Single phase induction type energy meter is also popularly known as watt-hour meter. This name is given to it. This article is only focused about its constructional features and its working. Induction type energy meter essentially consists of following components:

1. Driving system
2. Moving system
3. Braking system and
4. Registering system

Driving system

It consists of two electromagnets, called “shunt” magnet and “series” magnet, of laminated construction. A coil having large number of turns of fine wire is wound on the middle limb of the shunt magnet.

This coil is known as “pressure or voltage” coil and is connected across the supply mains. This voltage coil has many turns and is arranged to be as highly inductive as possible. In other words, the voltage coil produces a high ratio of inductance to resistance.

This causes the current and therefore the flux, to lag the supply voltage by nearly 90 degree.
Single-phase induction kilowatt hour meter - Construction
Single-phase induction kilowatt hour meter - Construction

An adjustable copper shading rings are provided on the central limb of the shunt magnet to make the phase angle displacement between magnetic field set up by shunt magnet and supply voltage is approximately 90 degree.

The copper shading bands are also called the power factor compensator or compensating loop. The series electromagnet is energized by a coil, known as “current” coil which is connected in series with the load so that it carry the load current. The flux produced by this magnet is proportional to, and in phase with the load current.

Go to index ↑


Moving system

The moving system essentially consists of a light rotating aluminium disk mounted on a vertical spindle or shaft. The shaft that supports the aluminium disk is connected by a gear arrangement to the clock mechanism on the front of the meter to provide information that consumed energy by the load.

The time varying (sinusoidal) fluxes produced by shunt and series magnet induce eddy currents in the aluminium disc.

The interaction between these two magnetic fields and eddy currents set up a driving torque in the disc.

The number of rotations of the disk is therefore proportional to the energy consumed by the load in a certain time interval and is commonly measured in kilowatt-hours (Kwh).

Go to index ↑


Braking system

Damping of the disk is provided by a small permanent magnet, located diametrically opposite to the a.c magnets. The disk passes between the magnet gaps. The movement of rotating disc through the magnetic field crossing the air gap sets up eddy currents in the disc that reacts with the magnetic field and exerts a braking torque.

By changing the position of the brake magnet or diverting some of the flux there form, the speed of the rotating disc can be controlled.

Go to index ↑


Registering or Counting system

Single-phase induction kilowatt hour meter scheme
Single-phase induction kilowatt hour meter scheme

The registering or counting system essentially consists of gear train, driven either by worm or pinion gear on the disc shaft, which turns pointers that indicate on dials the number of times the disc has turned.

The energy meter thus determines and adds together or integrates all the instantaneous power values so that total energy used over a period is thus known.

Therefore, this type of meter is also called an “integrating” meter.

Working of Single phase induction type Energy Meter

The basic working of  Single phase induction type Energy Meter is only focused on two mechanisms:

  1. Mechanism of rotation of an aluminum disc which is made to rotate at a speed proportional to the power.
  2. Mechanism of counting and displaying the amount of energy transferred.

Lets have a look over these mechanism in few words:


Mechanism of rotation of an aluminum disc

Which is made to rotate at a speed proportional to the power.

The metallic disc is acted upon by two coils. One coil is connected 0r arranged in such a way that it produces a magnetic flux in proportion to the voltage and the other produces a magnetic flux in proportion to the current. The field of the voltage coil is delayed by 90 degrees using a lag coil.

This produces eddy currents in the disc and the effect is such that a force is exerted on the disc in proportion to the product of the instantaneous current and voltage.

A permanent magnet exerts an opposing force proportional to the speed of rotation of the disc – this acts as a brake which causes the disc to stop spinning when power stops being drawn rather than allowing it to spin faster and faster. This causes the disc to rotate at a speed proportional to the power being used.

Go to index ↑


Mechanism of displaying the amount of energy transferred

Based on number of rotation of aluminum disc.

The aluminum disc is supported by a spindle which has a worm gear which drives the register. The register is a series of dials which record the amount of energy used.

The dials may be of the cyclometer type, an odometer-like display that is easy to read where for each dial a single digit is shown through a window in the face of the meter, or of the pointer type where a pointer indicates each digit.

It should be noted that with the dial pointer type, adjacent pointers generally rotate in opposite directions due to the gearing mechanism.

Go to index ↑

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
author-pic

Bipul Raman

Bipul Raman (@BipulRaman) is a Technology Enthusiast, Programmer and Blogger. Read more at : https://www.bipul.in

25 Comments


  1. dheeravath maheshwari
    Jan 27, 2023

    Induction type energy meter disc which shape


  2. Anshul
    Nov 23, 2019

    If the permanent magnet move towards the aluminium disc the speed of disc will increase or decrease . Why?


