Home / Technical Articles / Islanding in DER-Integrated Distribution Systems: Planning, Control, and Anti-Islanding Protection

Estimated Study Time: 33 minutes

Distributed Energy Resources (DERs)

The global energy landscape is undergoing a transformative shift, with Distributed Energy Resources (DERs) such as solar photovoltaics, wind turbines, battery energy storage systems, and controllable loads becoming increasingly prevalent in modern distribution networks.

Islanding in DER-Integrated Distribution Systems: Planning, Control, and Anti-Islanding Protection
Islanding in DER-Integrated Distribution Systems: Planning, Control, and Anti-Islanding Protection

This article explores the planning, control, and market integration aspects of DERs in future distribution grids, focusing on one of the most critical operational scenarios: island mode operation. When a portion of the grid operates autonomously, it must maintain voltage and frequency stability, ensure adequate load-generation balance, and protect against faults, all without support from the bulk power system.

These technical challenges are further compounded when transitioning between grid-connected and island states, where synchronization, protection coordination, and anti-islanding mechanisms become essential.

The distinction between intentional and unintentional islanding is vital for grid operators and DER designers. While intentional islanding, such as in microgrids or critical infrastructure, is a planned and controlled event, unintentional islanding poses serious risks including personnel safety hazards, equipment damage due to out-of-phase reconnection, and compromised protection reliability.

Detecting and preventing such scenarios requires a mix of passive, active, and communication-based techniques, each with specific strengths and limitations.

A central theme in the article is the role of inverter-based DERs, which dominate new installations. These systems operate as either grid-following or grid-forming inverters, each playing a distinct role in power system stability and control. Coordination between these inverter types is key to ensuring seamless transitions and stable island operation, especially as DER penetration increases.

The article also provides a brief review of the regulatory frameworks governing anti-islanding requirements across different regions, including IEEE 1547-2018 (USA), IEC 62116 (international), UL 1741 SA (USA), and G99 (UK). These standards define functional behavior, response times, and test procedures for DER anti-islanding capabilities, ensuring safety and interoperability in diverse grid environments.

By covering technical, operational, and regulatory dimensions, this article aims to provide utility engineers, protection specialists, and DER developers with a comprehensive understanding of island mode operation and anti-islanding protection in DER-integrated distribution systems.

As the power sector evolves toward a more decentralized architecture, mastering these aspects is crucial for maintaining grid reliability, enabling energy flexibility, and unlocking the full value of distributed generation.

Table of Contents:

  1. Island Mode Operation in Power Systems
    1. What is Island Mode?
  2. Types of Islanding:
    1. Intentional Islanding
    2. Unintentional Islanding
  3. Technical Implications of Island Mode Operation:
    1. Frequency and Voltage Control
    2. Protection Challenges
    3. Power Quality
    4. Resynchronization Risks
    5. Detection and Prevention
  4. Grid-Forming and Grid-Following Distributed Generation: Roles and Control Strategies:
    1. Grid-Following Distributed Generation
    2. Grid-Forming Distributed Generation
    3. Coordination Between Grid-Forming and Grid-Following Units
    4. Challenges in Islanding and Reconnection
    5. Future Outlook and Solutions
  5. Risks and Challenges of Unintentional Islanding:
    1. Safety Hazards to Utility Personnel
    2. Out-of-Phase Reconnection
    3. Loss of System Coordination
    4. Fault Detection and Clearance Challenges
  6. Islanding Detection Methods:
    1. Passive Detection Methods
    2. Active Detection Methods
    3. Communication-Based Detection Methods
  7. Anti-Islanding in Inverter-Based DERs:
    1. Key Functional Requirements:
      1. Fast Islanding Detection (≤2 Seconds)
      2. Cease Energizing the Grid Upon Island Detection
      3. Abnormal Voltage and Frequency Ride-Through
    2. Advanced Anti-Islanding Capabilities in Smart Inverters
  8. Regulatory and Compliance Considerations for Anti-Islanding in DER-Integrated Networks:
  9. Attachment (PDF) 🔗 Download ‘Distributed Generation Handbook”

1. Island Mode Operation in Power Systems

1.1 What is Island Mode?

Island mode (or islanding operation) refers to a condition where one or more generators continue to supply power to a portion of the electrical network that has become electrically isolated from the main utility grid. In this state, the generators operate independently, maintaining voltage and frequency without support from the larger power system.

Under normal operating conditions, generators, whether large synchronous machines or inverter-based resources, are synchronized with the grid. Synchronization ensures that frequency, voltage magnitude, and phase angle are matched within acceptable tolerances. Operating in parallel with the grid enhances overall system stability, increases short-circuit levels, improves fault detection sensitivity, and reduces voltage dips during disturbances.

However, in certain scenarios, a generator or group of generators may become isolated from the grid due to intentional switching operations or unintentional faults, such as:

When such disconnection occurs but the generator(s) continues to supply power to the local load, the system is said to be operating in island mode.

