Control & monitoring application using WLAN

Fast Distribution Bus Protection Scheme

A dedicated bus protection may not be economical for medium/low voltage distribution substation. Therefore, conventional method to protect distribution bus is using overcurrent relays, where the loads on the bus are fed radially (unidirectional power flow). Normally, the upstream protection IED (IED-1) is delayed by downstream feeder IEDs by coordination interval, i.e. approx. 400 to 500 ms or more.

Applying wireless LAN for IEC 61850 based smart LV/MV distribution substations
Applying wireless LAN for IEC 61850 based smart LV/MV distribution substations (on photo: 24kV Switchgear, Siemens NXplus C with Siprotec 7SJ64 relay; credit: Chanvit Direkwattanachai vus Linkedin)

This coordination interval is inserted in order to allow downstream feeder IED before bus IED in case of a feeder fault. However, if there is a fault on bus, bus overcurrent protection is delayed by this coordination delay (400 ms to 500 ms). This time delay can be drastically reduced by deploying low cost WLAN communication as explained below:

In this scheme, peer-to-peer IEC 61850 GOOSE message can be used to send signal from feeder protection IEDs to bus overcurrent IED.

This scheme only requires non-directional overcurrent protective elements, with low-cost communication channel (i.e. wireless LAN). In case of a fault on feeder, two IEDs will detect a fault: 1) corresponding feeder IED, and 2) upstream bus IED.

The feeder IED will immediately send BLOCK command using IEC 61850 GOOSE message, and feeder IED will isolate the fault.

On the other hand, if there is a fault on the distribution substation bus, none of the feeder IEDs will detect a fault, and this way, bus IED will not receive any BLOCK message, and will operate normally after a delay of approx. 60 ms (normally fault is detected in 4 ms, and average WLAN communication delay is approx. 5-10 ms).

Wireless LAN communication for fast distribution bus protection
Figure 1 – Wireless LAN communication for fast distribution bus protection

This way coordination delay can be reduced from 400-500 ms to 60 ms. This scheme improves the life of components installed on upstream of distribution bus, i.e. distribution transformer, since the time of fault current passing through these components reduces.

Furthermore, this scheme further can be enhanced to simultaneous faults. For example, if there is a simultaneous fault on bus and a feeder, this scheme can utilize IEC 61850 GOOSE message communication to not only send BLOCK command, but also incorporates information like, types of faults. This way, if feeder IED detects L-G fault, however, bus IED detects multiple phase faults, bus IED can immediately override BLOCK command, and operates.

The concept of fast distribution bus protection scheme is shown in Figure 1 above.


LTC Control and Monitoring for Enhanced Transformer Protection

(LTC – on-load tap changer)

Figure 2 shows the IEC 61850 based wireless LAN to enhance the distribution substation protection and automation. A technical report from IEEE PSRC has presented protection and control applications using spread spectrum radio, some of the reported intra-substation applications which include an enhanced transformer differential protection.

The wireless LAN channel can be installed to facilitate communication between LTC control/monitoring field device and transformer protection and control IED.

Wireless LAN communication for on-load tap changer (LTC) control and monitoring
Figure 2 – Wireless LAN communication for on-load tap changer (LTC) control and monitoring

The transformer IED can control LTC to maintain the bus voltages within the predefined range. The IEC 61850 GOOSE message can be used to communicate RAISE/DROP the transformer tap settings. The performance requirement for LTC control is 0.25 second, which can be well within WLAN average delay.

On the other hand, the on-load tap changer  (LTC) sensor can retransmit the IEC 61850 GOOSE messages to confirm the POS (position status) signal of the transformer tap value. Normally, the LTC has + 10% controllable tap setting range. And therefore, the transformer differential protection slope has to be set higher.

However, this higher protection slope affects the sensitivity and dependability of the protection. The IEC 61850 GOOSE messages with current tap value can be communicated to the conventional transformer IED over the WLAN network. And, this way slope of the differential protection IED can be adjusted adaptively (according to the tap status).

This way, with this wireless LTC sensor can enhance transformer differential protection by online monitoring of LTC position, as shown in Figure 2 above.

Title:Applying wireless LAN for IEC 61850 based smart LV/MV distribution substations – Doctoral thesis by Palak P. Parikh at The University of Western Ontario
Format:PDF
Size:9.3 MB
Pages:211
Download:Right here | Video Courses | Membership | Download Updates
Applying wireless LAN for IEC 61850 based smart LV/MV distribution substations
Applying wireless LAN for IEC 61850 based smart LV/MV distribution substations

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
More Information

One Comment


  1. Joachim Friederich
    Mar 25, 2020

    Good Day

    It is the most interesting forum on s much topics. So much Info what a Engineer can have.

Leave a Reply to Joachim Friederich

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

ninety six  −    =  eighty seven

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).