    • Permanent magnet does not moves it just stops the speed of the disc whenever necessary 😊
      Nov 30, 2019

      Single phase induction type energy metre


    • Ranatunga
      Feb 26, 2021

      Answering this question may lead bad influence to the electrical community! 🤔


  3. Thokozani Hadebe
    Sep 19, 2019

    Good morning everyone, if you connected three energy kWh meters class 2 on a say consuming circuit that will run maybe 21 days, what is the expected kWh readings between each one of them.


  4. ismail
    Jul 13, 2019

    on the energy meter above, what is the meaning of 600r/kwh


    • Manikandan. M
      Oct 07, 2020

      Meaning for 600r/kwh. If energy meter rotating in 600 rotations, there was consumed 1 kwh(1 unit).


  5. chamod
    Nov 18, 2018

    what will be the performance where there are many different power factor load(linear non linear)?


    • Ross Klooster
      May 24, 2019

      A kWh meter is specifically designed to read only “real” energy and is unaffected by capacitance or inductance of the system. It is also theoretically unaffected by non linearity.


  6. Aditya
    Oct 12, 2018

    About
    Single phase dynamometer type energy meter


  7. Aniket S Naphade
    Apr 30, 2017

    What will happen if the current direction reverses in energy meter?
    Is it possible that meter starts rotating in reverse direction?


    • Ross Klooster
      Jul 07, 2018

      The answer to your question is yes. In a typical residential, single phase meter (Form 2S type) the upper two lugs are connected to utility source and lower lugs are connected to the house branch circuit panel. If the meter is inserted in the socket upside down, it will in fact rotate backward and subtract apparent energy usage from the register. Meters can be purchased with what is referred to as a “detent” which is a ratchet that does not allow a meter to turn backward. If installed upside down, a meter with a detent will simply not turn at all.


      • ruth
        Mar 27, 2019

        is there any difference between how the kwh hour usage is calculated compared to the newer watt hour meter. sse are telling me my meter is read as 1 unit = 1kwh. / But my meter says it has a kh factor of 3..0 . not 1.0kh. is there a difference between the 2


  8. Clint s
    Dec 27, 2016

    Why is electromagnetic induction technology mostly used in energy meters?


    • Ross Klooster
      Jul 07, 2018

      Electromagnetic, or perhaps electromechanical meters, were invented by Shallenberger, a Westinghouse electrician in the 1890’s and it was almost identical to such meters in modern usage. Prior to that, an electrochemical technique using electrolytic cells were sometimes used that required weighing the migration of a metal, such as zinc or mercury, from anode to cathode. Another method used Kelvin heating but I am not sure how this worked. These techniques were purported to be labor intensive as well as inaccurate. Modern, Shallenberger type meters are extremely accurate if applied correctly. Most electric utilities are phasing out electromechanical meters in favor of electronic meters which I don’t think improve accuracy, but have lower maintenance.


  9. appi
    Oct 05, 2016

    nice


  10. tony
    Sep 18, 2015

    From the specification shown on the energy meter above, what is the meaning of 10(20)A ,please?


    • Raymond
      Oct 24, 2015

      10 Amp is the nominal rating of the meter. 20 Amp the maximum rating within the accuracy class of the meter.


    • S.M. Saiful Islam
      Apr 17, 2016

      10A is the rated current and 20A is the highest current when the energy meter works accurately.


    • Ross Klooster
      Jul 07, 2018

      This is a non-North American meter since it is 50 Hz. I am from the U.S. so I am unfamiliar with this meter face labeling, but I think that this is what is referred to as the metering class or current rating of the meter. Assuming this the case, this meter is rated for nominally 10 amperes, or a maximum of 20 amperes for rated metering accuracy. If I have this correct, in the U.S., this meter is referred to as a “transformer rated” meter, meaning that it is designed to meter large services, in excess of 200 amperes. Current transformers are required in the main service wires, to scale the large current down to much lower current value, nominally 5 amperes. The energy consumption, as displayed by the meter register, is multiplied by the primary/secondary current ratio of current transformers to determine actual kWh consumption.


  11. Tom Giblin
    Jun 12, 2015

    With the meter disconnected, I’m getting a resistance of 600 ohms across the load side of the meter. Is this right?


    • ed
      Apr 07, 2016

      me to, I get 570 ohms. it must be the coils? seems like it would be a lot of power used,


  12. vikas
    Sep 16, 2014

    great…


  13. dhiraj ghadage
    Mar 12, 2014

    great explaination!I have read about this topic till now.


  14. snazrulla
    Aug 12, 2013

    I am looking to design an eddy current drive for a truck wheel that is still mounted on its hub or axle and suspended in air as in a situation to change the tire. The idea is simple. Make a “U”/shoe shaped magnet made out of laminations, provide shaded poles AC to reach the “Rim” which is either steel or aluminum that should act as the disc. The supply voltage is 115 single phase; or 200V, 3 phase.

Leave a Reply to Thokozani Hadebe

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

eleven  +    =  16

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
EEP Academy Courses - A hand crafted cutting-edge electrical engineering knowledge