Home / Technical Articles / How to measure insulation resistance of a motor

Winding insulation resistance

If the motor is not put into operation immediately upon arrival, it is important to protect it against external factors like moisture, high temperature and impurities in order to avoid damage to the insulation. Before the motor is put into operation after a long period of storage, you have to measure the winding insulation resistance.

How to measure insulation resistance of a motor
How to measure insulation resistance of a motor (photo credit: elecls.cc.oita-u.ac.jp)

If the motor is kept in a place with high humidity, a periodical inspection is necessary.

It is practically impossible to determine rules for the actual minimum insulation resistance value of a motor because resistance varies according to method of construction, condition of insulation material used, rated voltage, size and type. In fact, it takes many years of experience to determine whether a motor is ready for operation or not.

A general rule-of-thumb is 10 Megohm or more.

 Insulation resistance value Insulation level
 2 Megohm or less Bad
 2-5 Megohm Critical
 5-10 Megohm Abnormal
 10-50 Megohm Good
 50-100 Megohm Very good
 100 Megohm or more Excellent

The measurement of insulation resistance is carried out by means of a megohmmeter – high resistance range ohmmeter. This is how the test works: DC voltage of 500 or 1000 V is applied between the windings and the ground of the motor.

Ground insulation test of a motor
Ground insulation test of a motor

During the measurement and immediately afterwards, some of the terminals carry dangerous voltages and MUST NOT BE TOUCHED.

Now, three points are worth mentioning in this connection: Insulation resistance, Measurement and Checking.


1. Insulation resistance

  • The minimum insulation resistance of new, cleaned or repaired windings with respect to ground is 10 Megohm or more.
  • The minimum insulation resistance, R, is calculated by multiplying the rated voltage Un, with the constant factor 0.5 Megohm/kV.

    For example: If the rated voltage is 690 V = 0.69 kV, the minimum insulation resistance is: 0.69 kV x 0.5 Megohm/kV = 0.35 Megohm

2. Measurement

  • Minimum insulation resistance of the winding to ground is measured with 500 V DC. The winding temperature should be 25°C ± 15°C.
  • Maximum insulation resistance should be measured with 500 V DC with the windings at a operating temperature of 80 – 120°C depending on the motor type and efficiency.

3. Checking

  • If the insulation resistance of a new, cleaned or repaired motor that has been stored for some time is less then 10 Mohm, the reason might be that the windings are humid and need to be dried.
  • If the motor has been operating for a long period of time, the minimum insulation resistance may drop to a critical level. As long as the measured value does not fall below the calculated value of minimum insulation resistance, the motor can continue to run.

    However, if it drops below this limit, the motor has to be stopped immediately, in order to avoid that people get hurt due to the high leakage voltage.

Reference: Grudfos – Motor Book

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
author-pic

Edvard Csanyi

Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV/MV switchgears and LV high power busbar trunking (<6300A) in power substations, commercial buildings and industry facilities. Professional in AutoCAD programming.

49 Comments


  1. AISIA SAMUEL
    Aug 05, 2021

    I want to learn more about LOGO SOFT work and actually programing logic control. I will be very happy is examples and exercises are sent to my email. Thanks so much.


  2. ali bouzkri
    Mar 20, 2021

    can this insulation test be applied to 3 phase heater and servo motors?


  3. IBRAHIMERAY
    Jan 13, 2021

    What about MV Motor insulation. We can not never run any MV motor with 10 Mohm IR value. My opinion is that it will be much more correct if voltage level of motor is mentioned in above article.

    Thanks for your sharings.


  4. Magdi siam
    Apr 16, 2020

    Ksa….. What is the different between the caculated value…. And the measured value? And How they are interconnected with different IR values?


  5. Alberto morada
    May 24, 2019

    I want learn more about electricity and motors control.so this blog very helpful forme


  6. Alberto morada
    May 24, 2019

    I want learn more about electricity and motors control.


  7. Biplob Sen
    Apr 24, 2019

    I would like to learning 3phase 5hp motor wiring . which is operating by PLC controller

Leave a Reply to AISIA SAMUEL

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

nine  ×  one  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).