An impedance Z comprising a resistance R in series with a reactance X can be converted to an admittance Y comprising a conductance G in parallel with a susceptance B:

Y = Z -1 = 1 / (R + jX) = (R – jX) / (R2 + X2) = R / (R2 + X2) – jX / (R2 + X2) = G – jB
G = R / (R2 + X2) = R / |Z|2
B = X / (R2 + X2) = X / |Z|2

Using the polar form of impedance Z:

Y = 1 / |Z|Ðf = |Z| -1Ð-f = |Y|Ð-f = |Y|cosf – j|Y|sinf

Conversely, an admittance Y comprising a conductance G in parallel with a susceptance B can be converted to an impedance Z comprising a resistance R in series with a reactance X:

Z = Y -1 = 1 / (G – jB) = (G + jB) / (G2 + B2) = G / (G2 + B2) + jB / (G2 + B2) = R + jX
R = G / (G2 + B2) = G / |Y|2
X = B / (G2 + B2) = B / |Y|2

Using the polar form of admittance Y:

Z = 1 / |Y|Ð-f = |Y| -1Ðf = |Z|Ðf = |Z|cosf + j|Z|sinf

The total impedance ZS of impedances Z1, Z2, Z3,… connected in series is:

ZS = Z1 + Z1 + Z1 +…

The total admittance YP of admittances Y1, Y2, Y3,… connected in parallel is:

YP = Y1 + Y1 + Y1 +…

In summary:
– use impedances when operating on series circuits,
– use admittances when operating on parallel circuits.

NOTATION
The symbol font is used for some notation and formulae. If the Greek symbols for alpha beta delta do not appear here [ a b d ] the symbol font needs to be installed for correct display of notation and formulae.
B
C
E
f
G
h
I
j
L
P
Q
susceptance
capacitance
voltage source
frequency
conductance
h-operator
current
j-operator
inductance
active power
reactive power
[siemens, S]
[farads, F]
[volts, V]
[hertz, Hz]
[siemens, S]
[1Ð120°]
[amps, A]
[1Ð90°]
[henrys, H]
[watts, W]
[VAreactive, VArs]
Q
R
S
t
V
W
X
Y
Z
f
w
quality factor
resistance
apparent power
time
voltage drop
energy
reactance
admittance
impedance
phase angle
angular frequency
[number]
[ohms, W]
[volt-amps, VA]
[seconds, s]
[volts, V]
[joules, J]
[ohms, W]
[siemens, S]
[ohms, W]
[degrees, °]
[rad/sec]

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information

One Comment


  1. Ihsan
    Mar 30, 2020

    I am interested of load flow , Distributed Generation , security systems, contingency ranking,power flow performance index(PI) and voltage stability index(Lmn).Also programming load flow and indices.

Leave a Comment

Tell us what you're thinking... we care about your opinion!

Subscribe to Weekly Digest

Get email alert whenever we publish new electrical guides and articles.

New Online Training Courses

World class online training for electrical engineers and industrial electricians.