Search

Premium Membership ♕

Limited Time Offer: Save 15% on PRO Plan with discount code: LRN15 and study specialized LV/MV/HV technical articles and studies.

Home / Download Center / Electrical Engineering Books and Technical Guides / Relay control and protection guides / The breaker failure protection (BFP) schemes in utilities

The Requirements of BFP Schemes

Since the BFP operation will trip a number of adjacent CBs, the consequence of its mis-operation is usually severe. In some cases, the BFP mis-operation was the starting point of cascading outage in the area.

The breaker failure protection (BFP) schemes in utilities
The breaker failure protection (BFP) schemes in utilities

On the other hand, if the BFP does not operate to isolate the fault, the system is at risk too and some equipment such as generator and transformer could be damaged. Therefore, a good BFP design should be able to prevent mis-operation due to single component failure or single human error.

It is desirable to achieve both security and dependability at the same time.

However, the design preference for a Line CB may be different from that for a Bank CB, which is defined as breaker associated with generator, transformer, shunt reactor or shunt capacitor bank.

The Line BFP may need to bias towards security while the Bank BFP need to bias towards sensitivity and dependability.


Breaker failure protection practices in utilities

This section reviews the BFP designs in three Utilities from the implementation point of views such as the BFP initiation, fault detector settings, the BFP timer settings, tripping circuits, system restoration design, direct transfer trip (DTT), etc.


A. BFP design in Utility-1

1. BFP Implementation

In Utility-1, most CBs at transmission level have dedicated BFP scheme that is based upon a stand-alone digital relay for each CB. The relay also includes other control and monitoring functions such as Auto Reclosing, CB control, CB alarms, trip circuit monitoring etc.

In the past several years, this Utility has extended the installation of dedicated BFP to subtransmission level at 69kV.


2. BFP Initiation

All protection devices/relays that trip the CB also initiate BFP except trips from another BFP Lockout relay operation. The BFP initiation signals from protective relays are hardwired to the inputs of the dedicated CB Control and Failure relay.

Utility-1’s BFP Logic
Figure 1 – Utility-1’s BFP Logic

3. BFP Logic

Residing in the dedicated CB control relay, the BFP logic includes the following three components:

  1. Current Detector (50P or 50G),
  2. CB Failure Initiation (BFI) and
  3. CB Failure Timer (tBF).

This simple BFP logic is inherited from EM relay design. As shown in Fig. 1, the BFP scheme is armed if the current detector (50P or 50G) is actuated and the breaker failure initiation (BFI) signal is presented.

If these conditions persist after BFP timer expires, the BFP will pick up the lockout relay (LOR) to trip all the adjacent CBs.

The typical tBF setting is 7~15 cycles, which is up to the CB type and voltage level. If applicable, the LOR also initiates DTT signal to remote terminal and stops the blocking signal of DCB schemes.

This Utility has DTT facilities installed for lines over 200kV, or for some generator interconnections. For lines below 200kV, the local relays are set to back up the remote CB.

For example, a far-reaching distance zone 3 and sensitive ground overcurrent used in a DCB scheme can backup the failed CB in remote station if the blocking signal is absent.

Title:Review of The Breaker Failure Protection Practices in Utilities – Yiyan Xue and Manish Thakhar (American Electric Power Company), Jacob C. Theron (Hydro One Networks Inc.) and Davis P. Erwin (Pacific Gas and Electric Company)
Format:PDF
Size:225.2 KB
Pages:9
Download:Right here | Video Courses | Membership | Download Updates
The breaker failure protection (BFP) schemes in utilities
The breaker failure protection (BFP) schemes in utilities

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount 💥 - Save 50% on all 90+ video courses with Enterprise Membership plan.

More Information

2 Comments


  1. qais
    May 29, 2019

    This is really advantage information


  2. DEEPAK KUMAR DASH
    May 28, 2019

    It is a very good presentation.

Leave a Reply to qais

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

3  ×  one  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
EEP Academy Courses - A hand crafted cutting-edge electrical engineering knowledge