Search

Premium Membership

Study specialized electrical engineering articles, papers & video courses in low/high voltage areas. Save 50% on all courses with the Enterprise Plan.

Home / Technical Articles / How to Determine Correct Number of Earthing Electrodes (Strips, Plates and Pipes) – part 1

Introduction

Number of Earthing Electrode and Earthing Resistance depends on the resistivity of soil and time for fault current to pass through (1 sec or 3 sec). If we divide the area for earthing required by the area of one earth plate gives the number of earth pits required.

How to Determine Correct Number of Earthing Electrodes (Strips, Plates and Pipes) - part 1
How to Determine Correct Number of Earthing Electrodes (Strips, Plates and Pipes) – part 1

There is no general rule to calculate the exact number of earth pits and size of earthing strip, but discharging of leakage current is certainly dependent on the cross section area of the material so for any equipment the earth strip size is calculated on the current to be carried by that strip.

First the leakage current to be carried is calculated and then size of the strip is determined.

For most of the electrical equipment like transformer, diesel generator set etc., the general concept is to have 4 number of earth pits. 2 no’s for body earthing with 2 separate strips with the pits shorted and 2 nos for Neutral with 2 separate strips with the pits shorted.

[pullquote_left]The Size of Neutral Earthing Strip should be capable to carry neutral current of that equipment.
The Size of Body Earthing should be capable to carry half of neutral Current.[/pullquote_left]

For example for 100kVA transformer, the full load current is around 140A.

The strip connected should be capable to carry at least 70A (neutral current) which means a strip of GI 25x3mm should be enough to carry the current and for body a strip of 25×3 will do the needful. Normally we consider the strip size that is generally used as standards.

However a strip with lesser size which can carry a current of 35A can be used for body earthing. The reason for using 2 earth pits for each body and neutral and then shorting them is to serve as back up. If one strip gets corroded and cuts the continuity is broken and the other leakage current flows through the other run thery by completing the circuit.

Similarly for panels the no of pits should be 2 nos. The size can be decided on the main incomer circuit breaker.

For example if main incomer to breaker is 400A, then body earthing for panel can have a strip size of 25×6 mm which can easily carry 100A.

Number of earth pits is decided by considering the total fault current to be dissipated to the ground in case of fault and the current that can be dissipated by each earth pit. Normally the density of current for GI strip can be roughly 200 amps per square cam. Based on the length and dia of the pipe used the number of earthing pits can be finalized.


1. Calculate numbers of pipe earthing

A. Earthing resistance and number of rods for isolated earth pit
(without buried earthing strip)

The earth resistance of single rod or pipe electrode is calculated as per BS 7430:

R=ρ/2×3.14xL (loge (8xL/d)-1)

Where:

ρ = Resistivity of soil (Ω meter),
L = Length of electrode (meter),
D = Diameter of electrode (meter)

Example:

Calculate isolated earthing rod resistance. The earthing rod is 4 meter long and having 12.2mm diameter, soil resistivity 500 Ω meter.

R=500/ (2×3.14×4) x (Loge (8×4/0.0125)-1) =156.19 Ω.

The earth resistance of single rod or pipe electrode is calculated as per IS 3040:

R=100xρ/2×3.14xL (loge(4xL/d))

Where:

ρ = Resistivity of soil (Ω meter),
L = Length of electrode (cm),
D = Diameter of electrode (cm)


Example:

Calculate number of CI earthing pipe of 100mm diameter, 3 meter length. System has fault current 50KA for 1 sec and soil resistivity is 72.44 Ω-Meters.

Current Density At The Surface of Earth Electrode (As per IS 3043):

  • Max. allowable current density  I = 7.57×1000/(√ρxt) A/m2
  • Max. allowable current density  = 7.57×1000/(√72.44X1) = 889.419 A/m2
  • Surface area of one 100mm dia. 3 meter Pipe = 2 x 3.14 x r x L = 2 x 3.14 x 0.05 x3 = 0.942 m2
  • Max. current dissipated by one Earthing Pipe = Current Density x Surface area of electrode
  • Max. current dissipated by one earthing pipe = 889.419x 0.942 = 837.83 A say 838 Amps
  • Number of earthing pipe required = Fault Current / Max.current dissipated by one earthing pipe.
  • Number of earthing pipe required = 50000/838 = 59.66 Say 60 No’s.
  • Total number of earthing pipe required = 60 No’s.
  • Resistance of earthing pipe (isolated) R = 100xρ/2×3.14xLx(loge (4XL/d))
  • Resistance of earthing pipe (isolated) R = 100×72.44 /2×3.14x300x(loge (4X300/10)) = 7.99 Ω/Pipe
  • Overall resistance of 60 no of earthing pipe = 7.99/60 = 0.133 Ω.

B. Earthing resistance and number of rods for isolated earth pit
(with buried earthing strip)

Resistance of earth strip (R) As per IS 3043:

R=ρ/2×3.14xLx (loge (2xLxL/wt))


Example:

Calculate GI strip having width of 12mm , length of 2200 meter buried in ground at depth of 200mm, soil resistivity is 72.44 Ω-meter.

  • Resistance of earth strip(Re) = 72.44/2×3.14x2200x(loge (2x2200x2200/.2x.012)) = 0.050 Ω
  • From above calculation overall resistance of 60 no of earthing pipes (Rp) = 0.133 Ω.
    And it connected to bury earthing strip. Here net earthing resistance = (RpxRe)/(Rp+Re)
  • Net eatrthing resistance = (0.133×0.05)/(0.133+0.05) = 0.036 Ω

C. Total earthing resistance and number of electrode for group
(parallel)

In cases where a single electrode is not sufficient to provide the desired earth resistance, more than one electrode shall be used. The separation of the electrodes shall be about 4 m. The combined resistance of parallel electrodes is a complex function of several factors, such as the number and configuration of electrode the array.

