If a node in a power system operating at frequency f has a inductive source reactance XL per phase and has power factor correction with a capacitive reactance XC per phase, the source inductance L and the correction capacitance C are:

L = XL / w

C = 1 / wXC

where w = 2pf

The series resonance angular frequency wr of an inductance L with a capacitance C is:

wr = (1 / LC)½ = w(XC / XL)½

The three phase fault level Ssc at the node for no-load phase voltage E and source impedance Z per-phase star is:

Ssc = 3E2 / |Z| = 3E2 / |R + jXL|

If the ratio XL / R of the source impedance Z is sufficiently large, |Z| » XL so that:

Ssc » 3E2 / XL

The reactive power rating QC of the power factor correction capacitors for a capacitive reactance XC per phase at phase voltage E is:

QC = 3E2 / XC

The harmonic number fr / f of the series resonance of XL with XC is:

fr / f = wr / w = (XC / XL)½ » (Ssc / QC)½

Note that the ratio XL / XC which results in a harmonic number fr / f is:

XL / XC = 1 / ( fr / f )2

so for fr / f to be equal to the geometric mean of the third and fifth harmonics:

fr / f = Ö15 = 3.873

XL / XC = 1 / 15 = 0.067

NOTATION
The symbol font is used for some notation and formulae. If the Greek symbols for alpha beta delta do not appear here [ a b d ] the symbol font needs to be installed for correct display of notation and formulae.
B
C
E
f
G
h
I
j
L
P
Q
susceptance
capacitance
voltage source
frequency
conductance
h-operator
current
j-operator
inductance
active power
reactive power
[siemens, S]
[farads, F]
[volts, V]
[hertz, Hz]
[siemens, S]
[1Ð120°]
[amps, A]
[1Ð90°]
[henrys, H]
[watts, W]
[VAreactive, VArs]
Q
R
S
t
V
W
X
Y
Z
f
w
quality factor
resistance
apparent power
time
voltage drop
energy
reactance
admittance
impedance
phase angle
angular frequency
[number]
[ohms, W]
[volt-amps, VA]
[seconds, s]
[volts, V]
[joules, J]
[ohms, W]
[siemens, S]
[ohms, W]
[degrees, °]
[rad/sec]

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information

Leave a Comment

Tell us what you're thinking... we care about your opinion!

Subscribe to Weekly Digest

Get email alert whenever we publish new electrical guides and articles.

New Online Training Courses

World class online training for electrical engineers and industrial electricians.