Search

Premium Membership

Save 50% on all courses at the EEP Academy with the Enterprise Plan and study specialized technical articles, papers & video courses.

Home / Technical Articles / Medium voltage circuit breaker operating sequence

Rated switching sequence according to IEC, O – t – CO – t’ – CO. (cf. opposite diagram):

O – Represents opening operation
CO – Represents closing operation followed immediately by an opening operation

Three rated operating sequences exist:

  • Slow: O – 3 min – CO – 3 min – CO
  • Fast 1: O – 0.3 s – CO – 3 min – CO
  • Fast 2: O – 0.3 s – CO – 15 s – CO

NOTE: Other sequences can be requested from manufacturer.

Close/Open cycle

Assumption: O order as soon as the circuit breaker is closed

Close/Open cycle of medium voltage circuit breaker
Close/Open cycle of medium voltage circuit breaker

.
.

Automatic reclosing cycle

Assumption: C order as soon as the circuit breaker is open, (with time delay to achieve 0.3 s or 15 s or 3 min).

Automatic reclosing cycle of medium voltage circuit breaker
Automatic reclosing cycle of medium voltage circuit breaker
SOURCE: Schneider Electric – Medium Voltage Technical Guide

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
author-pic

Edvard Csanyi

Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV/MV switchgears and LV high power busbar trunking (<6300A) in power substations, commercial buildings and industry facilities. Professional in AutoCAD programming.

6 Comments


  1. Ihsan A. Oudah
    Aug 20, 2021

    Please can you share with me the short circuit calculation guide for the protection relays

    Thank you


  2. Muhammad Usman
    Mar 27, 2018

    Hello Sir!
    Please explain Auxiliary Contacts State (OW-OD-C) what mean by (OW, OD).
    Also help how ti analysis of timing graph of High voltage Breakers.
    Thanks!


  3. Erl Von Abong
    Jun 25, 2014

    Hello Sir,

    We have this rated operating sequence O-0.3s-CO-3min-CO VCB but our available unit have this rated operating sequence O-0.3s-CO-15s-CO.

    Is it OK to use?

    Please help.

    Thank you.


    • Kamal
      Sep 04, 2014

      I suppose,
      Requirement is O-0.3s-CO-3min-CO. And available VCB is O-0.3s-CO-15s-CO.
      15s VCB is suitable for autoreclosing application while 3 min VCB can’t.
      Although 15s VCB can be used in place of 3 min VCB with suitable delay timer in circuit of breaker.

      I hope it is the answer of your question.

      Regards
      Kamal


  4. sudamadhav
    Jan 07, 2013

    The article is quite not clear, i want a detailed explanation on this and where could i find articles or features or details about VCB’s. pls help

Leave a Reply to Erl Von Abong

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

eight  +  one  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
Design a safer and energy-efficient medium voltage installation