The total resistance of group of electrodes in different configurations as per BS 7430:

Ra=R (1+λa/n) where a=ρ/2X3.14xRxS

Where:

S = Distance between adjustment rod (meter),
λ = Factor given in table below,
n = Number of electrodes,
ρ = Resistivity of soil (Ω meter),
R = Resistance of single rod in isolation (Ω)

Factors for parallel electrodes in line (BS 7430)
Number of electrodes (n)Factor (λ)
21.0
31.66
42.15
52.54
62.87
73.15

8

3.39
93.61
103.8

For electrodes equally spaced around a hollow square, e.g. around the perimeter of a building, the equations given above are used with a value of λ taken from following table.

For three rods placed in an equilateral triangle, or in an L formation, a value of λ = 1.66 may be assumed.

Factors for electrodes in a hollow square (BS 7430)
Number of electrodes (n)Factor (λ)
22.71
34.51
45.48
56.13
66.63
77.03
87.36
97.65
107.9
128.3
148.6
168.9
189.2
209.4

For Hollow square total number of electrodes (N) = (4n-1).

The rule of thumb is that rods in parallel should be spaced at least twice their length to utilize the full benefit of the additional rods. If the separation of the electrodes is much larger than their lengths and only a few electrodes are in parallel, then the resultant earth resistance can be calculated using the ordinary equation for resistances in parallel.

In practice, the effective earth resistance will usually be higher than calculation.

Typically, a 4 spike array may provide an improvement 2.5 to 3 times. An 8 spike array will typically give an improvement of maybe 5 to 6 times.

The  Resistance of Original Earthing Rod will be lowered by Total of 40% for Second Rod, 60% for third Rod,66% for forth rod.

Example:

Calculate Total Earthing Rod Resistance of 200 Number arranges in Parallel having 4 Meter Space of each and if it connects in Hollow Square arrangement. The Earthing Rod is 4 Meter Long and having 12.2mm Diameter, Soil Resistivity 500 Ω.


First Calculate Single Earthing Rod Resistance:

  • R = 500/ (2×3.14×4) x (Loge (8×4/0.0125)-1) =136.23 Ω.

Now calculate total resistance of earthing rod of 200 number in parallel condition:

  • a = 500/(2×3.14x136x4) =0.146
  • Ra (Parallel in Line) =136.23x (1+10×0.146/200) = 1.67 Ω.

If earthing rod is connected in Hollow square than rod in each side of square is 200 = (4n-1) so n = 49 No.

Ra (in hollow square) =136.23x (1+9.4×0.146/200) = 1.61 Ω.

Originally published atElectrical Notes – Calculate Numbers of Plate/Pipe/Strip Earthings (Part-1)

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
author-pic

Jignesh Parmar

Jignesh Parmar has completed M.Tech (Power System Control), B.E (Electrical). He is member of Institution of Engineers (MIE), India. He has more than 20 years experience in transmission & distribution-energy theft detection and maintenance electrical projects.

46 Comments


  1. Exer Lexis
    Jan 25, 2022

    Hello,
    Any reply on the issue of lambda=10?
    Can’t understand either.


  2. Amit Pitroda
    Apr 20, 2021

    Please let me know how to calculate the withstand capacity of a group of earthing?


  3. vinod kinekar
    Sep 23, 2020

    Dear Sir,
    Shall we know why chemical earthing is better than plate earthing and what are its IS, IES standards.

    Regards,

    Vinod Kinekar


  4. Kdhinde
    Sep 22, 2020

    Surface area of one 100mm dia. 3 meter pipe= 2×3.14 x r x L

    Please how did you get valve of r to be 0.05?


  5. manikanta
    Jul 10, 2020

    Pls advise how you got Lambda λ equals to 10 from the equation of the Ra:
    Ra (Parallel in Line) =136.23 x (1+10×0.146/200) = 1.67 Ω.

    Now calculate total resistance of earthing rod of 200 number in parallel condition:

    a = 500/(2×3.14x136x4) =0.146
    Ra (Parallel in Line) =136.23x (1+10×0.146/200) = 1.67 Ω.


  6. Mantu Gond
    Aug 07, 2019

    I want to knowledge of electrical fields about their electrical equipment.. Etc


  7. Engr. Sajo Olawande
    Jun 23, 2019

    Please i have the following parameters after my due calculations carried out,

    Size of Generator——————–250Kva
    Panel Rating ———————–350A
    Cable size—————————–240sqMM
    Earthing Cable (guess)————120sqMM(Half)
    please sir i was now asked to calculate the following:

    Do the earthing electrode resistance design as per BS 7430 or IS- 3040/43 to meet the reuse R¬< 1.0U.
    a. Determine the earth rod diameter/length
    b. The total number of earth rod to be used.


  8. Justina
    Mar 08, 2019

    Thanks for the lecture. At least I have gotten something from it. How do I calculate the fault current in 1*15MVA, 33/11kv substation


    • Vijay Kumar
      Nov 25, 2019

      V secondary = 11kV
      %Z = ___?
      I secondary= ((150×1000)/(Sqrt of 3*11000))
      =_____ kA
      Isc =(I secondary / %Z)
      =____kA


  9. Mostafa abd-ellatif
    Feb 04, 2019

    The you for your generousity


  10. sameer
    Mar 31, 2018

    Sir,

    Is the number of earth pits get reduced if I use copper clad steel (250 micron) instead of GI for vertical electrode.


  11. karthick
    Mar 10, 2018

    would u please tell me sir that how could have select the transformer neutral pit and strips

Leave a Reply to Amit Pitroda

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

  ×  five  =  25

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).