information

One Comment


  1. Abhilash K Sarang
    Jul 06, 2019

    Sir….I requested you.
    I want join your blog.

Leave a Reply to Abhilash K Sarang

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

  +  12  =  sixteen

Learn to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and electrical guides.