Go back to Content Table ↑


2. Types of Islanding

2.1 Intentional Islanding

Planned operation where local generation is designed to serve critical loads independently during grid outages (e.g., microgrids, emergency backup systems).


2.2 Unintentional Islanding

Occurs unexpectedly due to faults or protection actions. This condition is generally undesirable due to the safety and reliability risks involved, especially when inverter-based DERs are involved.

Watch Lesson – Generator island mode

Go back to Content Table ↑


3. Technical Implications of Island Mode Operation

3.1 Frequency and Voltage Control

In the absence of grid reference, the generator must independently regulate frequency and voltage. This is particularly challenging for inverter-based sources, which may require grid-forming capabilities.

Go back to Content Table ↑


3.2 Protection Challenges

Standard protection schemes may not function correctly due to reduced fault current levels and altered fault paths. This necessitates adaptive or island-specific protection settings.

Figure 1 – Schematic diagram of the island system

Schematic diagram of the island system
Figure 1 – Schematic diagram of the island system

Go back to Content Table ↑


3.3 Power Quality

Maintaining power quality becomes more difficult, as the inertia and damping normally provided by the grid are no longer available. Harmonics, flicker, and voltage fluctuations may increase.

Go back to Content Table ↑


3.4 Resynchronization Risks

If the island network is to be reconnected to the main grid, synchronization must again be ensured. Failure to do so can result in damaging transients or equipment failures.

Go back to Content Table ↑


3.5 Detection and Prevention

To avoid unsafe unintentional islanding, especially in systems with inverter-based DERs (like solar PV or battery storage), grid codes mandate islanding detection mechanisms. These include:

  • Passive techniques (monitoring voltage/frequency deviations)
  • Active techniques (injecting disturbances to detect loss of grid)
  • Communication-based schemes (transfer trip, SCADA-based disconnection)

Island mode operation is a critical aspect of modern power systems, especially as the penetration of distributed energy resources (DERs) increases. While intentional islanding through microgrids can enhance resilience, unintentional islanding poses safety and reliability concerns.

Understanding its mechanisms, implications, and protective requirements is essential for engineers working on grid integration and DER deployment.

Watch Lesson – Stability studies: Frequency, converter driven and resonance

Go back to Content Table ↑


4. Grid-Forming and Grid-Following Distributed Generation: Roles and Control Strategies

In modern distribution networks and microgrid systems, Distributed Generation (DG) units are generally categorized based on their control strategy into two major types: grid-forming and grid-following sources. These classifications are crucial for understanding how DG units interact with the power system, especially during transitions between grid-connected and islanded modes.


4.1 Grid-Following Distributed Generation

Grid-following inverters are current-controlled devices. They require a stable voltage and frequency reference from the main grid to operate. Their function is to inject a controlled amount of current (usually based on maximum power point tracking or reactive power control) into the network.

As a result, grid-following units cannot operate independently and must synchronize with an existing voltage waveform provided by either the utility grid or a grid-forming device.

Key Characteristics:

  • Dependent on external voltage/frequency reference
  • Typically used during grid-connected operation
  • Operate with phase-locked loop (PLL) to align with the grid
  • Simple control, suitable for large-scale solar PV and battery systems

Limitations:

  • Cannot support system voltage or frequency in island mode
  • Ineffective in black-start scenarios
  • Prone to instability in weak grid conditions

Figure 2 – Grid-Forming (right) and Grid-Following Distributed Generation (left)

Grid-Forming and Grid-Following Distributed Generation
Figure 2 – Grid-Forming and Grid-Following Distributed Generation

Go back to Content Table ↑


4.2 Grid-Forming Distributed Generation

Grid-forming inverters, on the other hand, are voltage-controlled devices. They can establish their own voltage and frequency reference and can operate autonomously. This makes them essential for islanded operation or in situations where the grid is unavailable or weak.

Grid-forming DGs are capable of black-start, voltage regulation, and even frequency regulation—functions traditionally provided by synchronous generators.

Membership Upgrade Required

This content is not available in your premium membership plan. Please upgrade your plan in order to access this content. You can choose an annually based Basic, Pro, or Enterprise membership plan. Subscribe and enjoy studying specialized technical articles, online video courses, electrical engineering guides, and papers.

With EEP’s premium membership, you get additional essence that enhances your knowledge and experience in low- medium- and high-voltage engineering fields.

Good to know: – Save 50% on all video courses with Enterprise plan.

Upgrade

Already a member? Log in here

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
Muhammad Kashif - Author at EEP-Electrical Engineering Portal

Muhammad Kashif

Muhammad Kashif Shamshad is an Electrical Engineer and has more than 17 years of experience in operation & maintenance, erection, testing project management, consultancy, supervision, and commissioning of Power Plant, GIS, and AIS high voltage substations ranging up to 500 kV HVAC & ±660kV HVDC more than ten years experience is with Siemens Saudi Arabia.
Profile: Muhammad Kashif

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!