Turns ratio between the windings

Power transformer turns ratio test is an AC low voltage test which determines the ratio of the high voltage winding to all other windings at no-load. The turns ratio test is performed on all taps of every winding.

Power Transformer Turns Ratio Test
Power Transformer Turns Ratio Test

The Transformer Turns Ratio tester (TTR) is device used to measure the turns ratio between the windings (example shown below).

Voltage is applied on the H marked leads and measured of the X marked lead by the test set.

Ratio measurements are conducted on all tap positions and calculated by dividing the induced voltage reading into the applied voltage value. When ratio tests are being made on three-phase transformers, the ratio is taken on one phase at a time with a three-phase TTR until the ratio measurements of all three phases are completed.

Figure 1 - Three-phase Transformer Turns Rati (TTR) Connection diagram.
Figure 1 – Three-phase Transformer Turns Rati (TTR) Connection diagram.

Measured ratio variations should be within 0.5% of the nameplate markings.

Some TTR can perform transformer ratio measurement and also assess if on-load tap changer contacts are making satisfactorily during its transition from one tap position to the next position.

Example of single phase, hand-cranked TTR - Transformer Turns Ratio Test Set
Example of single phase, hand-cranked TTR – Transformer Turns Ratio Test Set (Measures the turns ratio and exciting current of windings in power, potential and current transformers.)

Turns Ratio Test Procedure, Step by Step

Step 1.

Isolate the equipment, apply working grounds to all incoming and outgoing cables and disconnect all incoming and outgoing cables from the transformer bushing terminals connections.

Disconnected cables should have sufficient clearance from the switchgear terminals greater that the phase spacing distance. Use nylon rope to hold cable away from incoming and outgoing terminals as required.


Step 2.

Connect the H designated three-phase test lead with the military style connector at one end to the mating connection on the test set marked with an H. Ensure that the connector’s index notch lines up properly.


Step 3.

Connect the X designated three-phase test of lead military style connector at one end to the mating connection on the test set marked with an X. Ensure that the connector’s index notch lines up properly.


Step 4.

Connect the H1, H2, H3 designated test lead to the corresponding H1, H2, H3 transformer terminal / bushing. Connect the H0 test lead if H0 terminal/bushing is present.

Refer to Figure 1.


Step 5.

Connect the X1, X2, X3 designated test leads to the corresponding X1, X2,X3 transformer terminals / bushings. Connect the X0 test lead if X0 terminal/bushing is present.


Step 6.

Perform turns ratio measurements for all tap positions.


Step 7.

Confirm that the measured ratios is within 0.5% of the calculated ratios.

Important Note:

Transformers that have wye connections but do not have the neutral of the wye brought out shall be tested for ratio with three-phase power supply.

Any inequality in the magnetizing characteristics of the three phases will then result in a shift of the neutral and thereby cause unequal phase voltages. When such inequality is found, the connection should be changed, either to a delta or to a wye connection, and the line voltages measured.

When these are found to be equal to each other and the proper values (1.732 times the phase voltages when connected in wye), the ratio is correct.


Power Transformer Testing

Automatically measuring ratio and winding resistance of all taps/phases.

Reference: Substation Commissioning Course – Raymond Lee, Technical Trainer

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
author-pic

Edvard Csanyi

Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV/MV switchgears and LV high power busbar trunking (<6300A) in power substations, commercial buildings and industry facilities. Professional in AutoCAD programming.

17 Comments


  1. Samuel udo
    Oct 14, 2020

    Thank u sir for your brilliant explanation, apart from TTR meter which methods can I use to carry ratio test using multi meter.pls also attached diagrams .

Leave a Reply to Samuel udo

Tell us what you're thinking... we care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!