Identification of faults for protection

Both, protective relays and fault locators for overhead lines are dependent on the results of the auxiliary algorithms, which are applied for identifying fault features, such as: fault detection, fault direction discrimination and phase selection.

Analysis of power system faults and relay protection measures
Analysis of power system faults and relay protection measures (photo credit: ZGL)

Fault detection is required to activate the measurement process of protective relays. In relation to specification of time intervals of the signals, fault detection can be treated as distinguishing the fault interval from the pre-fault interval.

Fault direction is understood as the calculations aimed at answering a question whether a considered fault is forward or backward with respect to the direction at which the protective relay is design to respond.

For example, a distance relay protecting a transmission line is designed to operate under forward faults appearing within 85% of the line length (typical first zone setting) or faults overreaching the protected line (the next protective zones).

On the other hand, it is expected not to respond for backward faults, i.e. faults occurring back to the relaying point.

Phase selection is aimed at identifying the fault type, i.e. which phases are involved in a considered fault and whether it is an earthed fault or isolated one.


Fault detection

A number of approaches to fault detection are proposed in the literature. The abnormal conditions (not necessarily faults) are detected by watching the phase impedances and/or phase-current amplitudes and/or phase-voltage amplitudes and/or zero-sequence current amplitude.

Depending on a particular application, different activation criteria are combined in a different way. To speed up the fault detection, one may also apply derivatives of the relevant signals.

It is quite easy to introduce the adaptivity to such approaches. Knowing the breaker positions, monitoring the average load of a line, etc., the thresholds may be self-adjusted to improve the sensitivity and reliability of fault detection.

ault detection: illustration of differentiation methods: a) sample-by-sample, b) cycle-by-cycle
Figure 1 – Fault detection: illustration of differentiation methods: a) sample-by-sample, b) cycle-by-cycle

Much easier methods refer directly to samples of current and/or voltage waveforms. Disregarding a particular solution, two approaches (Figure 1) are commonly applied in contemporary digital protective relays:


Solution #1 – Sample-by-sample method

A sample-by-sample method computing numerically the first derivative of a watched signal. If this derivative overruns a pre-set value, an auxiliary counter starts to count up.

This counter is incremented by the absolute value of the derivative. When it reaches another pre-set threshold, a fault is confirmed. Certainly, the first threshold must be set above the maximum value of the scaled derivative under normal conditions.


Solution #1 – Cycle-by-cycle algorithm

A cycle-by-cycle algorithm compares a present sample with the sample one cycle back. The threshold for such a difference may be set much lower than in the sample-by-sample method. An auxiliary counter may be used to initiate when the absolute value of the defined difference overruns its threshold.

The detection is when the counter increased by the successive differences overreaches the second threshold.

Title:Analysis of power system faults (transformers, rotating machines, overhead and cable lines) – Jan Iżykowski (Wrocław University of Technology)
Format:PDF
Size:2.0 MB
Pages:191
Download:Here 🔗 (Get Premium Membership) | Video Courses | Download Updates
Analysis of power system faults (transformers, rotating machines, overhead and cable lines)
Analysis of power system faults (transformers, rotating machines, overhead and cable lines)

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount 💥 - Save 50% on all 90+ video courses with Enterprise Membership plan.

More Information

5 Comments


  1. Afip Nurul Hudah
    Sep 04, 2020

    Thanks. I immediatly got clear references the ground fault and generator.

    Best regards
    Afip


  2. CHOZHIYATTAL ANVAR ALI
    Aug 31, 2020

    Anvar Ali c
    August 31 2020

    your all infarmation is very useful my job and your update about electrical power system

    Thank you
    Anvar Ali


  3. layla abdulaa murad
    Mar 04, 2019

    first of all I would like to thanks you very much because always i found answers for my all questions on power substations with repleted equipment and under ground or overhead distribution lines so thank you again for sending me all these knowledge about power system which are very very useful
    with my best regard.
    layla

Leave a Reply to Edvard

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

seventy  ⁄  seven  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
EEP Academy Courses - A hand crafted cutting-edge electrical engineering knowledge